Performance Assessment of a Heat Pump Integrated with Thermal Energy Storage in Cooling & Heating Modes
Thermal Energy Storage (TES) systems have demonstrated significant potential to manage the fluctuating nature of energy demand and shifting peak loads. This technology has made significant recent advances, including new research on the integration of TES with residential and commercial Heating, Ventilation, and Air-Conditioning (HVAC) systems. In this paper, we present the use of a novel laboratory assessment framework for a prototype heat pump system integrated with latent heat phase change material-based TES. The assessment framework consists of 22 total test points (11 heating, 11 cooling) using psychrometric conditions from AHRI Standard 210/240 and includes transient conditions to evaluate TES charging and discharging modes. In addition, both continuous mode and cyclic mode were evaluated for charging and discharging to explore the benefits to TES heat transfer from repeated transient operation. The ambient conditions evaluated include heating mode charging at cold-climate heat pump conditions when winter-peaking utilities may most require demand reduction (H4Full conditions, 5°F/-15°C) and cooling mode charging at high ambient temperature that may occur during times of day when excess solar power generation results in low-cost electricity (105°F/40.6°C). The work demonstrates the demand reduction capabilities of integrating TES with HVAC, including up to 44% in cooling mode and 60% in heating mode compared to conventional HVAC equipment without TES.