Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Microgrid Controller”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 325 records · Page 18

Reinforcement Learning-Based Secondary Control Strategy for Voltage and Frequency Regulation in Islanded Inverter-Based Microgrids

This paper presents a reinforcement learning (RL) approach for secondary voltage and frequency control in islanded inverter-based microgrids. The proposed control strategy aims to restore voltage and frequency deviations caused by the primary droop control while ensuring proper power sharing between distributed generators. The RL agent is designed to provide correction signals to the primary control, considering communication delays and system constraints. The effectiveness of the proposed control strategy is validated through simulation results in MATLAB/Simulink environment, demonstrating superior performance in maintaining voltage and frequency within the nominal values.

Rodriguez Martinez, Omar Felipe [University of Pue↗

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters

As increasingly more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMS) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states. For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; altogether, the control algorithms seamlessly connect the states into a generic microgrid EMS that controls the nodal voltages and frequencies, becomes a virtual power plant (VPP) when connected to the main grid, and coordinates power sharing responsibility among GFM sources when islanded. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management systems↗

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters

As increasingly more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMS) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states.For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; altogether, the control algorithms seamlessly connect the states into a generic microgrid EMS that controls the nodal voltages and frequencies, becomes a virtual power plant (VPP) when connected to the main grid, and coordinates power sharing responsibility among GFM sources when islanded. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management system↗

Enabling Grid-Forming Control Under Unbalanced Conditions

Standalone microgrids often experience unbalanced loading and faults, which can cause grid-forming control designed for balanced conditions to produce oscillatory responses. To address this issue, a compact time-domain transformation appropriate for inverter control is proposed, allowing the conversion of unbalanced three-phase signals to positive and negative synchronous reference frames. This transformation supports the development of a grid-forming control with fault ride-through, featuring frequency and voltage droop controllers and nested current and voltage control loops that seamlessly integrate an enhanced current limiter. The effectiveness of the proposed control and transformation is demonstrated through analytical results and electromagnetic transient simulation.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

SolarPlus Optimizer: Integrated Control of Solar, Batteries, and Flexible Loads for Small Commercial Buildings

Building-level microgrids may be a key strategy to unlock the combined potential of flexible loads, renewable generation, and energy storage. However, few software options exist for integrated control of building loads and other distributed energy resources at this scale. The commercial software solutions on the market can force customers to adopt one particular ecosystem of products, thus limiting consumer choice. The SolarPlus Optimizer (SPO) is an open-source building-level microgrid control platform that uses Model Predictive Control to optimize both building loads and behind-the-meter energy storage to reduce energy bills and increase demand flexibility. This paper evaluates the capabilities of SPO in a small commercial building in Northern California under multiple electricity tariffs and demand response scenarios. Comparing SPO operation with an emulated battery and baseline operation employing a commercial optimization service, SPO reduced electricity bills by an estimated 7.3% in summer, 3.2% in spring, and 3.7% in winter. In a “load shape” scenario meant to counter the “duck curve”, SPO achieved 71% fewer violations from the load signal than the baseline control method. During a three hour long load shed event, SPO reduced cooling and refrigeration load by 38%. This research shows significant potential to provide load flexibility for building-level microgrids for this type of control systems. Finally, the paper discusses the future direction of research on open-source control systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Survivability of Autonomous Microgrid during Overload Events

Grid-forming sources are voltage sources that draw necessary currents to meet any load changes. A load step can cause part or all of these sources to become overloaded in a microgrid. This paper presents an overload mitigation controller that addresses the two overload issues in a microgrid by actively controlling the sources’ frequency. When part of the sources in a microgrid is overloaded, the controller autonomously transfers the extra load to other sources by rapidly reducing its frequency. The frequency difference between sources during transient results in a change of phase angle, which redistributes the power flow. When all sources in a microgrid are overloaded, each source keeps dropping the frequency. Therefore, under frequency load shedding can be used to trip the non-critical loads resulting in the survival of microgrid. The advantages of these concepts are that communications between sources are not needed during transient, and the robust voltage control is maintained. Lastly, simulation and field tests from CERTS/AEP microgrid test site verify that the control strategy is effective in both purely inverter-based microgrids and inverter & generator mixed microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Safe Deep Reinforcement Learning for Robust Frequency and Voltage-Constrained Networked Microgrid Restoration

Here, this paper proposes a safe soft actor-critic reinforcement learning (RL) algorithm–based controller for networked microgrid restoration. It formulates the post black-start start as a finite-horizon constrained Markov decision process. The RL agent co-optimizes real and reactive power set-points for both grid-forming and grid-following inverters under explicit voltage and frequency constraints, while enforcing proper power sharing via the Mean Active Power Sharing Index (MPSI) and Mean Reactive Power Sharing Index (MQSI). Numerical results obtained on the IEEE 123-bus distribution system show that the proposed method achieves a mean voltage build-up time of 0.01 s without breaching the 5% sharing-violation budget under various load scenarios, considering MPSI and MQSI indices. These findings demonstrate that the proposed method yields fast and safe black-start schedules without resorting to heuristic penalties.

Selim, Alaa [Dartmouth College, Hanover, NH (Unite↗

Testing and Analysis of Grid Forming Inverter Control for Achieving Resilient and Economic Operation of an Islanded Microgrid

This investigation examines the feasibility of operating a battery energy storage system (BESS) in parallel with synchronous generation by using grid forming (GFM) control in order to achieve frequency control objectives while mitigating increases to operating costs in the context of an islanded microgrid. The BESS GFM control system, which is based on conventional droop techniques, is modeled along with the overall microgrid using the Real Time Digital Simulator (RTDS) to allow for integration of genset controller hardware. A series of simulations are performed to test the voltage and frequency regulation capability of the BESS control system when the primary frequency regulating genset is tripped offline. The results of the simulations suggest that the GFM control scheme will successfully maintain frequency and voltage stability, which will enable operation without a back-up genset while not compromising the microgrid resiliency to contingencies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Passivity-Based Control of Grid Forming and Grid Following Converters in Microgrids

With the integration of more and more power electronics devices into the grid, it is not easy to guarantee the stability of the whole system due to the complexity of the control structure of various power converters. In this paper, we consider grid-forming and grid-following converters in one microgrid, in which the grid-forming converters support the voltage and frequency of the microgrid and the grid-following converters inject their maximum power into the microgrid. To handle the stability issue, the passivity principle is applied to guarantee the stability of the whole microgrid. We ensure every grid-following converter satisfies the passivity via the port-controlled Hamiltonian method. In addition, we apply the passivity-based proportional-resonant controller to the grid-forming converter. One of the advantages of the proposed method is that the phase lock loop system is eliminated, which may cause stability issues. Simulation results show that the proposed method can control the microgrid effectively.

Gui, Yonghao (Young)↗

Control and Real-Time Simulation of Microgrids with EV Fast-Charging and Grid-Forming Resources

Fast charging stations (FCSs) for electric vehicles (EVs) can behave as constant power loads, which is problematic for the operation of grid-forming (GFM) inverter-based resources (IBRs). To tackle this problem, this paper proposes a control suite that makes FCSs responsive to ac voltage and frequency disturbances. To test the performance of the FCS controls, the paper also sets forth theory to compensate for time-delays appearing in the real-time simulation of microgrid models divided into several central processing units (CPUs). Furthermore, these contributions are showcased via multi-CPU real-time simulations of a faulted microgrid having EV FCSs and GFM IBRs powered by photovoltaic solar arrays as well as power hardware-in-the-loop experiments. These contributions are significant to address NERC recommendations and IEEE standards.

14 SOLAR ENERGY↗

New Safety Feedback Control Design to Guarantee Adequate Frequency Performance in Microgrids

Safety analysis of power systems is concerned with the system's ability to maintain critical variables within specified limits following a disturbance. Frequency control adequacy has become increasingly important as the system inertia decreases due to the increase in renewable energy penetration. Various controllers for inverters have been proposed to improve the system frequency response and few are capable to ensure the safety of the response. In this article, a diesel-wind energy system is considered and modeled as a switching system between normal, faulted, and post-fault modes. Further, a safety feedback controller is designed as a supplementary signal for a wind turbine generator such that the speed of the diesel generator stays within a permissible range in the presence of a finite energy disturbance. Numerical results on the modified 33-bus microgrid system obtained of the proposed novel approach indicate that the suggested control configuration can guarantee adequate frequency response without excessive conservativeness.

barrier function↗

Optimization-Based Dynamic Voltage Support of Microgrids Using Energy Storage Systems

A microgrid network is characterized by a high R/X ratio, making the voltage more sensitive to active power changes compared to bulk power systems, where the voltage is regulated primarily by reactive power. Due to its sensitivity, voltage control approaches for microgrids should also consider the active power input coupling, making it very different from conventional power systems. Additionally, as the energy costs associated with active and reactive powers are different and the operational conditions of microgrids connected to active distribution systems vary over time, the ideal controller to provide voltage support must be flexible enough to handle these technical and operational constraints. This paper proposes a model predictive control approach to provide dynamic voltage support using energy storage systems. This approach uses a simplified predictive model of the system to solve the model predictive control problem. By proper selection of model predictive control weighting parameters, the quality of service provided can be adjusted to achieve the desired performance. A simulation study in MATLAB/Simulink validates the proposed approach for the Cordova, Alaska microgrid. Results show that the performance of the voltage support can be adjusted depending on the choice of weight and constraints of the controller.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Resilience Analysis of DC Microgrids under Denial of Service Threats

This paper develops a resilience analysis framework to study the fault ride-through capability of direct current (DC) microgrids in unknown denial of service (DoS) cyber incidents. DoS can be a frequent threat to DC microgrids with advanced controllers that hinge on active information exchanges: it can paralyze data communications and cause control ineptness or even system instability. Furthermore, we show that temporal DoS incidents render the DC microgrid cyber-physical topology and parameters time-varying and cause them to jump between faulty conditions. As existing DC microgrid stability analysis results are primarily developed from time-invariant systems, they might not be valid for the DoS interrupted systems. In this paper, we seek to study whether a DC microgrid is resilient against time-varying unknown DoS incidents. The problem is formulated as a stability analysis problem for a system with randomly switching dynamics. Scalable conditions are developed to provide provable resilience guarantees. In addition, we exploit the special structure of the conditions to yield quantified resilience measure by convex optimization techniques. As a result, the measure can be used for the evaluation of the resilience of different DC microgrid design against DoS incidents. We demonstrate the effectiveness of the proposed work using simulation case studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Uncovering Droop Control Laws Embedded Within the Nonlinear Dynamics of Van der Pol Oscillators

This paper examines the dynamics of power-electronic inverters in islanded microgrids that are controlled to emulate the dynamics of Van der Pol oscillators. The general strategy of controlling inverters to emulate the behavior of nonlinear oscillators presents a compelling time-domain alternative to ubiquitous droop control methods which presume the existence of a quasistationary sinusoidal steady state and operate on phasor quantities. We present two main results in this paper. First, by leveraging the method of periodic averaging, we demonstrate that droop laws are intrinsically embedded within a slower time scale in the nonlinear dynamics of Van der Pol oscillators. Second, we establish the global convergence of amplitude and phase dynamics in a resistive network interconnecting inverters controlled as Van der Pol oscillators. Furthermore, under a set of nonrestrictive decoupling approximations, we derive sufficient conditions for local exponential stability of desirable equilibria of the linearized amplitude and phase dynamics.

24 POWER TRANSMISSION AND DISTRIBUTION↗