Engineering PapersSearch

SEARCH · Engineering Papers

Results for “grid impedance”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Grid Parameters and Voltage Estimation Approach Integrating Data-Driven Converter Model

With Measurements of grid voltage and current are essential for the optimal operation of the grid protection and control (P&C) systems. Grid parameters vary through time during the faults and especially in the converter interfaced resources (CIRs) rich power grid, and thus accurate estimation is critical to avoid the mis-operation of the P&C systems. In this paper, a moving horizon estimation (MHE) as an observer is devised and applied to estimate the grid line parameters and grid voltages for protection enhancement. Due to the proprietary and confidentiality of CIRs, the proposed approach uses the black-box model to represent their dynamics. Leveraging the easily accessible measurements of output current from the black-box model of CIR and voltage at the point of common coupling, the proposed method estimates the grid impedance and grid voltage during normal and faulty operating conditions. The performance shows that the optimization-based observer was able to closely observe the accurate states and parameters, which can be utilized by the P&C systems.

Subedi, Sunil

Existing Methods for Grid Strength Assessment and Role of Hydropower in Future Grids

The power system is undergoing rapid evolution with increasing penetration of inverter-based resources (IBRs), large loads, microgrids, and power electronic devices. Ensuring reliable and stable operation of the modern power grid is a multi-faceted challenge that requires detailed understanding of this complex system. Dynamic stability is a major concern in maintaining the security of power grids as the generation mixes and large loads transitions to include high shares of power electronic devices. The operation of IBRs in regions with low system strength and higher grid impedances has been found to be the main reason behind many of the power system instabilities that manifest themselves in various types of oscillations and interactions that, if not properly addressed and damped, can jeopardize the reliable operation of the power system. Weak grid conditions compound such stability problems, particularly when many IBRs operate in proximity to and connect to weak power grids. Therefore, it is important to assess grid strength for planning, integration and operation of IBRs for a given power system. In this report, we aim to understand and classify existing methodologies for grid strength assessment, along with their limitations and future needs. Further, we aim to utilize the huge untapped potential in utilizing hydro energy resources in addressing some of the pertinent challenges of grid strength and reliable operation of modern power systems. Hydropower, historically valued for its flexibility and dispatchability, now faces new constraints due to reduced share of synchronous machines in the generation mix and seasonal variability of available water resources. Yet, these same plants present untapped potential beyond energy generation - notably, as providers of critical grid services. This report explores how hydropower plants, particularly through operation as synchronous condensers, can play a pivotal role in strengthening the grid amid evolving system dynamics.

13 HYDRO ENERGY

A finite element propagation model for extracting normal incidence impedance in nonprogressive acoustic wave fields

A propagation model method for extracting the normal incidence impedance of an acoustic material installed as a finite length segment in a wall of a duct carrying a nonprogressive wave field is presented. The method recasts the determination of the unknown impedance as the minimization of the normalized wall pressure error function. A finite element propagation model is combined with a coarse/fine grid impedance plane search technique to extract the impedance of the material. Results are presented for three different materials for which the impedance is known. For each material, the input data required for the prediction scheme was computed from modal theory and then contaminated by random error. The finite element method reproduces the known impedance of each material almost exactly for random errors typical of those found in many measurement environments. Thus, the method developed here provides a means for determining the impedance of materials in a nonprogressirve wave environment such as that usually encountered in a commercial aircraft engine and most laboratory settings.

Watson, Willie R.

A Digital Twin for an Inverter-Based Resource Power Plant: Real-time data streaming unlocks situation awareness

Here, this study presents the development and successful implementation of a digital twin specifically designed for a grid-connected IBR power plant. By integrating a reduced-order model of the IBR system and dynamically updating the grid impedance with real-time data, the digital twin effectively captures and replicates the behavior of the physical system. Its accuracy and reliability are validated through critical test scenarios, including a three-phase fault and a line-tripping event. The results confirm that the digital twin closely emulates its physical counterpart, demonstrating its strong potential for real-time analysis, system monitoring, and predictive decision making in modern power systems.

Digital twins

A Stable and Ultrafast Control for Multiparallel Grid-Tied SiC Inverters With LVRT Capability Considering Cable Impedance

The stability of multiparalleled grid-tied inverters remains a challenging issue especially during low-voltage ride-through (LVRT) in the presence of grid impedance. SiC device-based grid-tied inverters can achieve advantages such as higher efficiency, reduced size of interface filters, and fast dynamics; however, they can exacerbate this stability issue particularly when LVRT occurs along with high inrush current due to their low inertia characteristics. In this article, a direct deadbeat control method without any PI control loop is proposed for multiparallel grid-tied SiC inverters. The proposed control achieves instantaneous current regulations within switching cycles. In addition, it mitigates high inrush currents and maintains stability during LVRT transients without requiring mode transitions between normal and LVRT operation modes, thereby achieving an ultrafast response and seamless operation through this unified control method. The Lyapunov method is applied to analyze the multiparallel inverter stability in the presence of grid impedance with proposed deadbeat control method. The inverter V-I trajectories during LVRT transients are derived to illustrate the ultrafast and stable feature of proposed control. Finally, the experimental results of two grid-tied SiC inverters operating at LVRT transients are provided to verify the advantages of the proposed control method.

14 SOLAR ENERGY

Stability Analysis of Power Systems with High Penetration of State-of-the-Art Inverter Technologies

With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.

24 POWER TRANSMISSION AND DISTRIBUTION

Adaptation of virtual synchronous generators to dynamic conditions in power grids

Virtual synchronous generators (VSGs) are widely adopted as grid-forming controls for inverter-based resources. However, when grid conditions vary significantly as characterized by changes in short-circuit ratio (SCR) and the reactance-to-resistance (X/R) ratio, fixed-gain designs and the commonly used P–Q decoupling assumption can become inaccurate. Such conditions can degrade transient power performance, leading to oscillations, prolonged settling, and overshoot, particularly in stiff-grid operating points. This paper quantifies how grid strength and impedance-dependent coupling affect the active–reactive power dynamics of a conventional VSG over a broad range of SCR and X/R values. An adaptive VSG tuning framework is then developed by combining (i) a coupling-explicit, impedance-parameterized state-space model to enable systematic controller synthesis, (ii) a full-state-feedback law designed via pole placement to meet prescribed damping and settling-time specifications, and (iii) a physics-informed neural network (PINN)–based online grid-impedance estimator that updates controller gains in real time as grid conditions vary. Offline simulations in MATLAB/Simulink and real-time validation on an OPAL-RT platform show that the proposed method preserves consistent damping and settling behavior with reduced overshoot across wide SCR and X/R ranges, compared with fixed-gain VSG baselines.

Adaptive control

Modeling Framework for Data Center

This chapter highlights the critical need for advanced modeling of data centers due to their rapidly increasing energy consumption and impact on grid reliability. Driven by the demand for AI applications, data centers are projected to consume a significant portion of US energy by 2028, putting stress on an already challenged power grid. The chapter emphasizes the importance of "fast" time-scale models to understand the dynamic interactions between data centers and the grid, especially given the rapid power fluctuations of AI workloads. It outlines a modeling framework that includes both offline and real-time EMT domain simulations, detailing the necessary representations for various components like utility interfaces, transformers, IT loads, UPS, cooling loads, Battery Energy Storage Systems (BESS), generators, protection systems, and higher-level control systems. While standard simulation tools like PSCAD offer basic models, custom development is often required to accurately capture the unique and fast-changing behaviors of modern data centers. The chapter also discusses key metrics and test cases for validating these models, focusing on transient load responses, protection relay coordination, and demand flexibility. Finally, it addresses the challenges of modeling large-scale data centers, such as computational complexity and the trade-off between model fidelity and practicality, suggesting hybrid modeling approaches as a solution. The overarching goal is to create a robust framework that helps assess data center impacts on grid stability, identify vulnerabilities, and inform the development of standards for reliable integration of these large loads into the bulk power system.

25 ENERGY STORAGE

Virtual Cable Impedance based Load Sharing in a Microgrid for Parallel Connected Grid Forming Converters

This paper presents a novel approach to power sharing between direct connected grid-forming converters, utilizing virtual cable impedance and droop-based outer loop control. To enhance stability, resistive droop is implemented, while virtual cable impedance with non-zero resistive and inductive components ensures improved power sharing. The inner loop controller employs a Lyapunov energy function to achieve superior dynamic performance. The proposed control architecture is validated through comprehensive modeling and real-time processor-in-the-loop simulations, demonstrating its robustness and efficiency under various operating conditions. The results highlight the potential of this control strategy to improve the reliability and efficiency of renewable energy systems. Additionally, a comparative analysis with traditional methods underscores the advantages of the proposed approach in terms of stability and performance. The proposed control architecture offers a scalable and flexible solution for grid-forming converters, enabling seamless integration of renewable energy sources. Its robustness and adaptability make it an attractive solution for real-world applications. Furthermore, the approach can be extended to other power electronic systems, enhancing overall system performance and efficiency. By providing a reliable and efficient control strategy, this paper contributes to the advancement of renewable energy systems and their adoption in the energy sector. The proposed control strategy has far-reaching implications for the widespread adoption of renewable energy sources, enabling a more sustainable and efficient energy future. The overall system is modeled in MATLAB/Simulink and PLECS software domain.

grid forming converters (GFM)

Identifying Potential Sub-Synchronous Oscillations Using Impedance Scan Approach: Preprint

This paper presents an impedance scan study on the real-world power system in Australia that has observed 17 to 20 Hz intermittent subsynchronous oscillations. Through the impedance scan of each of the IBRs, both individually and collectively, potential resonance modes are identified. The impedance scans were carried out using electromagnetic transient PSCAD models of the network. The network comprises of site-specific, black-boxed models of IBRs supplied by the generators. The impedance scan approach was divided in three major steps: (1) the first step is to identify IBRs where impedance analysis needs to be performed based on the magnitude of oscillations observed at their points of interconnection (POIs); (2) the second step focuses on performing impedance scans at selected IBRs in single-machine infinite-bus (SMIB) configuration to identify internal resonance modes of an IBR and to evaluate if any of these modes become unstable under certain grid conditions; (3) the third step performs impedance scans at a few selected IBRs while connected to the wider network model to obtain the impedance response of both the IBR and the grid - this step evaluates control interactions among IBRs. The impedance scan study found that a few IBRs have an underdamped resonance mode at around 17 Hz, which becomes unstable under a certain operating condition. Another interesting finding was that certain IBRs increase the effective grid impedance seen by another IBR in proximity for a particular operating condition. Under this operating condition, the resulting subsynchronous oscillation mode is more pronounced due to a combination of control interactions among IBRs through the transmission network under study and a resonance mode inside the IBRs.

control interactions

Critical Clearing Time for Droop-Controlled Grid-Forming Inverters With Circular Current Limiting and Virtual Impedance Current Limiting

The critical clearing time is a crucial parameter for assessing the large-signal stability of grid-forming (GFM) inverters. Variations in current limiters can significantly impact an inverter's transient behavior during large disturbances. Here, this letter introduces a method based on the power-angle relationship to evaluate the fault recovery of a droop-controlled GFM inverter under a three-phase bolted fault scenario, considering both the circular current limiter and the virtual impedance method. High-fidelity simulations validate the accuracy of the proposed formulas in estimating the critical clearing time of the GFM inverter.

42 ENGINEERING

Large reflector antenna study

In some applications, the wires used to construct the grids are plated over with highly conducting materials such as gold or silver. In those cases, depending on the frequency of operation, the coating may not be thick enough to prevent currents from flowing in the substrate. The conjugate gradient method, in conjunction with the fast Fourier transform is employed to solve the problem of scattering from such rectangular grids. An internal impedance is utilized to account for the effects of the substrate conductivity on the induced current densities. Calculated values of the reflection coefficient and induced currents from different coating thicknesses, angles of incidence and polarizations are presented and discussed.

Christodoulou, C. G.

Software for Managing Parametric Studies

The Information Power Grid Virtual Laboratory (ILab) is a Practical Extraction and Reporting Language (PERL) graphical-user-interface computer program that generates shell scripts to facilitate parametric studies performed on the Grid. (The Grid denotes a worldwide network of supercomputers used for scientific and engineering computations involving data sets too large to fit on desktop computers.) Heretofore, parametric studies on the Grid have been impeded by the need to create control language scripts and edit input data files painstaking tasks that are necessary for managing multiple jobs on multiple computers. ILab reflects an object-oriented approach to automation of these tasks: All data and operations are organized into packages in order to accelerate development and debugging. A container or document object in ILab, called an experiment, contains all the information (data and file paths) necessary to define a complex series of repeated, sequenced, and/or branching processes. For convenience and to enable reuse, this object is serialized to and from disk storage. At run time, the current ILab experiment is used to generate required input files and shell scripts, create directories, copy data files, and then both initiate and monitor the execution of all computational processes.

Yarrow, Maurice

Barefoot Rover: a Sensor-Infused Rover Wheel Demonstrating In-Situ Engineering and Science Extractions using Machine Learning

In this work, we demonstrate an instrumented wheel concept which utilizes a 2D pressure grid, an electrochemical impedance spectroscopy (EIS) sensor and machine learning (ML) to extract meaningful metrics from the interaction between the wheel and surface terrain. These include continuous slip/skid estimation, balance, and sharpness for engineering applications. Estimates of surface hydration, texture, terrain patterns, and regolith physical properties such as cohesion and angle of internal friction are additionally calculated for science applications. Traditional systems rely on post-processing of visual images and vehicle telemetry to estimate these metrics. Through in-situ sensing, these metrics can be calculated in near real time and made available to onboard science and engineering autonomy applications. This work aims to provide a deployable system for future planetary exploration missions to increase science and engineering capabilities through increased knowledge of the terrain.

Marchetti, Yuliya

Small-Signal Stability of Grid-Forming Converters Under Fault Conditions

Threshold virtual impedance (TVI)-based current limiting for grid-forming converters (GFMs) has gained great interest due to its ability to maintain voltage source behaviour during faults. However, sequence component extraction (SCE) and negative-sequence control (NSC) are often overlooked in small-signal stability assessments during faults. This paper develops small-signal sequence impedance models for GFMs under four well-known SCE methods based on TVI current limiting control during symmetrical fault conditions. Using the developed impedance models, the impacts of SCE and NSC, and the voltage and current control loop bandwidths, on system stability during faults are investigated. Additionally, since negative-sequence TVI (TVI-) is typically added along with its positive-sequence counterpart, which is often inductive, inductive and resistive TVI- are examined. The findings suggest that a higher voltage or current control loop bandwidth has a negative impact on system stability, while SCE and NSC largely reduce the stable range for voltage and current control loop bandwidth during faults, and that the severity of such impacts is determined by the particular SCE method. Furthermore, it is observed that inductive TVI- significantly degrades system stability, while resistive TVI- can enhance stability when suitable SCE methods are appropriately selected and designed. Matlab/Simulink electromagnetic transient simulations validate these analytical results.

24 POWER TRANSMISSION AND DISTRIBUTION

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting

A study of the variable impedance surface concept as a means for reducing noise from jet interaction with deployed lift-augmenting flaps

The feasibility of quieting the externally-blown-flap (EBF) noise sources which are due to interaction of jet exhaust flow with deployed flaps was demonstrated on a 1/15-scale 3-flap EBF model. Sound field characteristics were measured and noise reduction fundamentals were reviewed in terms of source models. Test of the 1/15-scale model showed broadband noise reductions of up to 20 dB resulting from combination of variable impedance flap treatment and mesh grids placed in the jet flow upstream of the flaps. Steady-state lift, drag, and pitching moment were measured with and without noise reduction treatment.

Hayden, R. E.