LuSEE-night power distribution system design

The Lunar Surface Electromagnetic Experiment at Night (LuSEE-Night) is a low-frequency, 0.5 to 50 MHz, radio experiment on the radio-quiet far side of the Moon. The instrument will be launched by NASA Commercial Lunar Payload Services in 2026. The LuSEE-Night instrument core is composed of a radio frequency spectrometer (SPT) processing signals from four antennas, the Data Controller Board (DCB), low electromagnetic interference (EMI) Picket Fence Power Supply (PFPS), and Power Distribution Unit (PDU). The battery powers the instrument during the lunar night and stores energy harvested by the solar panel array during the lunar day. The battery charging is controlled by the Power Conditioning and Distribution Unit (PCDU). The unregulated power is supplied either by the SpaceCraft (S/C) or the battery and gets distributed to the PFPS, communication radio, heaters, and deployables through the PDU. The PFPS generates all regulated low-voltage rails using switching regulation synchronized to the LuSEE-Night clock, which ensures self-generated EMI will be confined to well-defined frequency bins. Here, we discussed the unregulated power distribution system architecture and functionality. The PDU engineering and flight modules are developed and characterized to confirm compliance with LuSEE-Night requirements. At the time of writing, all power subsystem components have been integrated into the payload.

47 OTHER INSTRUMENTATION↗

Investigating the Vulnerabilities of the Direct Transfer Trip Scheme for Network Protector Units in the Secondary Networks of Electric Power Distribution Grids

Network protector units (NPUs) are crucial parts of the protection of secondary networks to effectively isolate faults occurring on the primary feeders. When a fault occurs on the primary feeder, there is a path of the fault current going through the service transformers that causes a negative flow of current on the NPU connected to the faulted feeder. Conventionally, NPUs rely on the direction of current with respect to the voltage to detect faults and make a correct trip decision. However, the conventional NPU logic does not allow the reverse power flow caused by distributed energy resources installed on secondary networks. The communication-assisted direct transfer trip logic for NPUs can be used to address this challenge. However, the communication-assisted scheme is exposed to some vulnerabilities arising from the disruption or corruption of the communicated data that can endanger the reliable operation of NPUs. This paper evaluates the impact of the malfunction of the communication system on the operation of communication-assisted NPU logic. To this end, the impact of packet modification and denial-of-service cyberattacks on the communication-assisted scheme are evaluated. The evaluation was performed using a hardware-in-the-loop (HIL) co-simulation testbed that includes both real-time power system and communication network digital simulators. This paper evaluates the impact of the cyberattacks for different fault scenarios and provides a list of recommendations to improve the reliability of communication-assisted NPU protection.

direct transfer trip↗

Modeling Framework for Data Center

This chapter highlights the critical need for advanced modeling of data centers due to their rapidly increasing energy consumption and impact on grid reliability. Driven by the demand for AI applications, data centers are projected to consume a significant portion of US energy by 2028, putting stress on an already challenged power grid. The chapter emphasizes the importance of "fast" time-scale models to understand the dynamic interactions between data centers and the grid, especially given the rapid power fluctuations of AI workloads. It outlines a modeling framework that includes both offline and real-time EMT domain simulations, detailing the necessary representations for various components like utility interfaces, transformers, IT loads, UPS, cooling loads, Battery Energy Storage Systems (BESS), generators, protection systems, and higher-level control systems. While standard simulation tools like PSCAD offer basic models, custom development is often required to accurately capture the unique and fast-changing behaviors of modern data centers. The chapter also discusses key metrics and test cases for validating these models, focusing on transient load responses, protection relay coordination, and demand flexibility. Finally, it addresses the challenges of modeling large-scale data centers, such as computational complexity and the trade-off between model fidelity and practicality, suggesting hybrid modeling approaches as a solution. The overarching goal is to create a robust framework that helps assess data center impacts on grid stability, identify vulnerabilities, and inform the development of standards for reliable integration of these large loads into the bulk power system.

25 ENERGY STORAGE↗

Coordinated operation of pumped-storage hydropower with power and water distribution systems

Small pumped-storage hydropower (PSH) units have gained popularity as distributed energy storage options that can provide flexibility to the operation of power distribution systems. Optimal operation of small PSH units is not only dependent on the energy storage provided to power distribution system, but also on the inflow and outflow of water from and to the water distribution system. Here, in this context, this paper develops an optimization model for coordinated operation of PSH units with power and water distribution systems. The proposed model optimizes the operation of water tanks, variable-speed pumps and PSH in pumping and generating modes to minimize the operation cost of power distribution system, while respecting the power flow constraints of power distribution and hydraulic constraints of water distribution system. Appropriate electricity tariffs are implemented to avoid additional expenses in water distribution system that can be enforced by its coordinated operation in favor of power distribution system. The proposed model is implemented on a 33-bus and a 123-bus test power distribution system connected to a 16-node test water distribution system. Results demonstrate the effectiveness of proposed model in tapping PSH flexibility to reduce the operation cost of power and water distribution systems, while meeting the power and water demands.

13 HYDRO ENERGY↗

Data Management for Digital Twin Implementation: Enhancing Existing SCADA Architecture for INL's CITRC Test Distribution System

The United States power grid will continue to experience stress from aging infrastructure, extreme weather, and increasing loads. In order to strengthen resiliency, researchers need to run tests and simulations that model real-life infrastructure. Idaho National Laboratory (INL) is creating a digital twin of its Critical Infrastructure Test Range Complex (CITRC). CITRC is an at-scale grid testbed which can be configured in utility-realistic distribution scenarios for a variety of tests, such as advanced grid protection and control. A digital twin of this infrastructure would support in-depth tests/simulations without risking physical consequences, before trialing devices under test at-scale. This project focuses on the data acquisition part of constructing a digital twin. It investigates the Supervisory Data Acquisition and Control (SCADA) system of CITRC and explores ways to utilize this system for the twin. Future “ideal” at-scale implementations such as upgraded equipment, modern communication protocols, and automation applications are also explored.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Battery Degradation Modeling in Hybrid Power Plants: An Island System Unit Commitment Study: Preprint

As hybrid power plants (HPPs), such as photovoltaic (PV) and battery combinations, become increasingly important in power systems with high renewable energy penetration to address PV variability and ensure grid stability. This paper focuses on the urgent need to model the coordination between PV and battery systems in HPPs while accounting for battery degradation. We present a generation scheduling model that explicitly incorporates PV-battery hybridization in the unit commitment problem. Moreover, the cost function of the HPP scheduling problem endogenously considers battery degradation with adjustable weights to strike a balance between minimizing production costs and prolonging battery life, particularly when providing energy arbitrage and ancillary services. Using a realistic island system simulation, we demonstrate that accounting for battery degradation in the scheduling problem can significantly extend battery life with only minor additional production costs.

battery degradation↗

Predictive and Cooperative Voltage Control with Probabilistic Load and Solar Generation Forecasting

This paper proposes predictive cooperative voltage control method in a power system with high penetration of photovoltaic (PV) units. Cooperative distributed control of the reactive power output of PV inverters is coordinated with operation of voltage regulators (VRs) to maintain system voltages within an appropriate bandwidth. Probabilistic forecasting of the solar power generation and the loads is applied to estimate voltage changes which, in turn, are used to set the VR tap positions for preventing large voltage fluctuations with the lowest risk considering the voltage distribution estimation. The fine tuning of voltage adjustment is achieved by cooperative control of PV inverters to maintain a uniform voltage profile across the system. The proposed method is tested on the modified IEEE 123-node test feeder with high PV penetration using real insolation data and with constant loads replaced by several different load profiles. Simulation results demonstrate the effectiveness of the coordinated approach for voltage control with cooperative PV and predictive VR controls taking into account probabilistic load and solar power forecasts.

Cooperative Control↗

2021 Cost of Wind Energy Review [Slides]

This analysis uses representative utility-scale and distributed wind energy projects to estimate the levelized cost of energy (LCOE) for land-based, offshore, and distributed wind power in the United States. Data and results detailed here are derived from 2021 commissioned plants and representative industry data as well as state-of-the-art modeling capabilities. Modeling is conducted to provide more granular detail on specific cost categories. This study represents the 11th annual installment and is intended to provide insight into current component-level costs as well as a basis for understanding variability in wind energy LCOE across the country.

17 WIND ENERGY↗

Weather-Driven Resilience for Distribution Systems

With increasing billion dollar disasters due to weather events, it is of utmost priority for utility and grid operators to maintain and enhance the resilience of distribution grid. Traditionally, such analysis were conducted with reliability metrics alone. However, with increasing complexity of distribution grid and advancements in grid edge resources, evaluating grid resilience is challenging and involves multi-faceted analysis of the impact of weather events on the distribution grid. This presentation provides background, details, and future works in the field of weather-driven resilience for power distribution systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Architectural Approaches for Integrating ADMS and DERMS: Challenges, Comparisons, and Real-World Use Cases

The electrical distribution landscape is rapidly transforming due to the proliferation of distributed energy resources (DERs) such as solar panels, wind turbines, battery storage systems, combined heat and power units, and electric vehicles, introducing variability and uncontrollability that traditional grid operators are ill-equipped to manage. This transformation is further accelerated by advancements in Information and Communication Technology infrastructure that connects control centers with end devices, demanding automation and a deeper understanding of new technologies by utility personnel. Advanced grid control techniques using system-level optimization, Artificial Intelligence, and Machine Learning at the enterprise level and distributed level are evolving to address these issues. There is also an opportunity to utilize the enormous data created by these new DER technologies in the grid. Advanced Distribution Management Systems (ADMS) and Distributed Energy Resource Management Systems (DERMS) are critical in addressing these challenges by automating grid operations and enhancing reliability. Given the relatively recent development of ADMS and DERMS, and the still relatively low level of ADMS and DERMS deployment in the industry, there is a notable deficiency in the comprehensive understanding of the challenges and benefits associated with these new technologies, especially with their complementary natures and integration architectures. This paper aims to bridge the knowledge gap in ADMS and DERMS integration, presenting three distinct integration architectures currently available, and discussing the challenges and benefits of each architecture to guide utilities, industry professionals, and researchers in optimizing grid management and decision-making processes for a resilient and efficient energy future.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Energy, power, and infrastructure demands from electrifying airport ground support equipment at United States airports

As the airline industry seeks to reduce costs and transition to clean energy, electric ground support equipment is emerging as a favorable option. The integration of electric ground support equipment into airport operations requires careful planning for vehicle deployment, charging infrastructure, and grid impacts. We develop a flexible, bottom-up modeling framework to assess energy and infrastructure needs across more than 300 U.S. airports. Our analysis estimates site-specific power and energy demand, equipment counts by type, charger requirements, and costs. Here we quantify the magnitude of new electrical loads created by the electrification of airport ground support equipment, finding that peak power demand at the largest airports can reach up to 20 megawatts, with annual electricity consumption approaching 51,000 megawatt-hours. We further show that behind-the-meter battery energy storage systems and solar photovoltaic systems can reduce peak load and lower total system costs by as much as 10 million dollars.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Predictive Coordinated and Cooperative Voltage Control for Systems With High Penetration of PV

In this paper, we propose a predictive coordinated and cooperative voltage control method in a power distribution system with high penetration of photovoltaic (PV) units. First, an integrated coordinated voltage control of voltage regulators (VRs) tap positions and cooperative distributed control of the reactive power output from PV inverters are used to maintain system voltages within an appropriate bandwidth. Next, solar power forecasting is applied to predict voltage changes, which are used to set the VR tap positions and capacitor switch status to prevent large voltage fluctuations. The fine tuning of voltage adjustment is then achieved by cooperative control of PV inverters to maintain a uniform voltage profile across the system. The proposed method is tested on a modified IEEE 123-node test feeder with high penetration of PVs using real measurement data and compared with the base case. Simulation results demonstrate the effectiveness of the integrated voltage control, as well as the enhancement from the predictive control through solar power forecasting-enabled voltage change estimates. Comparison to previous work in the literature shows significant improvement in terms of voltage deviation and reduction in excessive tap changes.

14 SOLAR ENERGY↗

Solving the Grid Optimization Competition Challenge 3 Problem

The Grid Optimization Competition Challenge 3 Problem posed a multiperiod security-constrained unit commitment problem with base-case AC power flow. The problem formulation includes binary unit commitment decisions, nonlinear AC power flow and balance, dispatchable loads, and linearized contingency real power flow, among other features. This talk will present a modified consensus ADMM algorithm, which splits the problem into mixed-integer linear and nonlinear components, as a heuristic solution method for this large-scale mixed integer nonlinear program. We will present some computational results from the competition for our implementation and reflect on the challenges of participating the grid optimization competition.

AC power flow↗

United Kingdom's Action Plan for Power Sector Decarbonisation

A collaborative report from the Clean Energy Ministerial (CEM) on Lessons Learned for Rapid Decarbonization of Power Sectors was delivered to energy ministers and presented at CEM13 in the United States in September 2022. In light of these lessons learned and discussed at CEM13, several countries signaled intent to develop Action Plans for power sector decarbonization that will be presented at CEM14 in India. These action plans complement but are differentiated from other international power sector initiatives such as the Breakthrough Agenda whose broad purpose is to raise collective ambition and the Global Power System Transformation (G-PST) Consortium whose goals are to convene power system operators to accelerate research innovations and foster peer learning. These action plans, supported by the 21st Century Power Partnership (21CPP) and other CEM workstreams via direct technical assistance and capacity building, are instead intended to focus on implementation actions given each country's existing power sector goals and activities and are an opportunity for countries to display leadership in power sector decarbonization. These action plans are voluntary, developed by each country individually, and can be viewed as a living document that is subject to change.

decarbonization↗

Power grid frequency prediction using spatiotemporal modeling

Understanding power system dynamics is essential for interarea oscillation analysis and the detection of grid instabilities. The FNET/GridEye is a GPS-synchronized wide-area frequency measurement network that provides an accurate picture of the normal real-time operational condition of the power system-dynamics, giving rise to new and intricate spatiotemporal patterns of power loads. We propose to model FNET/GridEye grid frequency data from the U.S. Eastern Interconnection with a spatiotemporal statistical model. We predict the frequency data at locations without observations, a critical need during disruption events where measurement data are inaccessible. Spatial information is accounted for either as neighboring measurements in the form of covariates or with a spatiotemporal correlation model captured by a latent Gaussian field. Finally, the proposed method is useful in estimating power system dynamic response from limited phasor measurements and holds promise for predicting instability that may lead to undesirable effects such as cascading outages.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Decentralized Data-Driven Estimation of Generator Rotor Speed and Inertia Constant Based on Adaptive Unscented Kalman Filter

This paper proposes an online decentralized and data-driven method for synchronous generator rotor speed and inertia estimation. First, an analytical relationship between the generator terminal voltage/current phasors and its internal rotor speed is derived using the Thevenin equivalent. The parameters of the latter are obtained via a recursive estimator, which allows us to estimate the generator's internal rotor speed from voltage/current phasors without the need for any generator information. Second, we reformulate the equivalent swing equation into the Kalman filter form, which enables us to use a priori-estimated internal rotor speed along with measured real and reactive power injections to obtain an estimate of the inertia for each online synchronous generator. This is achieved through an adaptive unscented Kalman filter. We demonstrate that the use of terminal bus frequency to approximate the rotor speed for inertia estimation by existing methods leads to large estimation biases/errors. Numerical simulations carried out on the IEEE 39-bus and Texas 2000-bus systems reveal that our proposed method is consistently more accurate than existing methods. Moreover, our proposed method is insensitive to both the type and location of system disturbances, and it is robust to different levels of measurement noise.

bus frequency↗

Secure and Cost-Effective Micro Phasor Measurement Unit (PMU)-Like Metering for Behind-the-Meter (BTM) Solar Systems using Blockchain-Assisted Smart Inverters

Recently, there is increasing interest in using behind-the-meter (BTM) solar systems for grid services. However, providing visibility and operational situational awareness of BTM solar systems mainly operated by small-scale solar inverters is challenging due to the requirement of relatively expansive networked observation tools (e.g., micro phasor measurement units (µPMUs)) and consequent cybersecurity threats through networks. This paper presents a secure, cost-effective, µPMUs-like metering method using a blockchain-assisted smart (BAS) inverters for a BTM solar system. The proposed BAS inverter consisting of an internet of things device as a node of a local blockchain network enables the secure provision of inverter measurement data for grid services. The BAS inverter sends the encrypted local measurement data with a timestamp to a local blockchain miner. Once the blockchain miner generates a tamper-resistant metering ledger including the measurements, it is used to assess the situational awareness of the BTM solar system. The concept of the proposed metering using the BAS inverters is validated by experimental studies.

behind the meter↗

Evaluating Methods for Measuring Grid Frequency in Low-Inertia Power Systems: Preprint

Accurate measurement of grid frequency is a critical component of reliable grid control. Traditionally, methods such as phase locked loops (PLLs) and discrete Fourier transforms (DFTs) have been used in inverters and phasor measurement units (PMUs) to measure frequency. However, as the percentage of inverter-based resources (IBRs) such as solar and wind has increased, these conventional frequency measurement methods are proving unable to guarantee reliable control in some cases. One challenge is measuring frequency during transient events, where there is a disruption in the steady state sinusoidal voltage. During these events, the underlying frequency of the grid may barely change, but measurement methods report a large spike in frequency due to the disrupted waveform. New methods must balance between suppressing spikes in frequency during faults, and providing fast, accurate, measurements in all other grid operation conditions, especially during events with high rate-of-change-of frequency (ROCOF), which are more prevalent in high-IBR power systems. This paper first surveys frequency measurement methods that have been proposed to reduce measurement errors during transient events. Then, both conventional and more novel frequency measurement methods are tested against an IEEE standard and industry recommendations, and their performance is evaluated for events simulated in PSCAD. Results quantify the trade-offs in performance during different grid conditions and lead to suggestions for the most appropriate frequency and ROCOF measurement methods for low inertia grids.

frequency↗