Engineering PapersSearch

DOE OSTI · 2554065

Adaptive Linear State Estimation for Unbalanced Distribution System

Abstract

The inclusion of PMU functionality in distribution relays enables the implementation of a linear state estimator (LSE) in Distribution Systems (DS). However, the unbalanced topology and phase coupling in distribution lines necessitate modifications to the LSE formulation. Additionally, the higher fault frequency in distribution systems requires a state estimation approach that is resilient to contingencies. This work proposes an adaptive linear state estimation algorithm tailored for unbalanced distribution systems with single-phase and two-phase laterals. Furthermore, a modified Optimal PMU Placement (OPP) strategy is introduced to ensure full observability in distribution systems with single-phase and two-phase buses. To maintain adaptability to topology changes, the state estimator incorporates circuit breaker status data provided by PMUs, ensuring robust performance during topology changes triggered by faults. The performance of the algorithm is verified on the IEEE 13-bus, 34-bus, and 123-bus systems.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Zhou, Yijie [Virginia Polytechnic Inst. and State Univ. (Virginia Tech), Blacksburg, VA (United States)] (ORCID:0009000698969662), Centeno, Virgilio [Virginia Polytechnic Inst. and State Univ. (Virginia Tech), Blacksburg, VA (United States)] (ORCID:0000000192306522). 2025-04-10. Adaptive Linear State Estimation for Unbalanced Distribution System. https://doi.org/10.1109/access.2025.3559792

Cite the original work for its findings. Save a collection to share your selection of sources.