Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “medium voltage”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Wide-Input Voltage Range Two-Stages Auxiliary Power Supply for Medium Voltage Applications

This paper aims to present a two-stages auxiliary power supply (APS) providing 24 V output over a wide input DC voltage range, from 600 V to 2 kV. In this architecture, the medium voltage to low voltage scale is addressed by a simplified DC transformer (DCX) stage while the low voltage tight regulation is proposed to be accomplished in a cascaded second stage. Such architecture provides a simpler approach to the industry for the design of APS in MV applications. The implementation of main building blocks of the APS including the DCX stage, startup circuit and self-powered circuit is described. Experimental results at 1400 V and 100 W are presented.

Magri Kimpara, Marcio↗

Optimizing Insulation Design for Transformers in Medium Voltage Power Conversion Systems

Medium-frequency transformers (MFTs) play a crucial role in medium-voltage (MV) solidstate transformer (SST) systems, particularly in extreme fast charging applications. Achieving partial discharge (PD)-free operation while maintaining high power density is a significant challenge due to the high electric field (E-field) stresses inherent in MV applications. This dissertation focuses on the insulation design and optimization of MFTs used in both the main power electronics circuits and auxiliary power supplies. The study begins with an overview of insulation testing methodologies, including high potential tests, basic insulation level tests, and PD tests, which are critical for evaluating MFT insulation reliability. Given the importance of PD-free operation for long-term reliability, particular emphasis is placed on understanding PD mechanisms, including void, corona, and surface discharge, and their mitigation strategies. A high voltage isolated auxiliary power supply is then introduced, utilizing a gapped transformer encapsulated in silicone gel. This design achieves PD-free insulation up to 18 kV RMS while maintaining low coupling capacitance to minimize common-mode current. The proposed solution ensures reliable operation in MV environments and offers a scalable approach for auxiliary power in cascaded SST architectures. To improve MFT insulation in main power conversion circuits, a novel structure is developed using polypropylene sheets and potting compounds to create a void-free air gap, effectively mitigating E-field intensity. A prototype transformer with this insulation structure is built and achieves PD-free operation up to 30 kV RMS. This design is experimentally validated in a resonant converter operating at 46 kW, demonstrating its feasibility for MV SST applications. Further optimization is implemented to enhance MFT performance for dual-active-bridge(DAB) converters by integrating a semiconductive shielding layer within the insulation structure. This shielding layer improves the magnetic coupling coefficient while effectively confining the E-field within high insulation materials, thereby reducing eddy current losses. The optimized MFT achieves PD-free operation at 12.6 kV RMS and is successfully tested in a DAB converter operating at 43 kW, which meets the insulation requirements for a 13.2 kV SST system. This dissertation advances MFT insulation design by introducing and experimentally validating novel approaches that improve high voltage insulation while optimizing magnetic coupling and manufacturability. The proposed insulation structures enable PD-free operation while minimizing insulation material usage and simplifying assembly, making them ideal for high power, high voltage applications.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Modular, Multifunction, Multiport and Medium Voltage Utility Scale SiC PV Inverter (Final Report)

This project is to develop and demonstrate a Modular, Multi-function, Multiport and Medium Voltage utility scale SiC solar inverter (M4 Inverter). The M4 Inverter is a next generation utility scale PV + storage inverter that can substantially reduce the levelized cost of energy (LCOE) while providing grid friendly ancillary services. Conventional utility scale solar inverters includes three parts, a megawatt rated solar inverter, a low frequency transformer (LFT) and a medium voltage switch gear. The proposed M4 Inverter directly converts the DC output of solar panels to medium voltage AC, eliminating the bulky and costly LFT. The M4 Inverter also has a DC port to interface with an additional energy storage device. This plus its bidirectional power flow capability, allows multiple functions in addition to PV maximum power tracking be achieved. These additional functionalities include but not limited to reactive power support, peak shaving, fast frequency regulation and synthetic inertia. Predicted LCOE reductions with these added functionalities, improved efficiency and longer lifetime time are more than 30% compared with the 2017 utility scale solar LCOE. A 1MVA SiC M4 Inverter was developed and tested at high power level. The project has also advanced the state of the art in controller hardware in the loop simulation capability. Power electronic innovations introduced in the M4 Inverter includes 1700V SiC MOSFET application in 1500V PV system, soft switching three-port power converters and modular converter architecture.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluation of Damage in Medium Voltage Cable Using Machine Learning

Developments in cable test instrumentation coupled with artificial intelligence and machine learning (ML) to aid in interpretation of cable test signals supports the feasibility for automated analysis of reflectometry tests for low voltage power cables. This work seeks to leverage prior ML work and success for low voltage cables to evaluate potential application to medium voltage (2kV to 10kV) installations. The Accelerated and Real-Time Environmental Nodal Assessment (ARENA) Cable Motor Test Bed at Pacific Northwest National Laboratory (PNNL) was used to test a medium voltage cable with several types of damage including thermal aging and low resistance conductor-to-shield faults. The cable was tested using an inductive clamshell coupler to protect the test instruments from the energized cable voltages that would damage the test instruments if coupled directly to the energized conductor.

42 ENGINEERING↗

Visualizing Fault Induced Traveling Waves In Medium Voltage Systems

Traveling waves are induced in power systems during most transient events in the grid. These waves travel close to the speed of light in overhead lines and 50% to 60% the speed of light in underground cables. Even though traveling wave-based protection schemes for transmission systems are available commercially, traveling waves in medium voltage distribution networks are still in research space. Compared to transmission system, medium voltage distribution systems contain more reflections and refractions. Thus, visualization is challenging and is critical in locating faults in distribution network. To address this visualization challenge, this paper presents an open-source tool to visualize the traveling waves using Bewley lattice approach. The developed visualization tool will be useful for the protection engineers to detect and triangulate fault locations in the medium voltage systems and isolate the faults.

Bewley Lattice↗

Visualizing Fault Induced Traveling Waves in Medium Voltage Systems: Preprint

Traveling waves are induced in power systems during most transient events in the grid. These waves travel close to the speed of light in overhead lines and 50% to 60% the speed of light in underground cables. Even though traveling wave-based protection schemes for transmission systems are available commercially, traveling waves in medium voltage distribution networks are still in research space. Compared to transmission system, medium voltage distribution systems contain more reflections and refractions. Thus, visualization is challenging and is critical in locating faults in distribution network. To address this visualization challenge, this paper presents an open-source tool to visualize the traveling waves using Bewley lattice approach. The developed visualization tool will be useful for the protection and safety engineers to detect and triangulate fault locations in the medium voltage systems and isolate the faults.

Bewley Lattice↗

Medium Voltage Converter Inductor Insulation Design Considering Grid Requirements

Medium voltage (MV) SiC devices facilitate direct (without 50-/60-Hz transformer) connection of the power electronics converter to the MV grid using simple topology. Compared to the insulation design of MV inductors that have been widely used in the power system, the insulation design of the MV converter filter inductors has new challenges. Particularly, the grid impact on insulation requirements on converter filter inductors is rarely discussed. This article introduces the insulation design of a grid-side filter inductor for a 13.8-kV power conditioning system converter. The grid insulation requirements, including the short-duration power frequency overvoltage and the lightning impulse voltage, are considered in the design. To meet the requirements, the layer-to-layer insulation, winding-to-core/ground insulation, the air gap discharge between the winding and the core, the local electric field, as well as the interturn transient voltage distribution are considered. Furthermore, the designed inductors are validated by the 46 kV (>1 min) dc hi-pot test, 12-kV ac partial discharge test, one-hour single-phase converter full rating test, as well as three-phase converter full rating test.

42 ENGINEERING↗

Cooling methods for medium voltage drive systems

In one aspect, a medium voltage power converter includes a cabinet having: a power cube bay to house a plurality of power cubes, each of the plurality of power cubes adapted within a corresponding enclosure and comprising a low frequency front end stage, a DC link and a high frequency back end stage, the plurality of power cubes to couple to a high speed machine; and a plurality of first barriers adapted to isolate and direct a first flow of cooling air through one of the plurality of power cubes; and a transformer bay having at least one transformer to couple between a utility connection and the plurality of power cubes, the transformer bay including a plurality of cooling fans to cool the at least one transformer.

Ledezma, Enrique↗

Modular Wide-bandgap String Inverters for Low-cost Medium-voltage Transformerless PV Systems

The proposed technology combines advances in wide-bandgap power electronics with breakthroughs in distributed and decentralized control to produce ultra-low-cost medium-voltage transformerless PV inverters that are composed of stackable lightweight blocks. Taken together, the proposed circuit designs and accompanying control strategies will yield integrated control+circuit (C2) blocks, each comprising a converter and local controller, that can be assembled in a modular fashion to obtain distributed conversion interfaces for next-generation commercial and utility-scale PV systems. We will utilize SiC devices to obtain C2 blocks that can individually operate at a voltage and power in excess of 1 kV and 100 kW, respectively, such that ensembles of series-connected blocks perform direct dc to three-phase ac conversion at medium voltages (e.g., 12 kV–35 kV) and at multi-MW power levels.

42 ENGINEERING↗

Online Monitoring of Medium Voltage Cable Systems with Spread Spectrum Time Domain and Frequency Domain Reflectometry

In-service failures of wave energy convertor (WEC) cable systems can have a significant cost and power availability impact. Close parallel research 2019 data showed > 1B£ and 9 Terra-Watt-Hours associated with global off-shore wind (OSW) cable failures (Strang-Moran 2020). OSW is a closely related technology but currently is significantly cheaper than WEC technology. For wave energy to compete, the problem of reliable cable transmission must be mitigated. This project develops isolation technology to allow online high frequency reflectometry testing of medium voltage cables (1 to 10 kV and higher) without arcing or damage to the test instrument. Online spread spectrum time domain reflectometry (SSTDR) testing has been established for low voltage cable systems in the aircraft and rail industry and the ability to detect and locate cable flaws of interest is well understood. Extending reflectometry testing to medium voltage systems could enable detection of cable damage before failures occur thereby allowing repair and replacement of damaged cable segments to be scheduled and managed. The seedling project succeeded to pass and receive high frequency SSTDR signals onto a cable up to 1 kV using a parallel trace isolation circuit board that can be connected onto the test cable. The approach used a novel circuit design for which an invention disclosure has been filed. A proposed sapling project would extend the technology toward the higher operating voltages used by WEC systems, thereby enabling online SSTDR cable monitoring. The goal of the seedling project was to extend the capability of the ARENA cable/motor test bed to address medium voltages and to develop a high pass filter isolation architecture to protect the reflectometry instrument from the low frequency (DC – 60 Hz) line voltage while allowing the high frequency diagnostic signal to pass to and from the test instrument to the live line. Initial efforts focused on passive LCR filter circuits to reduce 60 Hz levels below 10 volts from a 10 kV line while allowing the MHz high frequency chirps to pass onto the cables and for mV signals to be detected. We discovered that the parasitic loss behavior of real high voltage components precluded this approach from working. An alternate approach was adapted for the electric field to couple between two parallel traces on a printed circuit board much like a radio-frequency coupler. The challenge here was and is to have the parallel traces close enough to each other to effectively pass the high frequency chirp onto the live line and receive any reflected signal from any encountered impedance change along the cable. This reflected signal will be in the mV range. The traces however must be far enough apart to not allow arcing on the board. A design with 3 mm spacing was determined to allow the high frequency signal to pass onto the live line and receive the mV signal back into the instrument while reducing the 60 Hz voltage amplitude by >80 dB (more than a factor of 10,000) without allowing arcing from across the parallel traces. This was confirmed by simulation and test.

16 TIDAL AND WAVE POWER↗

Sizing and Location Selection of Medium‐Voltage Back‐to‐Back Converters for DER‐Dominated Distribution Systems

Medium‐voltage back‐to‐back (MVB2B) converters can connect two distribution systems and quantifiably transfer power between them. This function can enable the MVB2B converter to exchange distributed energy resource (DER)‐generated power between two systems and bring significant value to enhancing distribution system DER adoption. Our previous work analysed and demonstrated the value MVB2B converter can bring to DER integration. As continuous work, this paper presents a methodology that helps address the MVB2B converter sizing and location selection problem in distribution systems with high DER penetrations. The proposed methodology aims to address three critical problems for MVB2B converter implementation in the real world: (1) which distribution systems are better to be connected, (2) what converter size is appropriate for connecting the distribution systems, and (3) where the optimal connection points are in the systems for connecting the MVB2B converter. The proposed methodology has been demonstrated by case studies that include various scenarios involving distribution systems with different dominated load types and high photovoltaic penetrations. The results demonstrate that selecting the optimal converter size based on net revenue and time of return considerations leads to a balance between maximizing energy savings and minimizing financial payback periods. Furthermore, feeder pair selection based on load profile standard deviation effectively identifies systems that derive the greatest value from MVB2B integration. Finally, an optimized connection point selection approach using a voltage load sensitivity matrix ensures minimal system impact while facilitating efficient power exchange. These findings provide practical insights for the real‐world deployment of MVB2B converters to enhance DER hosting capacity and improve grid resilience.

14 SOLAR ENERGY↗

Grid Application and Controls Development for Medium-Voltage SiC-Based Grid Interconnects

This paper studies, the grid-interconnection requirements of directly connected medium-voltage (MV) Silicon Carbide-based (SiC-based) converters and details the necessary control implementations. These power electronic converters follow the interconnection standard IEEE 1547-2018, but can also have additional controls supported by the microgrid standards in IEEE 2030.7, which is demonstrated in this work. Additionally, this paper defines the grid applications realized by these directly connected medium-voltage power electronic converters at the distribution scale and demonstrates results. The controls for the studied grid applications are then developed and implemented on the controller. The paper also includes details of the control algorithm development and validations of the control algorithm through hardware-in-the-loop results.

28 EE - Advanced Manufacturing Office (EE-5A)↗

Medium Voltage Integrated Drive and Motor

The objective of this program was to design, build, and test a medium voltage (4,160VAC) high speed permanent magnet machine (HSPMM) and variable speed drive (VSD) that incorporates next generation 10kV silicon carbide (SiC) modules. The use of a HSPMM allows for high efficiency, small footprint, maintenance free operation while the SiC modules enable higher voltage operating conditions, improved efficiency, and small footprint.

30 DIRECT ENERGY CONVERSION↗

Guest Editorial Special Section on Advanced Medium-Voltage Power Electronics for Grid Interactive Applications

Medium-voltage power electronics (MVPE) plays essential roles in power grid modernization and links the MV distribution grid with low-voltage consumers and prosumers. Various MVPE devices, such as solid-state transformers or circuit breakers, inverter-based resources, power flow controllers, etc., bring the benefits of voltage conversion and power regulation in small footprint, power quality and efficiency improvements, and enhancements of grid controllability, flexibility, stability, and resilience. The MVPE also makes it possible for sustainable energy systems, such as solar/wind farms and energy storage generating facilities, to directly access to MV grids without multistage conversions. With their intrinsic intelligence and communications, MVPE enables many new smart grid functions and applications, e.g., dc interconnections and electric vehicle charging, which were not envisioned by traditional power grids otherwise. In addition, the integration of physical power processing units with cyber components forms a cyber-physical system, which is essential for long-term sustainability, development, and environmental preservation. Nonetheless, technical challenges on MVPE device reliability, scalable and efficient converter topologies, control stability, large-scale modeling and simulation, to name a few, need to be addressed and advanced to the next level. In conclusion, this Special Section on Advanced MV Power Electronics for Grid Interactive Applications in IEEE Transactions on Power Electronics (TPEL) provides an insight on some of the recent advances in MVPE and emerging challenges and potential solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

High Speed Medium Voltage CHP System with Advanced Grid Support

The project was a collaboration between Clemson University and TECO Westinghouse Motor Company. The goal of the project was to develop a medium voltage commercial grid-tied system with advanced grid support functions. Current state-of-the-art in medium voltage, multi-megawatt power electronic systems do not support advanced grid functions, traditionally due to power electronic limitations and required applications. The developed system is capable of interacting with the power system at the distribution level to efficiently integrate gas turbine generation systems or any other ac generation system with up to 20MWe of power production capacity. This project demonstrated a high level of technical readiness of the 1MW, 500Hz, 15000 RPM high frequency Combined Heat and Power (CHP) generator and electric machine system, utilizing advanced grid support functions required by IEEE Std. 1547-2018.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensors with Intelligent Measurement Platform and Low-cost Equipment (SIMPLE) for Monitoring and Control of Medium Voltage Distribution Systems with High Penetration of Intermittent Distributed Energy Resources

The primary focus of the SIMPLE project was to develop, commission, test and introduce intelligent voltage and current sensor platform with enhanced characteristics (accuracy, bandwidth and harmonic range) and high measurement granularity for medium voltage distribution system monitoring, protection and control. The enhancements incorporated existing (commercially available) sensors and made them suitable for applications such as voltage regulation, frequency support, fault detection and location, distribution system state estimation, power quality measurements and electrical distribution network topology processing. The development of the intelligent sensor platform was driven by the need for high-fidelity monitoring and control of medium voltage distribution feeder to enable higher penetration of renewable resources and microgrid operation.

14 SOLAR ENERGY↗

Submodule-Level Decentralized Control for Cascaded Quadruple Active Bridge-Based Medium-Voltage Converters

High-power, low-voltage DC (LVDC) loads, such as AI data centers, electric vehicle fast-charging hubs, and hydrogen electrolyzers, are accelerating the deployment of solid-state transformers (SSTs) that directly interface medium-voltage AC (MVAC) to LVDC, streamlining power delivery. This paper proposes a submodule-level decentralized control strategy for an SST comprising a cascaded H-bridge (CHB) active rectifier on the MVAC side and per-module quadruple-active-bridge (QAB) converters on the LVDC side with local controllers. The proposed strategy eliminates the need for high-fidelity, real-time cross-isolation communication by synchronizing all active bridges to a common heartbeat signal and enabling the primary- and secondary-side controllers to generate independent local control signals (phase shifts). The resultant phase shifts naturally govern average and double-line frequency power transfer between active bridges, enabling each side to meet its control objectives using only local measurements. Detailed controller design considerations are presented based on a stability analysis. Comprehensive electromagnetic-transient simulations demonstrate tight DC-link voltage regulation, high-quality grid currents, and robust operation under load transients and grid disturbances, without real-time communication among the submodule controllers. These results indicate that the proposed scheme can significantly enhance the reliability, scalability, and flexibility of cascaded bridge-based medium-voltage converters.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Submodule-Level Decentralized Control for Cascaded Quadruple Active Bridge-Based Medium-Voltage Converters: Preprint

High-power, low-voltage DC (LVDC) loads, such as AI data centers, electric vehicle fast-charging hubs, and hydrogen electrolyzers, are accelerating the deployment of solid-state transformers (SSTs) that directly interface medium-voltage AC (MVAC) to LVDC, streamlining power delivery. This paper proposes a submodule-level decentralized control strategy for an SST comprising a cascaded H-bridge (CHB) active rectifier on the MVAC side and per-module quadruple-active-bridge (QAB) converters on the LVDC side with local controllers. The proposed strategy eliminates the need for high-fidelity, real-time cross-isolation communication by synchronizing all active bridges to a common heartbeat signal and enabling the primary- and secondary-side controllers to generate independent local control signals (phase shifts). The resultant phase shifts naturally govern average and double-line frequency power transfer between active bridges, enabling each side to meet its control objectives using only local measurements. Detailed controller design considerations are presented based on a stability analysis. Comprehensive electromagnetic-transient simulations demonstrate tight DC-link voltage regulation, high-quality grid currents, and robust operation under load transients and grid disturbances, without real-time communication among the submodule controllers. These results indicate that the proposed scheme can significantly enhance the reliability, scalability, and flexibility of cascaded bridge-based medium-voltage converters.

24 POWER TRANSMISSION AND DISTRIBUTION↗