At least 19 records

T-Type Modular DC Circuit Breaker (T-Breaker) for Future DC Networks

The developed T-Type Modular DC Circuit Breaker (T-Breaker) technology offers an all-in-one solution to challenges in DC networks. This includes swift fault detection and protection, power transient stability, and power quality improvement, achieved through the utilization of wide bandgap (WBG) power semiconductors and energy storage devices. The T-Breaker not only facilitates rapid fault current detection and interruption but also implements fault current limiting through active insertion of storage devices or by operating WBG devices in the saturation region. Additionally, with the assistance of energy storage devices, potential overvoltage issues on power devices induced by control signal misalignment can be mitigated. The T-Breaker can be regulated to perform shunt current injection/absorption using the vertical arm and series voltage insertion via the horizontal arm, thereby enhancing DC system stability during voltage or load power fluctuation transients. The OSU team and Raytheon team actively worked together on designing, fabricating, assembling, and testing of two T-Breaker prototypes. The first prototype is rated at 1 kV, 500 A with half-bridge (unipolar) structure to validate the T-Breaker concept. The second prototype is rated at 20 kV, 50 A with full-bridge (bipolar) topology which can reach an efficiency of 99.977%, realize a power density of 60.2 MW/m3, and eliminate the 500-A fault current with a fault response time of around 20 µs. The prototypes show great feasibility of adopting this technology in multiple applications including electrified aircraft, super charging stations, data centers, etc.

24 POWER TRANSMISSION AND DISTRIBUTION↗

SCR-based Medium Voltage DC Solid-State Circuit Breaker

This paper describes a medium voltage solid-state circuit breaker (SSCB) based on SCR technology, featuring short fault-interruption time and a minimal turn-off auxiliary circuit. The SSCB design incorporates a specialized SCR and a commutation circuit designed with an objective to reduce the required SCR hold-off/turn-off time, tq, which primarily determines the fault interruption duration. To validate the design, simulation analysis is presented, and a 1.5 kV 300 A SSCB prototype has been built and tested. The results confirm the effectiveness of the proposed design philosophy demonstrating the SSCB's ability to interrupt a 200 A load current in less than 50 μs. The proposed SCR-based SSCB has been developed for DC applications but is equally applicable to AC applications.

Kandula, Prasad [ORNL] (ORCID:0000000174017284)↗

Fast, Controllable, and Modular Solid-State Circuit Breaker Design for Battery Management Systems

Electric power grid is experiencing a growing number of distributed and inertia-free generation resources. To facilitate the growing generation and load demands, and ensure stable operation, energy storage systems, especially behind-themeter-storage (BTMS), have emerged as a potential candidate. BTMS plays a vital role in the grid storage sector and supports high power charging for EVs. However, the potential of thermal runaway and associated safety concerns in the batteries can hamper their widespread adoption. In this work, we provide a solution for a fast and controllable discharge of a cell that was identified as a stressful/faulty, in the battery pack, and fast circuit breaking leveraging the Solid-State Circuit Breaker (SSCB) technology which provides active control over the cell connection as opposed to conventional passive solutions. Testing on the simulation platform successfully validated the concept, demonstrating its efficacy. Controlled discharge testing with 20Ah LiFePO4 Lithium Iron Phosphate (LFP) cells from 1C-10C current rate on the hardware prototype corroborated simulation results, demonstrating design feasibility and providing essential data for its performance and thermal characteristics, while also revealing limitations that inform areas for further optimization.

33 ADVANCED PROPULSION SYSTEMS↗

Wide bandgap optical switch circuit breaker for controlling propagation of current therethrough a wide bandgap optical device

A high-voltage switch is adapted for use as a medium-voltage direct current circuit breaker, which provides a low-cost, small-footprint device to mitigate system faults. In one example, a method for operating a wideband optical device includes illuminating the wide bandgap optical device with a light within a first range of wavelengths and a first average intensity, allowing a current to propagate therethrough without substantial absorption of the current, illuminating the wide bandgap optical device with light within the first range of wavelengths and a second average intensity that is lower than the first average intensity to allow a sustained current flow though the wide bandgap optical device, and illuminating the wide bandgap optical device with light within a second range of wavelengths to stop or substantially restrict propagation of the current through the wide gap material.

Voss, Lars F.↗

Reliability Assessment of Solid-State Circuit Breakers (CRADA CRD-21-21469, Project 4 Final Report)

Growth in power requirements and the complexity of emerging distribution systems are creating the need for new solid-state products for many applications. The qualification requirements, testing standards and life-cycle management practices of solid-state devices used in protection applications is not established. The project will leverage newly developed accelerated testing capabilities design specifically for protection applications to generate large data sets that will enable advanced digital techniques for data analysis and embedded health monitoring.

14 SOLAR ENERGY↗

ION Work Reduction Opportunity Realization Demonstration

The purpose of this research was to realize one of the advanced training work reduction opportunities first presented in the Idaho National Laboratory (INL) report, “Process for Significant Nuclear Work Function Innovation Based on Integrated Operations Concepts” (INL/EXT-21-64134) [1], with a nuclear power plant (NPP) research partner. Researchers modernized two trainings: (1) an accredited instructor-led training (ILT) overview course on Westinghouse DS 480-volt (V) circuit breakers to a multimedia-focused computer-based-training (CBT) learning module, and (2) an on-demand chaptered video on how to properly rack and un-rack a Westinghouse DS 480-V circuit breaker. These modernized work products were developed and implemented in a manner consistent with the industry guidelines found in Institution of Nuclear Power Operations (INPO) Teaching and Learning 23-001 [2]. Researchers calculated that the modernized accredited training course reduced the time necessary to prepare and deliver the training material by a factor of 8:1. The amount of time learners spend in class could be reduced by this same factor. In other words, if a course took 8 hours to deliver a class, the new CBT instruction would take just over 1 hour. The researchers noted that the requirement for any practicum training by the learners with the instructor(s) would remain in place. But through interviews with new and experienced learners, the researchers discovered that the confidence of these learners in performing the racking and un-racking of the circuit breaker improved as a result of using the new modernized CBT process. Additionally, the learners who tested the modernized work products enjoyed the modernized CBT and the learning video significantly more than current in-class learning methods. These are encouraging results for the nuclear industry, as this modernization of training can be applied to other classes and is scalable across the industry. In line with the Integrated Operations for Nuclear (ION) model, positive workload analysis supports the investment of resources in modernizing NPP training processes and infrastructure. Implementation of the advanced training technologies in this report is likely to result in substantive long-term workload benefits to instructors and learners and result in hard-dollar savings on contractor spends. Additionally, investment in these modernized training processes will result in improved learner proficiency. The results of this research can be applied to additional operator, technical, and general training topics to provide additional workload and learning benefits in addition to what was explored.

42 ENGINEERING↗

Decentralized Microgrid Protection Through Relative Fault Direction Classification: Preprint

Protection in inverter-based resources (IBRs) dominated microgrids generally face significant challenges due to the low fault current and inconsistent fault behaviors from IBRs. Recently, machine learning-based approaches have attracted considerable attention to address these challenges. This paper introduces a novel decentralized protection strategy for microgrids. The proposed method decomposes the protection challenge into several distributed learning tasks, enabling individual relays to autonomously determine the direction of faults using a binary classification framework based on support vector machine (SVM) algorithms. Following the distributed fault direction estimation, classifier outcomes are shared among neighboring relays, facilitating a local decision-making process to ascertain the presence of faults within the neighborhood. Finally, a tripping signal is generated based on the classifier results of each relay to operate the circuit breaker. To test and validate this approach, a 100% renewable microgrid model is simulated in MATLAB/Simulink. In the numerical analysis, the application of SVM classifiers in our approach yields impressive results: an average relay classification accuracy of 98%, and a 96% accuracy in circuit breaker control. These findings highlight the potential of machine-learning-based approaches in enhancing the efficiency and reliability of microgrid protection systems.

decentralized algorithm↗

Intelligent, grid-friendly, modular extreme fast charging system with solid-state DC protection

The development of electric vehicle (EV) charging infrastructure is crucial for the widespread adoption of electric transportation. However, implementing such infrastructure is a complex task that requires consideration of factors such as space limitations, adherence to industry standards, grid capacity, and other technical and policy issues. This project seeks to create a framework for the efficient design of compact medium voltage (MV) extreme fast charging (XFC) stations for EVs. The station design involves the use of a solid-state transformer (SST) that connects to the MV distribution network, delivering power to a shared DC bus. This innovative approach eliminates the need for a step-down transformer to provide low-voltage service by connecting directly to the MV distribution network. Eliminating the low-frequency transformer not only reduces the system footprint and losses but also eliminates inrush currents during grid black-start. Additionally, placing power electronics directly on the distribution system allows for high-bandwidth filtering and power factor correction. The inclusion of a shared DC bus enables multiple charging dispensers and DC storage/generation units to connect, forming a DC microgrid. This setup facilitates power sharing with minimal conversion stages. The project showcases a DC distribution network protected by intelligent solid-state (SS) DC circuit breakers (DCCB) capable of isolating the smallest section of the faulted circuit much faster than existing mechanical solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Characterizing electrical panel capacity, breaker space, and loads in U.S. single-family homes

Electrical panels distribute electricity to appliances, equipment, and other building loads and maintain safety by preventing overloads of branch circuits, feeders, and utility service wires connecting homes to the grid. Load calculations in the National Electrical Code (NEC) determine the capacity of installed electrical panels in the United States, which are rated in amps (A). Circuit breakers within electrical panels affect the magnitude and number of loads that panels can serve. In home retrofits and renovations, existing electrical panels may not accommodate new electrical loads, either due to insufficient electrical capacity or a lack of available breaker spaces. Homes with these panel constraints may need to replace existing panels with new panels that have greater capacity and breaker space.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Forming Inverter With Increased Short-Circuit Contribution to Address Inverter-Based Microgrid Protection Challenges

Substantial differences in fault levels between grid-tied and islanded modes is one of the primary challenges of microgrid protection. During grid-tied mode, the bulk grid provides significant short-circuit, while during islanded operation the short-circuit magnitude is small due to inverter-based resources limiting their current output close to nominal ratings. Consequently, conventional distribution protection strategies based on overcurrent cannot reliably protect microgrids when operating in islanded mode. Fuses and circuit breakers are particularly affected because of their inverse characteristics. Presently, the absence of affordable solutions for protecting microgrids in islanded mode leads to microgrids shutting down during electrical faults. The contribution of this article is two-fold. The first innovation proposes specific hardware modifications to grid-forming inverters to increase their short-circuit current during electrical faults. The second innovation introduces a novel control strategy designed to preserve control stability margins even when the grid-filter saturates, ensuring sinusoidal output currents under normal and fault conditions. Through experimental results, the inverter with the proposed modifications can provide more than three-times its nominal current during electrical faults. For the prototype testbed, this was sufficient to enable the use of traditional legacy overcurrent protection, achieving the fuse-to-relay and relay-to-relay minimum coordination time for the line-to-ground, line-to-line to ground, and three-phase electrical faults.

42 ENGINEERING↗

End-to-end microgrid protection using distributed data-driven methods

This paper introduces an end-to-end microgrid protection framework that offers real-time system monitoring, fault-related decision making, and circuit breaker control. This is achieved through the design of distributed data-driven techniques based on the support vector machine method, where each relay is responsible for distributed data collection, fault detection, fault localization, and fault isolation. Local communication is established among neighboring relays, fostering cooperative fault localization and isolation. This decentralized design not only reduces the computational and communication requirements but also enables the adaptability of each relay under varying operational dynamics. The proposed end-to-end protection framework was validated using MATLAB/Simulink simulations on a 100% renewable microgrid, achieving an accuracy of 93.1% with response time of 0.0523 s, in protecting against a range of fault scenarios that are characterized by various types, locations, impedances, load conditions, photovoltaic power levels, and microgrid operating modes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Adaptive Fault Current-Limiting Control of MMC for Protection of Multiterminal HVDC Systems

A crucial requirement of the protection system for multi-terminal high-voltage DC (MTDC) transmission is that it is capable of selectively isolating the faulty area from the healthy part of the network using DC circuit breakers (DCCBs), while ensuring continuous operation of converter stations in the healthy part of the network. But in the half-bridge modular multilevel converters (HB-MMCs) based MTDC system, since HB-MMCs do not have fault current absorption capability, when a DC fault occurs, the rising fault currents can quickly reach the blocking threshold within a few milliseconds and disrupt the operation of the MMCs in the healthy part. To facilitate fault-ride-through capability of MTDC system, large DC reactors are often considered in series with DCCBs to reduce the rate of rise of the fault current and prevent blocking the MMCs in the healthy part of the DC networks; however, large DC reactors prohibitively increase the cost of the system, introduce stability issues and can create post-fault oscillations. This paper presents an adaptive fault current-limiting control method for MMCs to avoid their blocking and enable the continuous operation of the healthy part of MTDC systems. The method contains two parts: The first part is based on circulating current feedforward control, which emulates virtual reactors in each arm of an MMC, and is immediately activated when the fault current starts to increase to reduce the rate of rise of the fault current. The second part temporarily bypasses all the submodules when the fault current exceeds a preset threshold, complementing the fault current-limiting effect of the first part. Neither part requires fault detection signals, and they are automatically activated during faults. Simulation case studies of a four-terminal bipolar MMC-based high-voltage DC system are presented to demonstrate the effectiveness of the proposed control methods.

active fault current limiting↗

Adaptive Linear State Estimation for Unbalanced Distribution System

The inclusion of PMU functionality in distribution relays enables the implementation of a linear state estimator (LSE) in Distribution Systems (DS). However, the unbalanced topology and phase coupling in distribution lines necessitate modifications to the LSE formulation. Additionally, the higher fault frequency in distribution systems requires a state estimation approach that is resilient to contingencies. This work proposes an adaptive linear state estimation algorithm tailored for unbalanced distribution systems with single-phase and two-phase laterals. Furthermore, a modified Optimal PMU Placement (OPP) strategy is introduced to ensure full observability in distribution systems with single-phase and two-phase buses. To maintain adaptability to topology changes, the state estimator incorporates circuit breaker status data provided by PMUs, ensuring robust performance during topology changes triggered by faults. The performance of the algorithm is verified on the IEEE 13-bus, 34-bus, and 123-bus systems.

PMUs↗

On the Impact of High-Order Harmonic Generation in Electrical Distribution Systems

The modern power grid has seen a rise in the integration of non-linear loads, presenting a significant concern for operators. These loads introduce unwanted harmonics, leading to potential issues such as overheating and improper functioning of circuit breakers. In pursuing a more sustainable grid, the adoption of electric vehicles (EVs) and photovoltaic (PV) systems in residential networks has increased. Understanding and examining the effects of high-order harmonic frequencies beyond $1.5$ kHz is crucial to understanding their impact on the operation and planning of electrical distribution systems under varying nonlinear loading conditions. This study investigates a diverse set of critical power electronic loads within a household modeled using PSCAD/EMTdc, analyzing their unique harmonic spectra. This information is utilized to run the time-series harmonic analysis program in OpenDSS on a modified IEEE 34 bus test system model. The impact of high-order harmonics is quantified using metrics that evaluate total harmonic distortion (THD), transformer harmonic-driven eddy current loss component, and propagation of harmonics from the source to the substation transformer.

Peerzada, Aaqib A. [BATTELLE (PACIFIC NW LAB)]↗

Guest Editorial Special Section on Advanced Medium-Voltage Power Electronics for Grid Interactive Applications

Medium-voltage power electronics (MVPE) plays essential roles in power grid modernization and links the MV distribution grid with low-voltage consumers and prosumers. Various MVPE devices, such as solid-state transformers or circuit breakers, inverter-based resources, power flow controllers, etc., bring the benefits of voltage conversion and power regulation in small footprint, power quality and efficiency improvements, and enhancements of grid controllability, flexibility, stability, and resilience. The MVPE also makes it possible for sustainable energy systems, such as solar/wind farms and energy storage generating facilities, to directly access to MV grids without multistage conversions. With their intrinsic intelligence and communications, MVPE enables many new smart grid functions and applications, e.g., dc interconnections and electric vehicle charging, which were not envisioned by traditional power grids otherwise. In addition, the integration of physical power processing units with cyber components forms a cyber-physical system, which is essential for long-term sustainability, development, and environmental preservation. Nonetheless, technical challenges on MVPE device reliability, scalable and efficient converter topologies, control stability, large-scale modeling and simulation, to name a few, need to be addressed and advanced to the next level. In conclusion, this Special Section on Advanced MV Power Electronics for Grid Interactive Applications in IEEE Transactions on Power Electronics (TPEL) provides an insight on some of the recent advances in MVPE and emerging challenges and potential solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Integrating a Microgrid Controller with a Local OpenADR Server

When military microgrids isolate themselves from the main electrical grid, they must locally balance electricity supply and demand. Since local generation may be limited, the current strategy is to shed all but the most critical loads by tripping smart circuit breakers, which must then be reset manually (e.g., ESTCP project EW-201350). This strategy is typically applied at the building level, meaning that entire buildings housing mission critical activities must be excluded from any load management, while those considered non-critical may lose service entirely. The remotely controlled switchgear needed to manage load in this way is very expensive ($\$30,000$-$\$50,000$ per building). While effective at shedding load, this strategy disrupts installation operation and risks damaging equipment during both disconnection and re-energization. With the goals of lowering costs, protecting equipment, and enhancing the agility of DoD microgrids, this report demonstrates the use of cybersecure automated demand response (ADR) technology to manage microgrid loads during grid-independent (a.k.a. "islanded") operation. This automated approach achieves load shedding and shifting through communication signals sent to equipment controllers rather than by cutting off the flow of electricity within the microgrid itself. Because it operates only on the base network, with no connection to external entities, this strategy avoids the main cybersecurity concern raised by past applications of ADR on military bases.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Demonstration of a Novel Technology to Manage Electricity Demand in Grid-Independent Military Microgrids

This research was conducted by the National Renewable Energy Laboratory (NREL) in collaboration with the S&C Electric Inc. through funding provided by the ESTCP. The project demonstrates use of cybersecure Automated Demand Response (ADR) technology to effectively manage microgrid loads during grid-independent, also known as "islanded," operation. When military microgrids become isolated from the main electrical grid, they are required to balance electricity supply and demand locally. Given that local generation may be constrained, the prevailing strategy involves shedding all but the most critical loads by tripping smart circuit breakers, which then necessitate manual resetting. This approach is generally implemented at the building level, which means that the buildings with mission-critical activities are exempt from load management and remain fully powered, whereas those deemed non-critical can experience a complete loss of service. In this research we developed a method that allows building automation systems to selectively control their assets in response to load shedding request from a microgrid controller, avoiding total loss of service in contrast to the conventional control approach. A commercial OpenADR client server by GridFabric is used for communication between the microgrid controller and the building management system (BMS). The microgrid controller monitors both generation capacity and various assets within the microgrid and issues a demand reduction request when necessary. This request is communicated to the OpenADR server via Modbus. Upon receiving the request, the OpenADR server forwards it to the BMS utilizing the OpenADR protocol. The BMS is pre-configured with various levels of load reduction strategies based on the controllable assets available, allowing for a nuanced approach to demand reduction. Both lab and field tests were performed that considered load shedding needed to achieve closed transition into island mode and to accommodate changing loads and power source availability while islanded. A commercial microgrid controller was used for these tests with normal programming within the expected constraints of the system capabilities. That is, the solution did not require any specialized modification to the code base of the controller. Given the latency of the round-trip communication path between the microgrid controller and the various devices involved with the load shed processes, there are certain scenarios for which the demonstrated solution are appropriate and some which are not. The methods described in this report can be used for load shedding/restoration during transitions between islanded and grid-tied modes of operation, as well as accommodating normal variations in load and the need to remove a power source from operation for maintenance. These methods should not be used for scenarios that require load shedding within a second or two such as sudden and unanticipated significant load increases or loss of power sources through equipment faults.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Informing Transmission Supply Chain Needs from National Transmission Studies

Recent national studies indicate significant transmission expansion can provide the lowest-cost option to maintain grid reliability while meeting growing demand. However, constraints in domestic supply chains may limit grid expansion across the U.S., with higher costs and longer delays for required transmission equipment. Despite growing evidence of supply chain constraints for transmission components, transmission planning studies often assume transmission equipment is readily available for deployment or analyze future demand using historical trade and manufacturing data that may not capture evolving grid needs. This report aims to address this gap by demonstrating methods to quantify future demand for critical transmission components and input materials from national-scale planning models. These components include power transformers, generator step-up transformers, converter transformers, conductors, circuit breakers, and transmission towers and the materials include aluminum, steel, grain-oriented electrical steel (GOES), and copper. The analytical approach is applied to two nodal transmission expansion scenarios from the National Transmission Planning Study (NTP) to illustrate the methods. These scenarios represent different transmission expansion strategies for the contiguous U.S. to the year 2035: the Alternating Current (AC) scenario includes AC transmission expansion within each interconnection and the Multiterminal (MT) scenario includes interregional transmission expansion across the country using both AC and multiterminal HVDC options between neighboring zones. We also explore potential heuristics to derive transmission component demand from zonal capacity expansion models (CEMs) with coarse representation of the transmission grid.