Engineering PapersSearch

SEARCH · Engineering Papers

Results for “islanding operations”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Grid Forming Inverter With Increased Short-Circuit Contribution to Address Inverter-Based Microgrid Protection Challenges

Substantial differences in fault levels between grid-tied and islanded modes is one of the primary challenges of microgrid protection. During grid-tied mode, the bulk grid provides significant short-circuit, while during islanded operation the short-circuit magnitude is small due to inverter-based resources limiting their current output close to nominal ratings. Consequently, conventional distribution protection strategies based on overcurrent cannot reliably protect microgrids when operating in islanded mode. Fuses and circuit breakers are particularly affected because of their inverse characteristics. Presently, the absence of affordable solutions for protecting microgrids in islanded mode leads to microgrids shutting down during electrical faults. The contribution of this article is two-fold. The first innovation proposes specific hardware modifications to grid-forming inverters to increase their short-circuit current during electrical faults. The second innovation introduces a novel control strategy designed to preserve control stability margins even when the grid-filter saturates, ensuring sinusoidal output currents under normal and fault conditions. Through experimental results, the inverter with the proposed modifications can provide more than three-times its nominal current during electrical faults. For the prototype testbed, this was sufficient to enable the use of traditional legacy overcurrent protection, achieving the fuse-to-relay and relay-to-relay minimum coordination time for the line-to-ground, line-to-line to ground, and three-phase electrical faults.

42 ENGINEERING

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION

Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION

Laboratory Evaluation of Commercial Utility Microgrid Controller Test Results

The functional requirements of many microgrid controllers (MGCs) are expanding and evolving to meet growing utility and community needs. At a high level, the utility microgrid controller serves resilience and reliability use cases by coordinating transitions between grid-connected and islanded states and by managing the system during island operations. This includes control scenarios that require the microgrid controller to use flexible microgrid boundaries, maintain energy balance, coordinate with peer systems, and manage grid-forming (GFM) and grid-following (GFL) distributed energy resources (DER). In order to evaluate these functional enhancements, microgrid controller test plans must also be developed to ensure that the implemented controllers provide adequate performance. This report provides MGC test plans for both island operation and transition functions. The functions covered in this report include feeder level energy management, island constraint management, secondary voltage and frequency control, black start, and synchronized reconnection. This second edition update also includes results from applying the tests to a commercial utility microgrid controller. These results evaluate the performance and reliability of the controller under various operational scenarios. It identifies specific areas where the controller excels and highlights gaps that need to be addressed for future enhancements. The application of these test plans on real-world system behavior provides insights on commercial equipment readiness for field deployment. These test cases can be applied to utility-managed microgrid controllers that exclusively manage utility-owned equipment; the tests also apply to third-party managed microgrid controllers that coordinate with utility- and customer-owned equipment. The report can also be used by technology developers and project developers in industry to evaluate control strategies and performance characteristics for community microgrid controllers.

24 POWER TRANSMISSION AND DISTRIBUTION

Investigating Oscillations in Bulb Turbine Plant During Islanded black start Operation

This paper investigates the frequency oscillatory behavior displayed by the bulb turbine-based run-of-river (ROR) hydropower system under islanded operation. These oscillations prevent higher loading of these generators (under islanded conditions) and hence reduce the black start capability of these generators. To investigate the problem, first, a transfer function model of the bulb-turbine system, sensitive to the effects of head variation, blade angle, and other non-linearities pertaining to turbine characteristics is derived. Next, by analyzing this transfer function model and through simulations, it is determined that system inertia along with other parameters could be responsible for these oscillations. Also, through simulations it is shown that the same ROR system’s behavior is different under islanded mode compared to grid-connected mode.

13 HYDRO ENERGY

Modeling and Power-Hardware-in-the-Loop Validation of Synchronous Machine Governor

This paper introduces the development of a high-fidelity gas turbine governor model using a programmable logic controller for power-hardware-in-the-loop (PHIL) validation. The governor model is integrated with the National Renewable Energy Laboratory's (NREL) PHIL test bed, featuring a 2-MVA synchronous machine and a 2.5-MW variable-speed drive, to emulate NG-driven HRSGs and CTs under various operational scenarios. The primary objective of this research is to study the grid-connected and islanding operations of conventional generation sources, with representative startup sequences including turbine purge, ignition, speed ramp-up, synchronization, and breaker closure. Preliminary results of the generator governor model on NREL PHIL platform, particularly using the 2.5-MW dynamometer system, offered significant insights into the modeling techniques, hardware integration, scaling, and real-world simulation dynamics.

24 POWER TRANSMISSION AND DISTRIBUTION

A Networked Microgrid Framework and Testbed for Communication, Controls, and Optimization Testing

This paper presents the development and experimental results of a networked AC microgrid testbed located at Oak Ridge National Laboratory. The testbed comprises two, 480V three-phase, four wire microgrids designed to operate standalone, grid-tied, or as a network of microgrids. This testbed represents both the state of the industry, by incorporating grid-assets commonly found in real microgrids, and the state of the art, as it is a platform to evaluate advanced controllers. The main elements of this networked microgrid testbed are presented in this paper including a Scenario Manager, local microgrid controls, and a networked microgrid control. The Scenario Manager has the objective of emulating real-world conditions. The local microgrid controller oversees standalone, grid-tied, or islanded operation. The microgrid control is a higher-level control that coordinates interaction between islanded microgrids. This paper delves into these controllers and validates their operation in the networked microgrid testbed showcasing the operational flexibility and advance control capabilities.

Ferrari Maglia, Max

Testing and Analysis of Grid Forming Inverter Control for Achieving Resilient and Economic Operation of an Islanded Microgrid

This investigation examines the feasibility of operating a battery energy storage system (BESS) in parallel with synchronous generation by using grid forming (GFM) control in order to achieve frequency control objectives while mitigating increases to operating costs in the context of an islanded microgrid. The BESS GFM control system, which is based on conventional droop techniques, is modeled along with the overall microgrid using the Real Time Digital Simulator (RTDS) to allow for integration of genset controller hardware. A series of simulations are performed to test the voltage and frequency regulation capability of the BESS control system when the primary frequency regulating genset is tripped offline. The results of the simulations suggest that the GFM control scheme will successfully maintain frequency and voltage stability, which will enable operation without a back-up genset while not compromising the microgrid resiliency to contingencies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI

Demonstration of a Novel Technology to Manage Electricity Demand in Grid-Independent Military Microgrids

This research was conducted by the National Renewable Energy Laboratory (NREL) in collaboration with the S&C Electric Inc. through funding provided by the ESTCP. The project demonstrates use of cybersecure Automated Demand Response (ADR) technology to effectively manage microgrid loads during grid-independent, also known as "islanded," operation. When military microgrids become isolated from the main electrical grid, they are required to balance electricity supply and demand locally. Given that local generation may be constrained, the prevailing strategy involves shedding all but the most critical loads by tripping smart circuit breakers, which then necessitate manual resetting. This approach is generally implemented at the building level, which means that the buildings with mission-critical activities are exempt from load management and remain fully powered, whereas those deemed non-critical can experience a complete loss of service. In this research we developed a method that allows building automation systems to selectively control their assets in response to load shedding request from a microgrid controller, avoiding total loss of service in contrast to the conventional control approach. A commercial OpenADR client server by GridFabric is used for communication between the microgrid controller and the building management system (BMS). The microgrid controller monitors both generation capacity and various assets within the microgrid and issues a demand reduction request when necessary. This request is communicated to the OpenADR server via Modbus. Upon receiving the request, the OpenADR server forwards it to the BMS utilizing the OpenADR protocol. The BMS is pre-configured with various levels of load reduction strategies based on the controllable assets available, allowing for a nuanced approach to demand reduction. Both lab and field tests were performed that considered load shedding needed to achieve closed transition into island mode and to accommodate changing loads and power source availability while islanded. A commercial microgrid controller was used for these tests with normal programming within the expected constraints of the system capabilities. That is, the solution did not require any specialized modification to the code base of the controller. Given the latency of the round-trip communication path between the microgrid controller and the various devices involved with the load shed processes, there are certain scenarios for which the demonstrated solution are appropriate and some which are not. The methods described in this report can be used for load shedding/restoration during transitions between islanded and grid-tied modes of operation, as well as accommodating normal variations in load and the need to remove a power source from operation for maintenance. These methods should not be used for scenarios that require load shedding within a second or two such as sudden and unanticipated significant load increases or loss of power sources through equipment faults.

24 POWER TRANSMISSION AND DISTRIBUTION

Integrating a Microgrid Controller with a Local OpenADR Server

When military microgrids isolate themselves from the main electrical grid, they must locally balance electricity supply and demand. Since local generation may be limited, the current strategy is to shed all but the most critical loads by tripping smart circuit breakers, which must then be reset manually (e.g., ESTCP project EW-201350). This strategy is typically applied at the building level, meaning that entire buildings housing mission critical activities must be excluded from any load management, while those considered non-critical may lose service entirely. The remotely controlled switchgear needed to manage load in this way is very expensive ($\$30,000$-$\$50,000$ per building). While effective at shedding load, this strategy disrupts installation operation and risks damaging equipment during both disconnection and re-energization. With the goals of lowering costs, protecting equipment, and enhancing the agility of DoD microgrids, this report demonstrates the use of cybersecure automated demand response (ADR) technology to manage microgrid loads during grid-independent (a.k.a. "islanded") operation. This automated approach achieves load shedding and shifting through communication signals sent to equipment controllers rather than by cutting off the flow of electricity within the microgrid itself. Because it operates only on the base network, with no connection to external entities, this strategy avoids the main cybersecurity concern raised by past applications of ADR on military bases.

24 POWER TRANSMISSION AND DISTRIBUTION

Testbed Demonstration of a Microgrid Building Block Prototype

With the adoption of ambitious climate action goals, the penetration level of distributed energy resources (DERs) is rapidly increasing. Microgrids are an efficient way to integrate these DERs, facilitating their operation and control. Additionally, microgrids enhance the overall resilience of the distribution system by serving critical loads both within and outside their boundaries. However, the need for substantial customized engineering leads to a high cost of development, installation and maintenance of microgrids. To address this challenge, Microgrid Building Blocks (MBB) are proposed to reduce the deployment cost of microgrids through modular, standardized design and implementation. This work presents a testbed demonstrating the integrated power conversion, control, and communication functionalities of an MBB. The testbed is formed by a real-time electromagnetic transient (EMT) simulation combined with a hardware and software prototype of MBB. The use cases supported by the MBB testbed are enumerated. The islanded operation, voltage regulation, and optimal dispatch capabilities of an MBB-based microgrid controller are validated through a case study.

Somda, Baza [Virginia Tech]

Demonstrating the data center as a flexible grid asset using a C-HIL setup

Increasing data center demand is outpacing grid infrastructure development. Artificial intelligence workloads and hyperscale cloud growth are creating unprecedented demand for power, while traditional grid expansion faces multiyear development timelines. Verrus is developing an innovative datacenter solution for this challenge, data centers that act as active grid-supportive assets rather than passive loads. Our approach integrates a novel grid-aware power flow management system with battery energy storage systems(BESS) into a microgrid-controlled, medium-voltage power distribution architecture that delivers critical capabilities, such as: * Fast response to grid disturbances such over/ under voltage or over/ under frequency * Demand flexibility that can service requests from the utility within 10 s * Uninterrupted transition to islanded operation during grid outages * Continuous uptime assurance for compute loads while maintaining all customer service level agreements. Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), these capabilities were validated using NREL's Advanced Research on Integrated Energy Systems (ARIES) virtual emulation environment to model a 70-MW grid-interactive data center. This paper outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can provide both critical load resilience and ancillary grid support without compromising uptime requirements. Specifically, we present a digital real time simulation of a 70 MW data center integrated with a physical microgrid controller, and demonstrate the data center response in the event of a grid voltage and frequency event, utility demand response request and utility outage.

24 POWER TRANSMISSION AND DISTRIBUTION

Performance Evaluation of a Single-Phase Grid-Forming Inverter Through Hardware Experiments

This study conducts hardware experiments to assess the performance of a commercial single-phase grid-forming (GFM) inverter using a purely hardware-based approach. We adhere to a testing protocol for the GFM inverter and enhance it by exploring the transient performance of GFM inverters across various grid dynamic events. Quantifiable performance metrics are established for each testing scenario to gain insights into the performance of the single-phase GFM inverters. Based on the comprehensive tests, the following observations are summarized: 1) The performance of the single-phase GFM inverter is satisfactory, and it is capable of being the islanding master for residence homes when the main grid is gone. 2) For frequency response, the inverter is able to stay connected but cannot inject the needed active power to support the grid. This may be improved by the manufacturer by using droop control. 3) The GFM inverter exhibits harmful transients in voltage and frequency during islanding operation, which can be enhanced by maintaining the same operating points before and after the breaker is open.

black start

A Robust Communication-Free Protection Scheme for Islanded Microgrids with Relay Logic and Hardware-in-the-Loop Validation

This paper presents the Imbalance Square Factor (ISF) detection algorithm, an effective, computationally lightweight method for detecting faults in inverter-based microgrids. ISF provides a high magnitude at the time of the fault, which allows for fast detection and coordination between primary and backup relays. The imbalance squared factor, calculated using local voltage and currents, is used for fault detection and coordination among three relays. ISF is validated in hardware-in-the-loop (HIL) implementation inside commercial-grade relay logic (SEL-751). The HIL validation shows that ISF can coordinate primary, secondary, and tertiary relays in the 13-bus system in islanded operation.

Ferrari Maglia, Max [ORNL]

SVM-Based Synchronized Fault Detection for 100% Renewable Microgrids

Traditional protection schemes face significant challenges when applied to microgrids with high penetrations of renewables with inverter-based resources (IBRs). The proliferation of advanced sensing and communication technologies has generated copious data, offering an opportunity to overcome these limitations using data-driven machine learning approaches. This work proposes a novel approach based on a support vector machine (SVM) for detecting faults within a 100% renewable microgrid. The approach encompasses a systematic offline training stage for the development of a linear SVM-based fault detection algorithm. This process covers offline data collection from the microgrid under study, the extraction of features such as positive- and negative-sequence components and the total harmonic distortion of the voltage and current measurements of the relays, and the design of the linear SVM-based classifier. During the online implementation, however, different classifiers can exhibit asynchronicity in detecting the fault inception at different subcycle-to-cycle period-level delays. To circumvent this asynchronicity issue, a separate algorithm is developed for each relay to estimate the fault inception time as close to the real fault time. The performance of the proposed SVM-based synchronized fault detection method is evaluated using online time-domain simulation studies on a microgrid test system. The results corroborate the reliability of the fault detection scheme when tested under various fault cases (fault types, locations, and impedances) and non-fault cases during both grid-tied and islanded operation modes.

100% microgrid

Vulcan Test Platform: Demonstrating the Data Center as a Flexible Grid Asset

Explosive data center demand is outpacing grid infrastructure development. AI workloads and hyperscale cloud growth are creating unprecedented power requirements, while traditional grid expansion faces multi-year development timelines, regulatory hurdles, and decarbonization challenges. Sidewalk Infrastructure Partners recognized this impending crisis years ago and founded Verrus to develop an innovative solution: data centers that function as grid assets rather than passive loads. The Verrus approach integrates proprietary grid-aware controls with battery energy storage systems (BESS) in a medium-voltage architecture that delivers three critical capabilities: Fast-responding demand flexibility that can service requests from the utility within 10 seconds, Uninterrupted transition to islanded operation during grid disturbances, Continuous uptime assurance while maintaining all customer service level commitments Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), we validated these capabilities on Vulcan, a 70 MW utility-scale test platform powered by NREL's ARIES Virtual Emulation Environment. This deployment-ready technology has successfully demonstrated that Verrus data centers can deliver meaningful grid services while maintaining mission-critical reliability. This technical report outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can play a pivotal role in enhancing grid flexibility and reliability, without sacrificing service level guarantees.

24 POWER TRANSMISSION AND DISTRIBUTION

Small Hydro Power Plants with Integrated BESS for Enhance Resiliency

Battery energy storage systems (BESS) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various services to the grid. This paper presents the hardware demonstration and characterization of using a utility-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to perform a bottom-up power system black start that enhances power systems' resiliency. ROR hydropower plants are generally not used for power system restoration due to their frequency instability during islanded operation; however, BESS with droop control can provide critical damping to convert a ROR hydropower generator into a black start- capable unit. To demonstrate this, we carry out hardware experiments at the megawatt-scale integrating a synchronous generator driven by a dynamometer, an actual GFL/GFM BESS, a medium-voltage impedance network, and a load bank. The demonstration shows the different roles of BESS with GFL and GFM control in power system restoration. GFL BESS can suffer from high-frequency oscillations, even instability, depending on the droop control gain and loading condition. The results provide further insights for system operators on how GFL- or GFM controlled BESS can enhance grid stability and how hydro-BESS hybrids can operate as a black-start-capable unit. The presented experimental results are also a valuable resource to understand the different stability characteristics of real-world BESS with different control modes.

24 POWER TRANSMISSION AND DISTRIBUTION