Hierarchical Data-Driven Protection for Microgrid with 100% Renewable Penetration: Preprint

The accurate detection and isolation of faults is critical for the reliable operation of microgrids (MGs). Traditional protection approaches are even more challenged for 100% renewable MGs because inverter-based resources (IBRs) are the only sources for fault current which are usually low and unpredictable/non-uniform. This calls for new protection scheme that can identify IBR fault responses and detect faults in MGs. Data-driven based protection can learn the pattern of IBR fault responses and make the correct decision to identify faults. Therefore, this paper presents a data-driven approach for fault localization in island MGs. The approach builds a training dataset of comprehensive fault scenarios that can be used to learn fault characteristics from processed measurements. The localization task is modeled as a binary classification problem at each relay, which simplifies the learning process. Then, a hierarchical decision mechanism is used to identify the fault location. The proposed approach is assessed using an exemplary MG with several grid-forming (GFM) and grid-following (GFL) inverters, where accurate estimation of fault location is achieved. The data-driven based protection approach developed in this paper provides a generic framework and useful guidance for power system protection engineers to achieve reliable protection for MGs with 100% renewables.

artificial intelligence↗

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters

As increasingly more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMS) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states.For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; altogether, the control algorithms seamlessly connect the states into a generic microgrid EMS that controls the nodal voltages and frequencies, becomes a virtual power plant (VPP) when connected to the main grid, and coordinates power sharing responsibility among GFM sources when islanded. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management system↗

Control and Real-Time Simulation of Microgrids with EV Fast-Charging and Grid-Forming Resources

Fast charging stations (FCSs) for electric vehicles (EVs) can behave as constant power loads, which is problematic for the operation of grid-forming (GFM) inverter-based resources (IBRs). To tackle this problem, this paper proposes a control suite that makes FCSs responsive to ac voltage and frequency disturbances. To test the performance of the FCS controls, the paper also sets forth theory to compensate for time-delays appearing in the real-time simulation of microgrid models divided into several central processing units (CPUs). Furthermore, these contributions are showcased via multi-CPU real-time simulations of a faulted microgrid having EV FCSs and GFM IBRs powered by photovoltaic solar arrays as well as power hardware-in-the-loop experiments. These contributions are significant to address NERC recommendations and IEEE standards.

14 SOLAR ENERGY↗

Adaptive Protection and Validated Models to Enable Deployment of High Penetrations of Solar PV (PV-MOD)

The availability and validation of various PV models in commercial tools differ, with some models not yet thoroughly validated for advanced inverter functionalities and reliable performance under weak system conditions. Many existing models do not fully incorporate new inverter control functions, which can affect system stability. The increasing deployment of solar PV and other inverter-based resources (IBRs), including distributed energy resources (DERs), is influencing the reliable operation of protection schemes in distribution systems and microgrids. Emerging adaptive protection schemes (APS) offer new opportunities for protecting these systems during varying configurations and DER operating conditions, though their demonstration and validation remain limited. Adaptive protection schemes face similar challenges, as they are typically designed for specific configurations. There is a growing need for tools and methodologies to streamline the deployment of adaptive protection for safe and reliable DER integration. The project main objective was to develop and validate high-fidelity generic models of solar PV facilities for stability, protection, EMT, and QSTS analyses. This objective was achieved, and these models can now be integrated into commercial software tools, enabling utilities, vendors, and developers to study high-penetration PV systems more confidently. The project also demonstrated advanced applications of these models, including the design and deployment of adaptive protection schemes in high-penetration field applications and microgrids, supporting grid safety and reliability. Several milestones were reached by the end of the project. A sophisticated inverter test plan was developed, and inverters representative of the North American marketplace were selected. EPRI and NREL tested various inverters, conforming to IEEE standards. Improvements were made to existing generic models of IBR units, IBR plants, and aggregated feeders for various analyses. The first generic electromagnetic transient (EMT) model for a solar PV plant was developed, conforming to IEEE Std 2800™-2022 and validated against laboratory measurements of a 2.2 MVA large-scale battery energy storage system (BESS) inverter. That model was then used to produce reference responses illustrating examples of validated and verified IBR plant models that pass or fail tests for technical minimum capability and performance as specified in the IEEE standard. The developed, tested, and validated generic models can be used for transmission planning, stability assessments, expansion planning, and evaluating potential future IBR interconnection requirements. They can also support interconnection screens and conformity assessments of IBR plants, including solar PV. The project significantly contributed to the ongoing standardization and model-based representation and verification of IBR responses. The project further addressed challenges of common distribution protection schemes with increasing deployment of DER by developing, validating, and demonstrating adaptive protection schemes (APS) that can improve the reliable and safe integration of DER into distribution systems. New APS were designed using improved DER models for three common distribution systems: a radial feeder, a meshed network, and a microgrid. Modeling and hardware-in-the-loop (HIL) testing of the APS were conducted, successfully showing their effectiveness and selectivity. Proof-of-concept field demonstration was achieved for two APS, i.e., one on a radial feeder and another one in a microgrid. Field demonstration could not be achieved for the APS on a meshed network, primarily due apprehension of one utility partner and also due to limited access to the protective algorithms in the network protectors. Guidelines developed from the lessons learned in the project lay out the general process followed in the design, installation, and commissioning of APS for various distribution systems. Distribution utility partners’ apprehension about field demonstration of the new APS were addressed—with varying success—by taking a stepped risk-management approach of modeling of a wide range of sensitivities first, performing in-depth proof-of-concept testing in the laboratory including HIL next, and finally deliberately implementing and commissioning the actual protection equipment and algorithms into parts of—or in parallel operation to—the three real distribution systems. Future work should include pilot projects that further show the acceptable performance of the developed APS before these schemes be rolled out more widely. Inclusion of both utility and original equipment manufacturers (OEMs) in future projects could increase chances of successful field demonstration. Despite challenges in achieving the field demonstration goal of the project for all three APS, the research significantly contributed to the innovation of adaptive protection solutions for scalable and reliable DER integration into distribution systems. This project significantly enhances the understanding of the impact of using appropriate inverter models on distribution and transmission (T&D) systems. By addressing the limitations of existing generic models, the project introduces high-fidelity models for stability, protection, electromagnetic transient (EMT), and quasi-static time series (QSTS) analyses. These models, integrated into commercial software tools, enable utilities, vendors, and developers to confidently study high-penetration PV systems. The project also demonstrates advanced applications, including adaptive protection schemes (APS) for distribution systems and microgrids, ensuring grid safety and reliability. The technical effectiveness and economic feasibility of the methods are evident through the development and validation of sophisticated inverter test plans and the selection of representative inverters. Testing by EPRI and NREL on retail, commercial, and utility-scale inverters, conforming to IEEE standards, underscores the robustness of the models. Improvements to existing generic models for various analyses further enhance their validity and applicability. The project also identifies gaps in common distribution protection schemes and designed new APS using improved DER models, demonstrating their effectiveness through modeling and hardware-in-the-loop (HIL) testing. The project’s benefits to the public are manifold. By advancing the standardization and model-based representation of IBR response, it supports transmission planning, stability assessments, and future IBR interconnection requirements. The generic models can facilitate better communication between transmission planners and developers, supporting expected IBR plant capability and performance. Additionally, the development of APS for radial feeders, meshed networks, and microgrids supports the integration of distributed energy resources (DERs) into distribution systems, enhancing grid reliability and safety. The project’s emphasis on thorough testing and simplicity in design ensures practical and scalable solutions for DER integration.

14 SOLAR ENERGY↗

Impact of synchronous condensers on fault location and black start in multi-inverter isolated microgrids

Synchronous condensers have been used in power systems for decades, but they are now attracting interest as a potential means for solving certain issues associated with inverter-based resources in islanded power systems. They have been extensively studied in applications to large wind farms and weak grids, but there has been very little study of synchronous condensers in intentionally-islanded systems, and especially self-healing ones. This report documents the results of an LDRD project intended to create modeling tools for use in the study of synchronous condensers in these smaller off-grid systems, and to explore synchronous condensers in this application. The results indicate that synchronous condensers have the potential to provide many benefits, but there are also several unanswered questions and technical challenges requiring further study.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An Admittance-Based Protection Scheme for Microgrids

This paper presents a novel directional protection scheme to address the unique challenges associated with protection during unbalanced faults in a distribution system with high penetration of inverter-based resources. The scheme is based on a superimposed negative sequence admittance method. A coordination approach using a unique inverse-time undervoltage element is also presented. An analysis of the scheme, the detection criteria and the coordination method are performed. Also the impact of inverter-control on the scheme is discussed. Results from extensive simulation using MATLAB/Simulink are presented to show a selective and reliable response of the scheme to unbalanced faults

Opoku, Kwasi↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters: Preprint

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

Photovoltaic Analysis and Response Support (PARS) Platform for Solar Situational Awareness and Resiliency Services

The project's primary objective is to develop a digital-twin based Photovoltaic (PV) Analysis and Response Support (PARS) platform, which aims to provide real-time situational awareness and optimal response plans. This platform is designed to enhance the performance of hybrid PV systems, making them competitive with or even superior to conventional generation resources. The PARS platform enabled the project team to develop and evaluate an extensive suite of grid support functionalities for the hybrid PV systems to enhance grid performance, across key areas including visibility, dispatchability, security, resilience, and reliability. Given the global push toward achieving 100% clean energy by 2035, there is a significant increase in the integration of inverter-based resources (IBRs) throughout the energy grid. Effectively managing the inherent variability and uncertainty associated with IBRs is crucial for ensuring cost-effectiveness, reliability, and security in both the main grid and islanded microgrids. Constrained to a limited array of IEEE test systems or standard feeder models, traditional IBR modeling struggles to assimilate new field data, accurately reflect system dynamics, and adapt to the evolving energy landscape. In our project, we embraced a Digital Twin (DT) strategy for crafting the PARS platform. A digital twin acts as a precise virtual counterpart of a physical system, built on historical data and continuously honed with real-time insights. This enables the high-fidelity DT to accurately mirror current system operations and forecast future scenarios. Consequently, the PARS platform becomes an ideal environment for testing and refining monitoring, control, power, and energy management algorithms designed to boost hybrid PV system performance. The defining feature of the PARS platform, distinguishing it from other advanced simulation tools, is its exceptional adaptability. This is achieved by employing actual network topologies and utilizing real-time field data for fine-tuning and calibration, ensuring a close emulation of real-world conditions. The project deliverables include: 1) High-fidelity IBR models and tools for real-time parameterization, utilizing real-time field measurements to refine IBR models for enhanced accuracy and performance; 2) Grid-forming and Grid-following capabilities to deliver resilience services, including blackstart, voltage and frequency support, cold-load pick-up, power reserves, and three-phase load balancing across grid-connected and microgrid settings; 3) Machine learning-based forecasting tools and methods for generating synthetic data and topologies, creating diverse and realistic simulation environments for evaluating varied operational scenarios; 4) Advanced microgrid power and energy management algorithms for optimizing the integration and operation of PV, storage, and demand response resources within both feeder and community scales. The power grid data sets are provided by four utility companies in North Carolina and the New York Power Administration. Acting as industry advisors, our industry partners communicated stakeholder needs and regulatory standards to the research teams, aiding technology transfer by incorporating the developed methodologies into their daily operations. This collaboration ensures that the PARS platform, functioning as a power system digital twin, enhances our understanding of IBR dynamic behaviors and enables the development and evaluation of IBR control functions that match or exceed the capabilities of conventional synchronous generators.

14 SOLAR ENERGY↗

Quantitative Small-Signal Stability Analysis of Grid-Forming Inverters in Large-Scale Power Systems

In this paper, the challenges induced by the integration of inverter-based resources (IBRs) into existing power systems are discussed. Although the grid-forming (GFM) control has been used to enhance system performance in multiple sections of electric power systems (e.g., transmission and distribution systems, microgrids, among others), the coupling mechanism between GFM inverter and various types of other components in modern power systems should be clearly explored. Existing analyses mainly focus on qualitative investigations that verify the effectiveness of deploying GFM inverters for stability enhancement. A holistic system-level quantitative analysis is still missing to verify the detailed benefits of GFM inverters and their interactions with other generation units (e.g., synchronous generators [SGs], conventional grid-following [GFL] inverters, synchronous condensers, among others). To fill in the technical gaps, a holistic small-signal model of the entire system with both rotating generation units and IBRs is established along with the customized power flow analysis for varying steady-state operating points. Further, a quantitative method is proposed to identify the impacts of GFM inverters on system performance with an emphasis on a quantifiable stability margin and a complete modal analysis at the system level. Finally, a realistic test system is used to verify the proposed approach.

grid-following↗

A Large-Scale Hardware Experiment Demonstration of Operating High Inverter-Based Resource Power Systems With Grid-Forming Inverters

This paper presents experimental hardware results from a microgrid system as the penetration level of grid-forming (GFM) inverters increases. The experiment aims to showcase the advantages of GFM inverters in enhancing system stability and to investigate the operational challenges in systems relying entirely on inverter-based resources (IBRs). Five test scenarios are devised to progressively increase GFM inverter penetration levels: 0% (S1), 19% (S2), 37% (S3), 68% (S4), and 100% (S5). To ensure consistency, identical loading conditions and dynamic events are applied across all scenarios. The conducted tests include load step changes, output variation of grid-following (GFL) inverters during islanded mode, transition operations (such as synchronization to the grid and islanding), and rateof- change-of-frequency (ROCOF) and voltage jump tests during grid-connected mode. Key findings from the tests are summarized as follows: (1) Scenario S1 proved most challenging for load steps, and GFL variations because of insufficient GFM capacity, leaving the diesel generator unable to handle transient ridethrough; (2) Scenario S5 was the most difficult for transition operations, because the lack of a diesel generator to maintain stiff bus voltage resulted in unexpected reactive power flows during synchronization, causing the point of common coupling (PCC) breaker to trip; (3) Scenarios S4 and S5 were particularly challenging for ROCOF tests because of minimal system inertia, leading to large transients that triggered breaker trips; and (4) Scenario S4 exhibited the strongest voltage recovery capability because of the presence of the diesel generator and a higher number of GFM inverters, both of which possess the highest capacity for reactive power injection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Dynamic Shaping of Grid Response of Multi-Machine Multi-Inverter Systems Through Grid-Forming IBRs: Preprint

We consider the problem of controlling the frequency response of weakly-coupled multi-machine multi-inverter low-inertia power systems via grid-forming inverter-based resources (IBRs). In contrast to existing methods, our approach relies on dividing the larger system into multiple strongly-coupled subsystems, without ignoring either the underlying network or approximating the subsystem response as an aggregate harmonic mean model. Rather, through a structured clustering and recursive dynamic shaping approach, the frequency response of the overall system to load perturbations is shaped appropriately. We demonstrate the proposed approach for a three-node triangular configuration and a small-scale radial network. Furthermore, for small-scale radial microgrids, we demonstrate the ability of IBRs to tune the effective transfer functions of synchronous machines. This enables us to relax the uniform turbine time-constant assumptions and widen the scope of existing synchronization results for proportionally heterogeneous machines.

frequency-shaping control↗

Grid-Forming Inverters: Project Demonstrations and Pilots

Power system operators around the world are pushing the limits of integrating inverter-based resources (IBRs) to very high levels, approaching 100% instantaneous penetration under certain operating conditions. This often applies to smaller power systems with very little or no ac interconnections to other neighboring regions or sometimes to fringes of large balancing areas, such as Denmark or Portugal, within the mainland European power system. These jurisdictions have identified the potential of grid-forming (GFM) technology as a key enabler to support the energy transition with very few or no synchronous generators online. Until recently, practical applications of GFM inverters were limited to microgrids and isolated grids and in smaller grid applications on the order of a few tens of megawatts (MW).

Australia↗

Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition

Power systems are transforming with increasing levels of inverter-based resources (IBRs). This transformation requires critical roles of grid-forming (GFM) inverters replacing synchronous generators for bulk power system stabilization and ancillary services, also allowing flexible power system operation, such as microgrid that is operated by multiple GFM IBRs to achieve system resilience against contingencies. To realize the resilient power systems allowing flexible in-and-out operation of GFM IBRs potentially programmed with different primary controls, a synchronization method universally applicable, i.e., independent of control types, would be beneficial to ease the integration process, but it has not been actively studied. To fill the gap, this paper proposes a universal synchronization method that achieves a passive synchronization to enable a smooth transition in a grid with off-nominal system parameters, i.e., voltage and frequency. The logic proposed requires no modification on the primary control, thus applicable to any type of GFMs with a voltage reference input. To validate the concept, a simulation of an IEEE 13-bus benchmark system modified with 3 GFM inverters is presented. It simulates an inverter-driven black start scenario in which GFM inverters autonomously turn on and connect to the grid under heavy loading, using the synchronization logic. The case study demonstrates that GFM inverters can tune their voltage reference to smoothly synchronize without severe transients, and contribute to a seamless black start of the grid under unbalanced load conditions. Two GFM methods - Droop and dispatchable virtual oscillator control - are used for the demo to validate feasibility and interoperability of the passive synchronization.

black start↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode

This paper explores the dispatchability of grid-forming (GFM) inverters in grid-connected and islanded mode. GFM inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generators) and follow the change in the load demand; however, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help grid operators better manage their inverter-based resources (IBRs) to improve operation efficiency and reliability; therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and synchronous generators) to output the target power in both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, and thus dispatching the active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one GFL inverter, and the load in both grid-connected and islanded mode. This pioneering work results in practical guidance for the development of energy management systems for future electric grids with GFM and GFL inverters.

dispatching↗

Unified Universal Control and Coordination of Inverter-Based Resources, and Validation for a PV + Battery Hybrid Plant

As renewable energy deployment grows, hybrid power plants (HPPs) combining photovoltaic (PV) and battery systems must evolve to offer both energy and grid stability services. These systems typically include a mix of grid-following (GFL) and grid-forming (GFM) inverters, presenting unique coordination and control challenges. This Department of Energy–funded project developed and validated a Unified Universal Control and Coordination (UUCC) framework for such PV + battery hybrid plants, enabling seamless and stable operation, including ultrafast black start, autonomous synchronization, and robust frequency and voltage regulation, under different grid conditions. The project significantly advanced the understanding of inverter-based resource (IBR) control by developing and validating three complementary system-level approaches for hybrid GFL/GFM operation: 1. A combined Virtual Resistance (VR)-based GFL and Virtual Oscillator Control (VOC)-based GFM method, where each inverter type is governed by a specialized control strategy. Together, these achieve stable, fast-response coordination, eliminating inrush current and enabling smooth black start and grid synchronization across a wide range of grid strengths. 2. A Deadbeat-based UUCC strategy, which uses discrete-time, switching-cycle-level control for both GFL and GFM inverters. This approach replaces traditional PI/PLL control with a control parameter-free, high-bandwidth framework that supports stable LVRT and instantaneous synchronization under all conditions. 3. A benchmark comparison with Siemens’ commercial GFM microgrid controller, which provided a fast baseline platform. The commercial approach decoupled v & f control was implemented on a commercial microgrid controller.The baseline commercial benchmark helped highlight superior transient response and black start performance offered by the deadbeat and VOC approaches. These technical contributions offer substantial improvements over conventional inverter control schemes, which often rely on slow phase-locked loop (PLL)-based synchronization, require careful control parameters tuning, and prone to unstable in weak grids with GFL inverters and in stiff grid with GFM inverters therefore challenging for hybrid GFL+GFM under all grid conditions. The deadbeat-based UUCC framework enables simpler, faster, and more robust operation of hybrid IBR systems using wide-bandgap (WBG) devices such as SiC power semiconductors. The rapid expansion of hybrid distributed energy resources (DERs), including residential and commercial PV-BESS installations such as Tesla Powerwall, PV with vehicle-to-grid (V2G) capability, and other integrated configurations, presents complex operational challenges for medium-voltage radial distribution feeders. These networks are subject to frequent disturbances such as faults, switching operations, rapid reclosing sequences, and feeder reconfigurations, all of which introduce dynamic stress on IBRs. In addition, planned feeder segmentation and deliberate islanding for resilience will require DERs that can autonomously perform blackstart, establish voltage and frequency references, and resynchronize with the main grid. The advanced deadbeat-based UUCC control and blackstart functionalities developed in this project directly address these requirements, enabling decentralized and autonomous operation of inverter-dominated DERs in distribution systems under a wide range of fault and reconfiguration scenarios. From a public benefit perspective, these innovations enable more reliable and cost-effective integration of renewable energy into distribution networks. The ability to autonomously black start and stabilize grids under varying grid conditions support accelerates recovery from outages and support decentralized resilient energy systems. By reducing system complexity and improving performance, this project lays critical groundwork for future inverter-dominated power grids that are clean, reliable, and accessible to all.

14 SOLAR ENERGY↗

Analysis of Grid-Forming Inverter Controls for Grid-Connected and Islanded Microgrid Integration

Autonomous grid-forming (GFM) inverter testbeds with scalable platforms have attracted interest recently. In this study, a self-synchronized universal droop controller (SUDC) was adopted, tested, and scaled in a small network and a test feeder using a real-time simulation tool to operate microgrids without synchronous generators. We presented a novel GFM inverter control adoption to better understand the dynamic behavior of the inverters and their scalability, which can impact the distribution system (DS). This paper provides a steady-state and transient analysis of the GFM power inverter controller via simulation to better understand voltage and frequency stabilization and ensure that the critical electric loads are not affected during a prolonged power outage. The controllers of the GFM inverter are simulated in HYPERSIM to examine voltage and frequency fluctuations. This analysis includes assessing the black start capability for photovoltaic microgrids, both grid-connected and islanded, during transient fault conditions. The high photovoltaic PV penetration levels open exciting opportunities and challenges for the DS. The GFM inverter control demonstrated appropriate response times for synchronization, connection, and disconnection to the grid. The DS has become more resilient and independent of fossil fuels by increasing the penetration of inverter-based distributed energy resources (DERs).

Ward, Laura (ORCID:0000000345501581)↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode: Preprint

This paper explores the dispatch-ability of grid-forming (GFM) inverters in grid-connected and islanded mode. Grid-forming (GFM) inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generator (SG)) and follow the change of the load demand. However, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help the grid operator better manage their inverter-based resources (IBRs) for improved operation efficiency and reliability. Therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and SG) to output the target power for both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle of doing so is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, thus, dispatching active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one grid-following inverter and loads in both grid-connected and islanded mode. This pioneering work results in a practical guidance for power system energy management system (EMS) development to control a future grid with GFM and GFL inverters.

droop control↗