Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “modular multilevel converter (MMC)”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Modular Multilevel Converter (MMC) Modeling Considering Submodule Voltage Sensor Noise

The modular multilevel converter (MMC) is a popular topology in medium- and high-voltage applications, and many efforts have been spent on MMC modeling. However, the impact of submodule voltage sensor noise (SVSN), which becomes more severe due to increasing switching speed of power semiconductors and compact submodule design, has not been considered in conventional models. In this letter, the SVSN is introduced by coupling capacitances between the sensor and power stage in an MMC switching model. Furthermore, the SVSN impact is considered in an MMC average model based on derivation of the relationship between the SVSN and the duty cycle. Here, the proposed MMC switching model and average model considering the SVSN are validated by comparing simulations with experimental results in an MMC prototype using 10-kV SiC MOSFETS.

47 OTHER INSTRUMENTATION↗

Modeling and Harmonic Stability of MMC-HVDC With Passive Circulating Current Filters

A modular multilevel converter (MMC) is an emerging converter technology widely used in wind power applications using high-voltage direct current (HVDC) transmission, and it has been largely investigated in medium-voltage solar harvesting as well as electric motor drives. Different from studies dealing with active circulating current control loops, this paper focuses on impedance modeling and harmonic stability studies for MMCs with passive circulating current filters (PCCFs). A power stage circuit including a PCCF is transformed and remodeled to obtain small-signal formulations. This transformation leads to additional high-order matrix computing complexity due to the added impedance subnetwork matrix from the PCCF as well as relevant crossed-frequency impacts. To simplify the computational burden, the proposed model aims to solve one arm equation instead of all six MMC arm equations. To achieve this result, additional challenges occur when the MMC is connected to a renewable energy source instead of the grid voltage, where low-level zero-sequence components might exist in the neutral point of three phases, especially in the case of no integrated advanced modular voltage balancing control, which prevents computational simplification. To overcome this challenge, further impedance matrix adjustments are conducted in this paper to theoretically suppress the impact of zero-sequence harmonics when obtaining small-signal impedance, taking into account the frequency coupling effect. Finally, simulations are carried out to validate the developed impedance model under different operating scenarios. Harmonic stability case studies of MMCs with PCCFs connected to renewable energy current sources are also presented, where frequency-domain stability analyses based on Bode diagrams are compared to time-domain simulation waveforms and FFTs, which validate the effectiveness of the proposed impedance model.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Novel Voltage Balancing Control With dv/dt Reduction for 10-kV SiC MOSFET-Based Medium Voltage Modular Multilevel Converter

Using high voltage (HV) silicon carbide (SiC) power semiconductors in a modular multilevel converter (MMC) is promising because it results in fewer submodules and lower switching loss compared to conventional Si based solutions. The nearest level pulsewidth modulation (NL-PWM) is commonly used in the MMC for medium voltage applications. However, with the NL-PWM and existing voltage balancing control, there are many submodules that switch their modes in a control cycle, resulting in a high dv/dt during the deadtime of the power semiconductor, which could be multiple times of the dv/dt of the single device. This poses great challenges on the noise immunity and insulation design in the MMC using HV SiC devices, which have very fast switching speed. A novel voltage balancing control, which ensures only two submodules switch their modes in a control cycle, is proposed in this article, limiting the maximum dv/dt to the dv/dt of a single power semiconductor and also maintaining the voltage balance performance. Furthermore, the proposed voltage balancing control is experimentally validated in a 10-kV SiC mosfet based MMC with four submodules per arm.

42 ENGINEERING↗

Hardware Design of Medium Voltage SiC-Based Modular Multilevel Converters for Grid-Tied Applications

This paper presents a design of a 10 kV silicon carbide (SiC) MOSFET based modular multilevel converter (MMC). The MMC functions as the interconnection between a 24 kV dc bus and a 13. SkV distribution grid. This paper focuses on the hardware design of the MMC and its submodules. The gate driver, auxiliary power supply and bus bur in submodules are major components that need to meet high dv/dt immunity and high insulation voltage requirements. The gate driver achieves over 200 kV/us common mode transient immunity (CMTI). Its associated auxiliary power supply is based on an on-board transformer with over 30 kV insulation capability and 1.4 pF barrier capacitance. The busbar achieves less than 11 kV/cm electric field in the air to avoid partial discharges. Validation tests of the MMC submodule were performed by double pulse tests at 5 kV and buck converter tests at3 kV, 52A (peak). Reliable operations were achieved in validation tests.

auxiliary power supply↗

Control and Grid Support Function Evaluation for a Three-Phase Back-to-Back Modular Multilevel Converter System

This paper focuses on the evaluation of advanced inverter controls for a 500kW back-to-back (B2B), silicon carbide, multilevel modular converter (MMC) used as a direct-connected medium-voltage grid intertie. A decentralized hierarchical controller architecture for the MMC system is presented, which uses the main controller to implement higher level grid interconnection functions per the IEEE 1547–2018 standards and the local controllers to execute lower level closed-loop functionality of the MMC stages. This paper presents and elaborates on the grid functionalities are elaborated and presented. The back-to-back converter system is equipped with local controllers and their corresponding functionalities are presented. Case study results for the corresponding functionalities presented show the effectiveness of the proposed architecture. To enhance the operation capabilities of the system, a parameter update scheme has been implemented and utilized in unison with the controller.

decentralized control↗

Open-circuit submodule fault diagnosis in MMCs using support vector machines

Series connection of semiconductor submodules (SM) in a modular multilevel converter (MMC) makes the MMC prone to open-circuit (OC) IGBT failures inside SMs. If left undetected, these faults degrade the operation of the MMC and lead to its instability. This article proposes a method to detect, localise, and classify single OC SM faults in an MMC using support vector machines (SVM) trained with data obtained from the capacitor voltage balancing block of the MMC control system. The proposed method relies on data extracted from the sorted capacitor voltage arrays of the upper and lower phase arms. Therefore, it does not require extra measurements and hardware. Additionally, it offers a fixed time for detecting and localising OC SM faults. This method is easy to implement as SVM has a simple decision function. Time-domain simulation case studies are performed on a three-phase nine-level MMC to evaluate the performance of the proposed method.

42 ENGINEERING↗

Fast and fault-tolerant model predictive control of MMCs under selective harmonic elimination

Selective harmonic elimination (SHE) is a suitable pulse-width modulation (PWM) tech-nique for some applications of modular multilevel converters (MMC) with lower numberof semiconductor submodules (SM). However, SHE can make it difficult to control circu-lating currents in the MMC. Moreover, the MMC is vulnerable to SM switch failures thatreduce its output power magnitude and quality. This paper proposes a fault-tolerant modelpredictive control strategy for MMCs operating with SHE (FT SHE-MPC). The effects ofswitch failure on phase voltage waveforms are studied first. Then, a method is proposedto design the FT SHE waveform to preserve its harmonic performance. Next, the pro-posed FT SHE-MPC is designed to increase the capacitor voltages during an SM failure tomaintain the fundamental component of the faulty phase voltage and control the circulat-ing currents, maintaining balance among line voltages and the output power of the MMC.Additionally, the proposed method offers as much as 60% faster FT transition time and asmuch as 36% lower capacitor voltage ripple. The advantages of the proposed method areverified through offline and real-time simulation studies on a three-phase nine-level MMCin PSCAD/EMTDC software and RTDS.

42 ENGINEERING↗

Adaptive Narrowband Damping for Improving Harmonic Stability of Modular Multilevel Converter

Harmonic instability events between modular multilevel converter (MMC) and ac systems have been widely reported in recent years. To damp harmonic resonance, this paper proposes an adaptive narrowband damping control that automatically programs, adds, and adjusts the damping around the oscillation frequency when an oscillation is detected. First, the paper presents a low-pass filter design for MMC control loops that pushes all negative damping of the MMC impedance down to the medium-frequency range (< ~ 1000 Hz). Then, an adaptive damping control that uses online oscillation detection is proposed, which can automatically configure the narrowband damper to provide positive damping to the MMC around the detected oscillation frequency. In contrast to existing narrowband damping methods, the proposed adaptive narrowband damper dynamically adjusts the damping gain and the width of the damping range based on continuous monitoring of system resonance conditions (e.g., adjust damping gain to zero when the system resonance disappears). Electromagnetic transient simulation results validate the efficacy of the proposed method in two typical MMC-based power systems.

active damping↗

Design Paradigm for Modular Multilevel Converter-Based Generator Rectifier Systems

Modular Multilevel Converters (MMC) are being widely considered for medium to high voltage DC applications. Designing such converters through multi-objective optimization is of interest because such an approach allows the trade-off between competing objectives (for example mass and loss) to be explicitly and quantitatively identified. In this work, an optimization based design paradigm for MMC based generator rectifier systems is proposed. Such development typically requires detailed component design and simulation models for the electric machine and converter which are computationally expensive. As an alternative, the proposed work utilizes an electric machine metamodel, inductor metamodel, and high-speed steady-state simulation model for the MMC to facilitate multi-objective optimization minimizing system metrics of interest while satisfying system constraints. A case study is undertaken to demonstrate the functionality of the proposed design paradigm.

42 ENGINEERING↗

Advanced Models and Fast Simulation Algorithms for MARS Plants

With the successful commercialization of modular multilevel converters (MMC) and rapid increase in photovoltaic (PV) penetration and energy storage systems (ESS), one of the research areas being explored dynamically is integration of PV systems and ESS systems to MMCs. On this front, an integrated development of PV plants, ESS, and alternating- and direct-current (ac/dc) systems through Multi-Port Autonomous Reconfigurable Solar (MARS) plant is proposed and being researched upon. However, simulation of MARS systems on traditional existing software takes very long time (order of days) due to the presence of a large number of states and non-linear devices. Therefore, development of fast high fidelity models is of paramount importance to test the hardware design, control design and planning of power system expansions. In this context, two research objectives are addressed in this paper: firstly, an ultra fast single- or multi- CPU simulation algorithm to simulate the MARS system based on state-space models, hybrid discretization algorithm with a relaxation technique that reduces the imposed computational burden and a multi-rate method is presented. Secondly, a reduced order model of MARS is also presented. Both the developed techniques are validated with respect to reference PSCAD/EMTDC model.

Marthi, Phani Ratna Vanamali↗

Control Oriented Models for Co-Design: Technical Overview of MT HVDC, MVDC, and Solid State Transformer Building Blocks

The electric power system is shifting toward a power electronics–enabled grid, where converter based “building blocks” (e.g., high voltage direct current (HVDC) links, multi terminal HVDC (MT HVDC) networks, medium voltage DC (MVDC) links, and solid state transformers (SSTs)) provide fast, precise control of power flows, voltage, and frequency. This report develops and applies publicly shareable electromagnetic transient (EMT) and phasor models to examine how such building blocks can be composed and coordinated to support offshore wind integration, inter area transfers, feeder support, and resilience. Section 2 documents a modular multilevel converter (MMC)–based MT HVDC modeling framework and two use cases: a compact WSCC/IEEE 9 bus test system and a 240 bus “mini WECC” case with five offshore wind plants (OWFs). Phasor to EMT transfer, initialization, and sanity checks are summarized, and neutral demonstrations of normal and contingency operation are reported. Section 3 frames the problem of wind plant inertial frequency response (IFR): shaping energy release and recovery to improve nadir while avoiding aerodynamic stall; representative simulations illustrate the issues without disclosing proprietary control. Section 4 develops MVDC concepts through an IEEE 16 bus loop and an Olympic Peninsula case study that compares AC vs. MVDC corridors and shows how feeder headroom can be pooled via DC couplers. Section 5 surveys SST architectures and identifies a gap: scalable, communication free coordination of multiple SSTs for islanded feeder networks. Across the report, novel methods and configurations under separate publication and IP review are not disclosed; only topic oriented, replicable setups and non proprietary results are shown. These models and use cases are intended as foundations for future publications and co design studies on architecture, control, and coordination of PE enabled grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Adaptive Narrowband Damping for Improving Harmonic Stability of Modular Multilevel Converter: Preprint

Harmonic instability events between modular multilevel converter (MMC) and ac systems have been widely reported in recent years. To resolve it, this paper proposes an adaptive narrowband damping control that automatically programs, adds and adjusts damping around the oscillation frequency when detect the oscillation. The paper first presents a low-pass filter design for MMC control loops, which pushes all negative damping of MMC impedance down to the medium frequency range (< approximately 1000 Hz). This makes narrowband damping can be more targeted and easier to design because multiple harmonic oscillations are avoided. An adaptive damping control that uses online oscillation detection is then proposed, which can automatically configure the narrowband damper to provide damping to the MMC at the detected oscillation frequency. In contrast to existing narrowband damping methods, the proposed adaptive narrowband damper adjusts the damping gain (e.g., to zero when system resonance disappears) and the width of the damping range automatically based on continuous monitoring of system resonance conditions. Electromagnetic transient (EMT) simulation results validate the efficacy of the proposed method in two typical MMC-based power systems.

active damping↗

Active Fault Current Limiting Control for Half-Bridge MMC in HVDC Systems

DC faults of MMC can result in a significantly large fault current due to the discharge of submodule capacitors. The fault current not only risks damaging the MMC but also demands a considerable breaking capacity from the dc circuit breaker (DCCBs). This paper introduces two novel active fault current limiting methods (AFCLs), namely virtual impedance-based and energy control-based AFCL. The first method utilizes circulating current feedforward, which introduces a virtual arm impedance to suppress the rate of rise of the fault current. Meanwhile, the second method relies on the control of the internally stored energy of the MMC to automatically minimize the number of submodules that discharge during a dc-side fault. Therefore, both the dc-side current and the MMC arm current can be effectively suppressed after the occurrence of the fault. The proposed methods do not require fault detection and their response is proportional to the rate of rise in the fault current. Simulation case studies are presented to demonstrate the proposed methods.

active current limiting control↗

Analysis of Transformer Magnetizing Reactance Using Describing Function in Direct Power Control of Back-to-Back Modular Multilevel Converter with Advanced Grid Support

This paper presents a Port Controlled Hamiltonian based direct power control architecture for a back-to-back modular multilevel converter system connecting two ac sources at different frequencies. The system features advanced grid support functionalities based on IEEE 1547-2018, implemented on the inverter side. The rectifier side controller ensures reference following for active and/or reactive powers and maintains the commanded dc bus voltage. The inverter side controller ensures power command following for active and reactive powers.The proposed control architecture is designed to suppress second harmonic oscillations in powers during unbalanced grid voltage sags by dynamically adjusting the currents on each ac side. This also ensures effective elimination of any second harmonic oscillations in the equivalent dc bus voltage. Validation is performed on an OPAL-RT real-time platform with case studies on unbalanced and balanced sags, demonstrating the controller's effectiveness during real time implementation. A reduced-scale laboratory prototype further verifies these case studies, with experimental results for balanced sags due to grid simulator limitations. The results confirm the robustness and efficiency of the proposed control strategy in ensuring stable and reliable operation under various grid conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Adaptive Threshold-Based Zonal Isolation of Faults in a Multiterminal DC Using Local Measurements

Fast and accurate methods of fault detection and isolation are a pre-emptive measure in multiterminal dc (MTdc) systems. Zonal isolation of faults is necessary to prevent any misopertation of the dc breakers that can lead to a shutdown of the network. Existing techniques require fast-communication or data synchronization methods have their own disadvantages. This article proposes a method for efficient fault zone isolation without the need of a communication link that prevents any misoperation of the dc breakers in a radial MTdc. This method provides individual local measurement-based control to the hybrid dc circuit breakers (dcCB). Faults created outside the zone of protection for a breaker create a change in the rate of change of current or voltage leading to misoperation. To avoid detection using a fixed threshold, an adaptive threshold based approach is suggested that updates the threshold based on the present operating status. Sensitivity analysis by varying the current limiting inductance and fault location is performed. In conclusion, a three terminal radial model of an MTdc is used for zonal isolation using power system computer aided design/electromagnetic transients including dc.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling and ZVS Operation of the Isolated Modular Multilevel DC–DC Converter With a Unified Trapezoidal Wave Modulation

Here, this article introduces a unified trapezoidal wave (UTW) modulation scheme for the isolated modular multilevel dc–dc (IM2dc) converter, which consolidates multiple existing modulation strategies for the IM2dc converter, including the quasi-square wave (QSW) modulation, trapezoidal wave modulation, and sinusoidal wave modulation, into a unified framework. Furthermore, this article introduces the harmonic state-space (HSS) equations to model the IM2dc converter based on the UTW modulation method. The HSS model operates in the frequency domain, enabling it to circumvent the complexities associated with time-domain analysis and seamlessly integrate with the UTW modulation. This article proceeds to analyze the real and reactive power transfer characteristics of the IM2dc converter, as well as the power factor, considering the influence of multiple modulation parameters. Subsequently, it delves into the examination of zero voltage switching (ZVS) conditions for the IM2dc converter based on the UTW modulation and the HSS model. The complete ZVS boundaries of the IM2dc converter, taking various voltage ratios into account, are derived. This article also illustrates the effects of including harmonic orders in the modeling process, modulation parameters, and internal harmonic ripples on the ZVS boundaries. Finally, experimental validation of the analyses is conducted on a down-scaled prototype.

42 ENGINEERING↗

Operation and control of hybrid HVDC system with LCC and full-bridge MMC connected in parallel

In this study, a new kind of hybrid high-voltage direct current (HVDC) system is proposed. Each terminal of the proposed system consists of one line commutated converter (LCC) and one full-bridge modular multilevel converter (FB-MMC). The LCC and FB-MMC are connected in parallel so that they can share the same transmission line. The active–reactive power capability of the hybrid HVDC system is extended compared with the conventional LCC-HVDC system, and power reversal control without power interruption can be achieved by the coordination control of LCC and FB-MMC. Besides, the proposed hybrid HVDC system is capable of handling DC fault, because both LCC and FB-MMC have DC fault blocking capability. Moreover, the power rating of FB-MMC can be designed to low value while keeping the bulk-power transmission capability of LCC. A two-terminal bipolar hybrid HVDC system is built in PSCAD/EMTDC. The simulation results verify the effectiveness and feasibility of the proposed hybrid topology and corresponding control strategies.

42 ENGINEERING↗

Hybrid EMT-TS Simulation Strategies to Study High Bandwidth MMC-Based HVdc Systems

Modular multilevel converters (MMCs) are widely used in the design of modern high-voltage direct current (HVdc) transmission system. High-fidelity dynamic models of MMCs-based HVdc system require small simulation time step and can be accurately modeled in electro-magnetic transient (EMT) simulation programs. The EMT program exhibits slow simulation speed and limitation on the size of the model and brings certain challenges to test the high-fidelity HVdc model in system-level simulations. This paper presents the design and implementation of a hybrid simulation framework, which enables the co-simulation of the EMT model of Atlanta-Orlando HVdc line and the transient stability (TS) model of the entire Eastern Interconnection system. This paper also introduces the implementation of two high-fidelity HVdc line models simulated at different time steps and discusses a dedicated method for sizing the buffer areas on both sides of the HVdc line. The simulation results of the two HVdc models with different sizes of buffer areas are presented and compared.

Liu, Yuan↗