Experimental study of a thermal energy storage-integrated heat pump system for load shifting in space cooling and heating
This study experimentally investigates an all-season thermal energy storage-integrated heat pump (TES-HP) system developed to enhance building energy efficiency and support grid-interactive operation through load shifting in both cooling and heating. A 4-ton commercial rooftop air-source heat pump was modified by integrating a hydronic thermal energy storage (TES) unit containing a phase change material (PCM) with a melting temperature of 22.0 °C. The system employs two reversing valves and three electronic expansion valves to enable six operating modes, including normal, TES charging, and TES discharging in both cooling and heating seasons. A subcooling-controlled electronic expansion valve was implemented to mitigate refrigerant maldistribution caused by unequal internal volumes among the heat exchangers. Compared with a baseline heat pump, the TES-HP reduced power consumption by 30–50% during cooling at an ambient temperature of 40.6 °C, and by up to 60% during heating at −15.0 °C, while maintaining high performance under cold-climate conditions. Additionaly to experimental evaluation, a simplified annualized on-peak analysis was conducted to compare the TES-HP with the baseline system, indicating an on-peak electricity reduction of approximately 876 kWhₑ per unit per year and associated on-peak cost savings under time-of-use pricing. These results demonstrate that the TES-HP effectively decouples HP operation from adverse ambient conditions, improving flexibility, resilience, and energy efficiency. This work advances prior research by experimentally proving the integration of PCM-based TES for a year-round, load-flexible HVAC operation.