Energy management system (EMS) consists of several wide-area control applications that serve as a backbone for security, stability, and reliability of the power system. Wide-area voltage control system (WAVCS), one of the critical wide-area applications, operates in coordination with local Flexible AC Transmission System (FACTS) devices to provide voltage security and optimal management of active and reactive power resources. Since the WAVCS relies on wide-area communication and data sharing devices, possible cybersecurity vulnerabilities have to be addressed to ensure the closed-loop operation of WAVCS. In this paper, we present a methodology for performing an impact analysis of cyber-attacks in WAVCS cybersecurity. In particular, different types of data integrity attacks, such as malicious tripping, fault replay, and signal altering attacks, are considered, and detailed impact analysis is conducted in a testbed environment using the Kundur's four machine two-area system. For performing an impact analysis, the transient voltage stability of the sensitive bus voltage is studied, followed by the quantitative assessment and severity ranking using the voltage profile index. Our experimental evaluation reveals that the data integrity attacks on control signals exhibit a higher attack severity than on the measurement signals. Further, the severity of these attacks varies with nature (static or dynamic), location, and types of attacks.
We examine the merit of Bernoulli packet drops in actively detecting integrity attacks on control systems. The aim is to detect an adversary who delivers fake sensor measurements to a system operator in order to conceal their effect on the plant. Physical watermarks, or noisy additive Gaussian inputs, have been previously used to detect several classes of integrity attacks in control systems. In this paper, we consider the analysis and design of Gaussian physical watermarks in the presence of packet drops at the control input. On one hand, this enables analysis in a more general network setting. On the other hand, we observe that in certain cases, Bernoulli packet drops can improve detection performance relative to a purely Gaussian watermark. This motivates the joint design of a Bernoulli-Gaussian watermark which incorporates both an additive Gaussian input and a Bernoulli drop process. We characterize the effect of such a watermark on system performance as well as attack detectability in two separate design scenarios. Here, we consider a correlation detector for attack recognition. We then propose efficiently solvable optimization problems to intelligently select parameters of the Gaussian input and the Bernoulli drop process while addressing security and performance trade-offs. Finally, we provide numerical results which illustrate that a watermark with packet drops can indeed outperform a Gaussian watermark.
Photovoltaic (PV) systems are becoming more vulnerable to cyber threats. In response to this emerging concern, developing cyber-secure power electronics converters has received increased attention from the IEEE Power Electronics Society that recently launched a cyber-physical-security initiative. Here this letter proposes a deep sequence learning based diagnosis solution for data integrity attacks on PV systems in smart grids, including dc–dc and dc–ac converters. The multilayer long short-term memory networks are used to leverage time-series electric waveform data from current and voltage sensors in PV systems. The proposed method has been evaluated in a PV smart grid benchmark model with extensive quantitative analysis. As a comparison, we have evaluated classic data-driven methods, including K-nearest neighbor, decision tree, support vector machine, artificial neural network, and convolutional neural network. Comparison results verify performances of the proposed method for detection and diagnosis of various data integrity attacks on PV systems.
With the rapid growth of internet-connected smart devices capable of exchanging energy price information and adaptively controlling energy consumption of connected loads, the role of transactive control is expected to become more prominent in the modern grid. Transactive control systems integrate the wholesale and retail energy markets, and enable active participation of end users, thereby playing a key role in managing the rising number of distributed assets in the smart grid. The use of internet for the communication of data between the controllers at the building, distribution, and transmission levels makes the system susceptible to cyber-attacks. A skilled adversary can potentially manipulate the exchanged data with the intention of inflicting damage to the system. In this paper, four categories of metrics are put forth for evaluating the performance of the system when under data integrity attacks. A model for scaling-based data integrity attack has been described, and co-simulations have been performed on a 240 bus WECC transmission system model with detailed modeling of distribution systems at specific buses. Our results show that scaling-based data integrity attacks can have non-trivial impacts on the operational, financial, and comfort aspects of the transactive control system.
Real power injections at loads and generators, and
Not Available
Not Available
Future smart power distribution system with multiple active consumers and aggregators exchanging real-time electricity pricing and electricity consumption information over a communication network is prone to cyberattack. The goal of this paper is to understand the impact of attacks on pricing/load signals on the physical grid within a transactive energy market framework. First, this paper models the interaction between real-time electricity price and total energy demand in the form of a discrete time nonlinear autonomous dynamical system. Second, equilibrium electricity price and energy demand associated with this coupled dynamical system is derived and conditions for bounded input bounded output (BIBO) stability are identified. Third, a BIBO stable algorithm to design real-time electricity pricing scheme from a techno-economic perspective is developed. Finally, the impact of various levels of false data injection (FDI) attack on price of electricity, demand, and distribution system voltage is investigated. The proposed model is analyzed using simulations on the IEEE 69-bus test system and the impact of FDI attack on both electricity price/demand and distribution grid voltage is quantified. In conclusion, this paper shows that impact of FDI attack on electricity prices is more severe than an attack on electricity demand.
The generation level of a generator in power grid is under control of multiple control loops such as governor action, Automatic Generation Control (AGC), and manual control. These control loops are vulnerable to cyber attacks and could become potential targets for the malicious adversary. In this paper, we investigated the detection of abnormal generation controls induced by cyber attacks. One data-driven anomaly detection methodology is presented based on the behavior conformity of generation units located in the same balancing authority. A semi-supervised clustering algorithm with Hierarchical Density based Spatial Clustering of Application with Noise (HDBSCAN) is proposed for the detection model training. In our previous work, we obtained a synthetic dataset that covers scenarios including normal operation, generation control under ramp attack, switching attack, AGC integrity attacks, etc. and it is used to evaluate the proposed clustering algorithm. Experimental results show that the proposed algorithm provides better detection accuracy than K-means clustering and can distinguish not only between normal and abnormal generation controls but also among various anomaly scenarios.
Integration and operation of distributed generation (DG) and energy storage (ES) in power distribution systems are enabled by communication networks and embedded sensor and control devices that increase the vulnerability of the systems to cyber-threats, broadening the attack surface and making adversary actions more unpredictable. This paper proposes a methodology that uses ellipsoidal approximations to quantify the potential damage caused by successful attacks that affect, directly or indirectly, the desired operation setpoints and may drive the power distribution operation to unsafe states by violating the limits of voltage or line flows. More specifically, a new methodology is introduced to find the optimal non-symmetric operating constraints that can be imposed to each DG and ES in order to guarantee that the power distribution system is resilient to any malicious setpoints. The proposed method takes as inputs the system topology, DG and ES capabilities, and load limits to solve a convex optimization problem formulated using linear matrix inequalities (LMIs) and the power flow equations. The proposed solution is agnostic to the attacker's action or load profile and it does not require any assumption about the location or means of the attack. The numerical results on a test distribution feeder with several DG and ES illustrate how the proposed resilient operating constraints guarantee the security of the power distribution system under setpoint attacks.
Hydropower operators and energy storage providers are increasingly interested in participating in frequency regulation services, driven by the incentives offered by independent system operators, such as the PJM Interconnection. This transition, however, unfolds against the backdrop of a modernizing and rapidly digitizing power grid, exposing the integrated legacy infrastructure to a multitude of cybersecurity threats. This work presents an approach for developing an anomaly detection and mitigation system to address cybersecurity challenges during the participation of a hydropower-integrated battery energy storage system (BESS) in a frequency regulation market. The applied anomaly detector utilizes machine learning algorithms to provide detailed classification of cyber-physical events. Later, the applied mitigation system triggers predefined corrective actions to minimize the impact of data integrity attacks on the regulation market and system stability. We evaluated the proposed approach on a hydropower-integrated BESS topology, specifically analyzing the slow regulation signal (Reg A) coming from the PJM market. Our simulation results demonstrate that the proposed approach performs well in detecting data integrity attacks within the allocated time frame and also minimizes the system's transient instability during the participation of hydropower and BESS in the regulation market.
Not provided.
A cyber-security threat detection system and method stores physical data measurements from a cyber-physical system and extracts synchronized measurement vectors synchronized to one or more timing pulses. The system and method synthesizes data integrity attacks in response to the physical data measurements and applies alternating parametrized linear and non-linear operations in response to the synthesized data integrity attacks. The synthesis renders optimized model parameters used to detect multiple cyber-attacks.
A cyber-security threat detection system and method stores physical data measurements from a cyber-physical system and extracts synchronized measurement vectors synchronized to one or more timing pulses. The system and method synthesize data integrity attacks in response to the physical data measurements and applies alternating parameterized linear and non-linear operations in response to the synthesized data integrity attacks. The synthesis renders optimized model parameters used to detect multiple cyber-attacks.
The CPAD technology relates to anomaly detection and more specifically to cyber physical attack detection. It infers underlying physical relationships between components by analyzing the sensor measurements of a system. It then uses these measurements to detect signs of a non-physically realizable state, which is indicative of an integrity attack on the system. CPAD can be used on any highly-instrumented cyber-physical system to detect integrity attacks and identify the component or components compromised. It has applications to power transmission and distribution, nuclear and industrial plants, and complex vehicles.
Cyber-physical microgrids are vulnerable to stealthy cybersecurity threats that disguise their actions through the exploitation of system knowledge. Such actions can severely impacts microgrids deployed in defense bases, slowing the response time of military forces during national emergencies. Several machine-learning algorithms have been proposed to detect intrusions in the grid networks; however, these traditional machine-learning algorithms lack data privacy and are subject to several adversarial machine-learning threats. This paper proposes a novel federated machine learning (FML)-based three-model framework to detect and identify stealthy data-integrity attacks while ensuring data privacy in microgrid networks. The proposed architecture uses a variational mode decomposition technique to extract derived features from incoming measurement and control datasets. The extraction of these derived features allows FML models to learn minute variations in data patterns that allow them to perform significantly better than the models trained with generic datasets consisting of raw features. Our experimental results show the efficient performance of the proposed methodology against different types of data integrity attacks while considering primary and secondary controllers in microgrids. Further, the applied FML-integrated random forest ensemble algorithm outperforms the existing generic FML algorithms during noisy and noise-free datasets with prediction latencies of only 91–134 µs per sample within the 0.1 s sampling interval and requires communication bandwidth of around ∼8.25 KB/s at the control center and ∼2.7 KB/s per edge client for communication.