Engineering PapersSearch

SEARCH · Engineering Papers

Results for “inverter-based resources (IBRs)”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

A Sensitivity-driven Wide Area Protection (SWAP) Coordination Tool for High Penetration of Inverter-based Resources (IBR)

Traditionally, power system generation sources have been composed of synchronous generators, of which the fault current behavior is understood with minimal differences between generation size and types due to the physics of their construction. Present protection schemes and modeling methods are based upon these understood characteristics. Most renewable generation is composed of inverter-based resources (IBR), in which fault current is determined by switching control software and hardware limitations, each of which can vary between manufacturers and even between models of the same manufacturer. The resulting fault current is low in magnitude, low in negative-sequence current, unpredictable phase angles, and is a challenge to model. These characteristics also result in a challenge to traditional protection schemes and fault simulation software. To address several of these concerns, the project has the following goals: 1. Improve IBR models: Improve IBR models used in short circuit (SC) programs to accurately capture the response of IBRs at the bulk power system (BPS) level for fault and protection studies. 2. Develop automation tool: Develop an automation tool that allows engineers to identify protection coordination and sensitivity issues by performing SC and protection coordination studies in a high IBR-penetrated grid by applying variations to the IBR models, faults, contingencies, etc. 3. Develop schemes: Develop new protection mitigation solution schemes that complement the existing protection systems to ensure safe operation of the BPS with higher IBR penetration levels. The project team did not achieve this final goal, as the Department of Energy (DOE) stopped the project early due to changes in DOE funding priorities. The termination notice came at the beginning of the final project phase, while the team was identifying and beginning to investigate protection issues. It should be noted that the team discussed a 100% penetration scenario. However, this scenario would require the use of grid-forming IBR models that are not presently available. Since developing these models requires additional effort, the 100% penetration scenario was not pursued during this project. In the future, developing the methodology and models for the 100% scenario could benefit the industry.

14 SOLAR ENERGY

Transient Stability Study of IEEE 2800-2022 Standard Negative-Sequence-Current Compliant GFM IBRs

The primary function of grid-forming (GFM) inverter-based resources (IBRs) is to maintain voltage and fre- quency/phase angle stability; however, during unbalanced grid faults, IEEE Std. 2800-2022 requires IBRs to inject both positive- and negative-sequence reactive current. Enforcing compliance with this standard could compromise the stability of GFM IBRs under such fault conditions. This paper presents a preliminary transient stability study focused on the power angle stability of GFM IBRs operating in compliance with IEEE Std. 2800 during unbalanced faults. The goal is to assess potential stability issues associated with the standard's current injection requirements under fault ride-through conditions. The results show that injecting positive-sequence current with d-axis priority during unbalanced faults better preserves the power angle stability than the q-axis priority while still enabling negative-sequence current injection. These findings suggest that, to ensure stability, GFM IBRs might need to partially comply with IEEE Std. 2800 by prioritizing positive-sequence current injection along the d-axis.

14 SOLAR ENERGY

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION

Large Scale Field Demonstration Evaluation Plan

This Evaluation Plan defines practical, commissioning-oriented test protocols for in-field assessment of grid-forming (GFM) inverter-based resources (IBRs) deployed under the UNIFI Consortium Field Demonstration. The demonstration’s overarching objective is to validate multi vendor GFM technologies at impactful unit/plant scale, assess interoperability and grid-service performance, and evaluate the applicability of the UNIFI Specifications for Grid-forming Inverter-based Resources in real utility environments, including integration with operational systems and protection schemes.

24 POWER TRANSMISSION AND DISTRIBUTION

Study the Protection Improvements for a Weak Grid Area With High IBRs

NLR is collaborating with Florida Power & Light (FPL) and GE to investigate power system stability and protection reliability challenges in a weak-grid region with high penetration of inverter-based resources (IBRs). This presentation will primarily focus on the protection aspects of the study. We will share key insights from this real-world project, including best practices for developing high-fidelity fault study models, establishing a controller-hardware-in-the-loop (CHIL) platform for testing physical relays, identifying system-level protection challenges, and designing enhanced protection schemes to address those issues. Through this discussion, the audience will gain practical understanding of protection studies in IBR-dominated systems, the emerging challenges associated with reduced fault current and altered transient behavior, and effective mitigation strategies. In particular, we will highlight the critical importance of IBR compliance with IEEE 2800-2022 to ensure dependable and secure protection relay operation in modern transmission systems.

24 POWER TRANSMISSION AND DISTRIBUTION

Quantifying System Strength From Grid-Forming Resources Using Frequency Scan Approach: Preprint

Current industry practices for quantifying the system strength contribution from grid-forming (GFM) resources to ensure stability of power systems dominated by inverter-based resources (IBRs) are primarily based on iterative electromagnetic transient (EMT) time-domain simulation studies. While feasible, these approaches are resource-intensive, lack scalability and intuition, and might not evaluate the system strength contribution over the entire frequency range of interest. This paper introduces a novel, frequency-domain approach to quantify system strength support provided by a GFM resource using frequency scans. The proposed method uses transfer functions from the grid voltage magnitude (V) and phase (?), respectively, to the reactive (Q) and active power (P) output of a GFM resource for quantifying its contribution to system strength. These transfer functions provide a direct measure of the ability of a GFM resource to behave as a stiff voltage source behind a reactance over a specified frequency range, enabling robust quantification of its system strength contribution. The key innovation of this work is the development of a frequency domain system strength metric called the dynamic short-circuit ratio (dSCR) that is suitable for IBR-dominated power systems and is directly related with the familiar short circuit ratio (SCR) metric. The new metric, dSCR, enables the assessment of system strength contributions from both synchronous machines and converter-based GFM resources using a unified benchmark, which is not possible with the traditional SCR metric. The paper also demonstrates how impedance scans could identify if an unstable condition observed during weak grid conditions is a result of the lack active or reactive power support or both. By leveraging the proposed frequency-domain dSCR metric for quantifying system strength contribution from GFM IBRs, the paper demonstrates targeted mitigation strategies for weak grid instabilities without resorting to repeated, time-consuming time-domain simulations. The result is a scalable and efficient approach to remediate stability challenges in power systems with high shares of IBRs and accelerating the integration of GFM technologies for system strength support in power systems.

24 POWER TRANSMISSION AND DISTRIBUTION

End-To-End Decentralized Transmission Line Protection in IBR-Dominated Weak Grids Using Interpretable Data-Driven Methods

Traditional transmission line protection relies on predictable synchronous-based fault signatures, which frequently fail under the non-standard, current-limited fault characteristics of Inverter-Based Resources (IBRs). This study investigates how to achieve secure, communication-free fault isolation in IBR-dominated weak grids without relying on opaque, computationally heavy "black-box" machine learning algorithms. To address this, we propose a novel, standalone, and inherently interpretable data-driven protection framework. Unlike centralized methods requiring multi-terminal communication, this decentralized approach relies solely on local measurements using a hierarchical linear-kernel Support Vector Machine (SVM). The methodology decomposes the protection task into four sequential stages that mimic traditional protection elements: fault detection and fault direction identification, fault type classification, zone classification, and location estimation. This multi-stage architecture allows for specialized feature engineering at each stage, combining high computational efficiency with logic traceability. The framework's end-to-end performance was validated via C-code and PSCAD/EMTDC co-simulation, utilizing a real-world utility network and an OEM black-box IBR model. The proposed relay achieves 97.2% overall accuracy and provides a reliable trip decision within a 2.5-cycle window. The results confirm 100% accuracy in fundamental fault detection, reliable zone selectivity across low to moderate fault resistances, and robust security against non-fault transients, proving its immediate viability for integration into commercial numerical relays.

24 POWER TRANSMISSION AND DISTRIBUTION

Development and Evaluation of a Cost-Effective Behind-the-Meter Synchronized Measurement Unit for Enhanced Grid Integration

This paper presents the development of the Inverter Based Resource Monitor (IBRM), an innovative behind-the-meter synchronized measurement unit (SMU) tailored for integration with inverter-based resources (IBRs). The IBRM distinguishes itself as a highly accurate and cost-effective SMU, offering facile deployment and connectivity to IBRs. It is equipped to conduct real-time voltage and current waveform analyses, serving as a phasor measurement unit (PMU) with exceptionally rapid synchrophasor transmission capabilities. The device incorporates a cutting-edge dual-core architecture designed to minimize sampling delays inherent to its microprocessor, thereby enhancing the precision of synchronized waveform measurements. Moreover, the IBRM is adept at recording high-fidelity waveform data, capturing nuances such as waveform distortions, high-order harmonics, and wide-band oscillations prevalent in power grids with substantial IBR presence. A prototype of the IBRM has been constructed and subjected to rigorous testing to assess its functional capabilities and measurement precision, utilizing both idealized signal generators and a real-world off-grid inverter setup as benchmarks.

Wu, Ori [ORNL] (ORCID:0000000326723410)

Utilities Perspective on Protection Challenges with High IBR Penetration

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This presentation identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, we are looking broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the presentation summarizes on gathered data and internal experiences.

24 POWER TRANSMISSION AND DISTRIBUTION

Utility Experience with Inverter Based Resource Impacts on Transmission Protection

High penetration of inverter-based resources (IBR) can adversely affect the transmission protection schemes in the area. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems because the existing system has been designed based on the fault current response of conventional rotating-machine-based generators. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. It includes a broad review of all challenges that system protection has experienced so far with high penetration of IBRs. Key issues have been identified based on a survey of different utility protection engineers. Finally, fault event recordings are shown to demonstrate some actual cases of mis-operations of relays near IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION

Control Parameter Sensitivity Study for Inverter-Based-Resource Dominated Grids: A Small Signal Stability Approach and Framework

The growing adoption of renewable energy is driving the prevalence of inverter-based resources (IBRs) within power grids. Future power grids will integrate both grid-following IBRs (GFM-IBRs) and grid-forming IBRs (GFL-IBRs) alongside synchronous generators. Therefore, it is crucial to perform stability studies that account for all components and especially control interactions related to IBRs. Extensive research has performed to study the IBR-related stability, however, the sensitivity study of IBRs' control parameters on system stability has not been adequately studied yet, especially from a systematic way. Therefore, this paper conducts a small signal stability analysis for a generic grid with multiple types of resources and develops an analytical framework for assessing the sensitivity of control parameters affecting stability margins. To achieve that, the non-autonomous reduced-order non-linear dynamic model is developed for a generic power system with multiple synchronous generator-based resources (SGBRs), GFM-IBRs, and GFL-IBRs. Based on the analytic model, a systematic framework for parametric sensitivity on systems' asymptotic stability is developed. A parameter sensitivity analysis based on eigenvalue methods is proposed. The impact of the droop controllers of GFM-IBRs, PQ-dispatch and the PLL controller of GFL-IBR on the system asymptotic stability is discussed. This sensitivity study is aiming to provide deep insights on control parameters' impact on system stability, and gives direction for parameter tuning in case of instability.

24 POWER TRANSMISSION AND DISTRIBUTION

BIL GRID-READY WIND: Reliable and Economical Grid Services Design, Implementation, and Demonstration at the Great Pathfinder Wind Power Plant

The GRID-READY WIND project aimed to demonstrate the ability of utility-scale wind power plants (WPPs) to deliver traditional and emerging grid services (GSs) in both grid-following (GFL) and grid-forming (GFM) modes through a centralized control framework, supplemented by local control adjustments at the wind turbine generator as needed. Throughout the project, the team offered recommendations on how the grid services demonstrated with WPPs could be applied to other inverter-based resources (IBRs), such as photovoltaic (PV) systems and battery energy storage systems (BESS), while considering the unique dynamics of these resources arising from their energy generation characteristics. The project sought to enhance the confidence of system operators (SOs) and planners in utilizing WPPs, alongside other IBRs such as PV plants and BESS, to provide essential grid services over extended periods under diverse operating conditions, thereby supporting their integration into the bulk power system.

17 WIND ENERGY

Evaluation of a Reduced-Order Model for IBR Fault Response Representation via OEM Blackbox Models

This paper presents a fully implemented inverter reduced-order-model (ROM) in an EMT simulation (PSCAD) library component for direct user utilization in protection studies. The developed inverter ROM has the following features: Equivalent to a full inverter-based resource (IBR) inverter model with positive- and negative-sequence current formulation and representation. A Python script is developed to fully automate this process, including training data generation, ROM parameter training, updating parameters, and model verification and validation. The ROM is validated using both IEEE 2800-compliant and non-compliant OEM modes in a real-world system, building confidence of its usability by protection engineers.

24 POWER TRANSMISSION AND DISTRIBUTION

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a realtime digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBRonly scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION

Summary of GFL Inverter Capability and Performance: Malawi [Slides]

This presentation provides a comprehensive comparison of inverter-based resource (IBR) technical requirements across multiple international grid codes - including IEEE 2800, ESO, EirGrid, and Malawi's evolving regulatory framework - to support capacity building for electricity-sector institutions in Malawi. It highlights key performance expectations for grid-following (GFL) inverters across critical domains such as primary and fast frequency response, ramping behavior, frequency and voltage ride-through capabilities, reactive power and voltage control, ROCOF withstand, phase jump tolerance, system strength considerations, protection schemes, and dynamic modeling requirements. Emphasizing a "Do no harm, do something, do more" philosophy, the document synthesizes best practices and operational benchmarks to guide the integration and stability of inverter-based resources within Malawi's power system. The presentation forms part of the SABESS Center of Excellence initiative supported by the Global Energy Alliance for People and the Planet.

24 POWER TRANSMISSION AND DISTRIBUTION

Grid-Forming and -Following Background, Future, and Strategies

This paper reviews current grid forming (GFM) and grid following (GFL) inverter control strategies and explores the optimized ratio between these assets in high-penetration inverter-based resource (IBR) grids. Two case studies demonstrate that an insufficient GFM ratio leads to instability, while increasing GFM participation improves fault recovery, voltage stability, and frequency regulation.

14 - SOLAR ENERGY

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources: Preprint

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION

Frequency-Nadir-Constrained Unit Commitment for Low-Inertia, High-IBR Island Power Systems [Slides]

The process of energy decarbonization in island power systems is accelerated due to the swift integration of inverter-based renewable energy resources (IBRs). The unique features of such systems, including rapid frequency changes resulting from potential generation outages or imbalances due to the unpredictability of renewable power, pose a significant challenge in maintaining the frequency nadir without external support. This paper presents a unit commitment (UC) model with data-driven frequency nadir constraints, including either frequency nadir or minimum inertia requirements, helping to limit frequency deviations after significant generator outages. The constraints are formulated using a linear regression model that takes advantage of real-world, year-long generation scheduling and dynamic simulation data. The efficacy of the proposed UC model is verified through a year-long simulation in an actual island power system using historical weather data. The alternative minimum inertia constraint, derived from actual system operation assumptions, is also evaluated. Findings demonstrate that the proposed frequency nadir constraint notably improves the system's frequency nadir under high photovoltaic (PV) penetration levels, albeit with a slight increase in generation costs, when compared to the alternative minimum inertia constraint.

14 SOLAR ENERGY