Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “forced oscillation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

A Comprehensive Method to Mitigate Forced Oscillations in Large Interconnected Power Grids

Multiple severe forced oscillation events have recently been observed across the North American interconnections and around the world. These forced oscillations have caused power swings, limited power transfer capability, damaged equipment, and persisted indefinitely until the driving source was located and removed. This paper proposes a comprehensive method to mitigate forced oscillations. Once a forced oscillation is detected, a new source location algorithm can be used to locate the source based on the oscillation mode angle without requiring system topology information. If the source cannot be quickly located and removed, a control strategy can be activated to modulate the active power of utility-scale inverterbased battery energy storage systems (BESSs) to reduce the energy of forced oscillations to a safe level and allow sufficient time for locating the exact source. The proposed source location algorithm is validated using measurements collected during the January 11, 2019 forced oscillation event in North America and other actual grid events, while the proposed control strategy is verified using the Eastern Interconnection dynamic model under the replicated January 11, 2019 forced oscillation event. The simulation results demonstrated that the proposed source location algorithm can accurately identify the forced oscillation source, and the proposed control strategy can significantly reduce forced oscillation energy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impact of the Exciter and Governor Parameters on Forced Oscillations

In recent years, the frequency of forced oscillation events due to control system malfunctions or improper parameter settings has increased. Tuning the parameters of exciters and governor models is crucial for maintaining power system stability. Traditional simulation studies typically involve small transient disturbances or step changes to find optimal parameter sets, but existing optimization algorithms often fall short in fine-tuning for forced oscillations. Identifying the sensitive parameters within these control models is essential for ensuring stability during large, sustained disturbances. This study focuses on identifying these critical exciter and governor model parameters by analyzing their influence on sustained forced oscillations. Using Kundur’s two-area system, we analyze common exciter models such as SCRX, ESST1A, and AC7B, along with governor models like GAST, HYGOV, and GGOV1, utilizing PSS®E software version 34. Sustained forced oscillations are injected at generator-1 of area-1, with individual parameter changes dynamically simulated. By considering a local oscillation frequency of 1.4 Hz and an inter-area oscillation mode of 0.25 Hz, we analyze the impact of each parameter change on the magnitude and frequency of forced oscillations as well as on active and reactive power outputs. This novel approach highlights the most influential parameters of each tested model—such as exciter, governor, and turbine gains, as well as time constant parameters—on the impact of forced oscillations. Based on our findings, the sensitive parameters of each tested model are ranked. These would provide valuable insights for industry operators to fine-tune control settings during oscillation events, ultimately enhancing system stability.

42 ENGINEERING↗

Forced Oscillation Grid Vulnerability Analysis and Mitigation Using Inverter-Based Resources: Texas Grid Case Study

Forced oscillation events have become a challenging problem with the increasing penetration of renewable and other inverter-based resources (IBRs), especially when the forced oscillation frequency coincides with the dominant natural oscillation frequency. A severe forced oscillation event can deteriorate power system dynamic stability, damage equipment, and limit power transfer capability. This paper proposes a two-dimension scanning forced oscillation grid vulnerability analysis method to identify areas/zones in the system that are critical to forced oscillation. These critical areas/zones can be further considered as effective actuator locations for the deployment of forced oscillation damping controllers. Additionally, active power modulation control through IBRs is also proposed to reduce the forced oscillation impact on the entire grid. The proposed methods are demonstrated through a case study on a synthetic Texas power system model. The simulation results demonstrate that the critical areas/zones of forced oscillation are related to the areas that highly participate in the natural oscillations and the proposed oscillation damping controller through IBRs can effectively reduce the forced oscillation impact in the entire system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Locating the Source of Forced Oscillations in Transmission Power Grids

A forced oscillation event in power grids refers to a state where malfunctioning or abnormally operating equipment causes persisting periodic disturbances in the system. While power grids are designed to damp most perturbations during standard operations, some of them can excite normal modes of the system and cause significant energy transfers across the system, creating large oscillations thousands of miles away from the source. Localization of the source of such disturbances remains an outstanding challenge due to a limited knowledge of the system parameters outside of the zone of responsibility of system operators. Here, we propose a new method for locating the source of forced oscillations that addresses this challenge by performing a simultaneous dynamic model identification using a principled maximum likelihood approach. We illustrate the validity of the algorithm on a variety of examples where forcing leads to resonance conditions in the system dynamics. Our results establish that an accurate knowledge of system parameters is not required for a successful inference of the source and frequency of a forced oscillation. We anticipate that our method will find a broader application in general dynamical systems that can be well described by their linearized dynamics over short periods of time.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forced Oscillation Source Location in Power Systems Using MVMD-assisted DEF in TF Plane

Fast and accurate forced oscillation source location (FOSL) is critical for mitigating forced oscillations in power systems. Here, to overcome the shortcomings of traditional dissipating energy flow (DEF) in decomposing the forced oscillation components from the measurement responses, a multivariate variational mode decomposition (MVMD)-assisted FOSL is proposed in this paper to locate the forced oscillation sources from measurements in time-frequency (TF) plane. The multi-channel measurement matrix of each generator is formed, then the multi-channel modes are decomposed from the formed multi-channel measurement matrix using the MVMD. Further, the intrinsic mode functions (IMFs) associated with the forced oscillation mode are distinguished from the decomposed modes according to the relative energy weights. With the distinguished IMFs, the MVMD-assisted DEF calculation method is developed to locate the forced oscillation source. Finally, the performance of the proposed method is evaluated using the simulation data of the WECC 179-bus test system and IEEE-NASPI Oscillation Source Location Contest as well as the actual PMU data of ISO New England. The results validated the effectiveness and accuracy of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Model-less Source Location for Forced Oscillation based on Synchrophasor and Moving Fast Fourier Transformation

Forced oscillations in power systems occur when the grid is driven by an external and periodic force. To quickly detect and locate the source of the forced oscillation is critical in terms of ensuring the reliability of an interconnected power grid. This paper explores the electromechanical wave propagation theory and the Fast Fourier Transformation to analyze the forced oscillations. It proposes a model-less, adaptive, fast, and accurate source location algorithm. The proposed algorithm is extensively evaluated through simulation data from a 70k-bus U.S. Eastern Interconnection test system and field-collected synchrophasor data from the distribution-level wide-area monitoring system, FNET/GridEye. The evaluation results demonstrate the correctness and effectiveness of the proposed model-less forced oscillation source location algorithm.

Wang, Weikang↗

Non-Stationary Power System Forced Oscillation Analysis using Synchrosqueezing Transform

Non-stationary forced oscillations (FOs) have been observed in power system operations. However, most detection methods assume that the frequency of FOs is stationary. In this paper, we present a methodology for the analysis of nonstationary FOs. Firstly, Fourier synchrosqueezing transform (FSST) is used to provide a concentrated time-frequency representation of the signals that allows identification and retrieval of non-stationary signal components. To continue, the Dissipating Energy Flow (DEF) method is applied to the extracted components to locate the source of forced oscillations. The methodology is tested using simulated as well as real PMU data. In conclusion, the results show that the proposed FSST-based signal decomposition provides a systematic framework for the application of DEF Method to non-stationary FOs.

42 ENGINEERING↗

Forced Oscillation Source Location of Bulk Power Systems Using Synchrosqueezing Wavelet Transform

Forced oscillation source location (FOSL) plays a significant role in mitigating forced oscillations (FOs), which threaten the power system stability. Here, this paper proposes a data-driven approach for FOSL in power systems using synchrosqueezing wavelet transform (SWT). The proposed approach conducts SWT on the measured system responses to obtain the SWT matrix. Then, the SWT-based dissipating energy flow (DEF) model in time-frequency domain and dissipating energy spectrum (DES) model in frequency domain are derived from the traditional DEF model. Further, the characteristics of SWT-based DEF and DES are revealed by referring to the traditional DEF, and the FOSL criteria of the SWT-based DEF and DES can be hereby obtained. Using the obtained FOSL criteria, the FO source can be located from the measured responses. The performance of the proposed FOSL method is evaluated by simulation data of the WECC 179-bus test system and field-measurement PMU data of the ISO New England. The results confirm the accuracy and efficiency of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluation of Mode Meters Robust to Forced Oscillations using Field-Measured Data

Mode meters are tools used by power system operators to continuously monitor a system's small-signal stability. They do so by estimating the system's electromechanical modes of oscillation. When a system undergoes a forced oscillation, mode meters may become biased because the two types of oscillation cannot be distinguished. Modified mode meter algorithms robust to this bias have been proposed in prior research, but these studies were based primarily on simulated data. In this paper, modified least squares and Yule-Walker mode meter algorithms are evaluated using field-measured data from phasor measurement units (PMUs). Results show that the sensitivities of the least squares algorithm make it impractical for use given the complexities of real-world forced oscillations. However, the modified Yule-Walker algorithm is shown to perform well and has significant potential for practical deployment in mode meter tools.

Follum, James D.↗

Interpreting Forced Oscillation Notifications from ESAMS: General Guidance for Reliability Coordinators

The Eastern Interconnection Situational Awareness Monitoring System (ESAMS) project demonstrated the feasibility of aggregating synchrophasor measurements from across an interconnection, analyzing them, and providing real-time wide-area situational awareness to system operators who may have excellent visibility within their footprint but lack an interconnection-wide view. An application within ESAMS that has garnered industry interest involves detecting forced oscillations visible across multiple areas, identifying the region where the oscillation originated from, quantifying the uncertainty in source localization results, and notifying users in real-time if the detected oscillation amplitudes cross a specified threshold. It is expected that system operators will utilize their internal SCADA/EMS/synchrophasor systems in conjunction with information provided by ESAMS to take effective mitigation actions if forced oscillation notifications are received. This report provides some general guidance on how the ESAMS information can be used for source localization and coordination among multiple reliability coordinators; and also identifies potential enhancements to ESAMS notifications for improved interpretability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Adaptive controller for forced oscillation suppression in the grid

A control system and method for an inverter-based resource device provided in a synchronous power grid. The control system includes at least one inverter based resource device connected to an electrical power system, and a controller module. The inverter based resource device includes a reference power Pref, a combination module and a transfer function. The inverter based resource device injects modulated power into the power system. The power system (which is represented by a transfer function in the control system) receives an undesirable forced oscillation, which is connected to a measuring device. A controller module processes the measured output and provides a control signal to the inverter based resource device. The controller is arranged to suppress a forced oscillation detected in the power system.

Guttromson, Ross↗

Time Series Classification for Locating Forced Oscillation Sources

Here, this article presents a machine learning based time-series classification method for using synchrophasor measurements to locate the source of forced oscillation (FO) for fast disturbance removal. First, multivariate time series (MTS) matrices are constructed by the most informative measurements selected by sequential feature selection from each power plant. Then, the Mahalanobis matrix is trained such that the Mahalanobis distance between the MTSs from the same class (i.e., with the same FO source location) are minimized and from different classes (i.e., with different FO source locations) are maximized. This allows MTSs to be classified by classifiers with class membership corresponding to the location of each FO source. To meet the runtime requirements of online matching, class templates are constructed to reduce data size and improve matching efficiency. To account for uncertainty in identifying the exact beginning of an FO event, dynamic time warping is used to align the out-of-sync MTSs. IEEE 39bus and WECC 179bus systems are used for algorithm development and validation. Simulation results demonstrate that the algorithm meets online operation runtime requirement with high accuracy using misaligned data sets.

42 ENGINEERING↗

Symmetrized Drude Oscillator Force Fields Improve Numerical Performance of Polarizable Molecular Dynamics

Drude oscillator potentials are a popular and computationally efficient class of polarizable models that represent each polarizable atom as a positively charged Drude core harmonically bound to a negatively charged Drude shell. Here we show that existing force fields that place all non-Coulomb forces on the Drude core and none on the shell inadvertently couple the dipole to non-Coulombic forces. This introduces errors where interactions with neutral particles can erroneously induce atomic polarization, leading to spurious polarizations in the absence of an electric field, exacerbating violations of equipartition in the employed Carr–Parinello scheme. A suitable symmetrization of the interaction potential that correctly splits the force between the Drude core and shell can correct this shortcoming, improving the stability and numerical performance of Drude oscillator-based simulations. The symmetrization procedure is straightforward and only requires the rescaling of a few force field parameters.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

Statistical Performance of Forced Oscillation Detectors in the Presence of Missing Measurements

In bulk power systems, measurement-based monitoring for large oscillations can help maintain system reliability. One of the challenges encountered in a recent field demonstration was the unavailability of measurements due to underlying measurement quality or communication problems. During the demonstration, the oscillation detector ignored a measurement location if even 10 seconds of data was missing. To extend the detector's ability to operate in these conditions, this paper evaluates the impact of three methods for addressing missing data. The strengths and weaknesses of each approach are evaluated using theoretical expressions for the probability of detection along with results from simulated data and publicly available field measurements. Based on these results, a suitable approach is identified that can extend the oscillation detector's performance when large segments of data are missing.

Follum, James D.↗

Forced Power Systems Oscillations Due to Cyberattacks: Threats, Detection and Partial Mitigation

Forced oscillations in power systems can be caused by misconfigured controllers at generator stations. They can also be caused by cyberattacks against the exciters or governors. This paper explores the effects of forced oscillations from cyberattacks on generator excitation and governor systems and the effectiveness of a novel control system for a static var compensator in mitigating those oscillations to enhance transmission system resilience. A brief overview of oscillations, especially forced oscillations, within power systems is presented, along with an overview of cyberattacks on power systems. This paper also examines and implements FACTS devices to partially mitigate the forced oscillations created by cyberattacks by reducing the magnitude of the oscillations caused by the attack. The proposed approach is more effective against attacks targeting exciters.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Imaging Bias‐Driven Domain Wall Motion With Scanning Oscillator Piezoresponse Force Microscopy

Understanding ferroelectric domain wall dynamics at the nanoscale across a broad range of timescales requires measuring domain wall position under different applied electric fields. The success of piezoresponse force microscopy (PFM) as a tool to apply local electric fields at different positions and imaging their changing position, together with the information obtained from associated switching spectroscopies has fueled numerous studies of the dynamics of ferroelectric domains to determine the impact of intrinsic parameters such as crystalline order, defects and pinning centers, as well as boundary conditions such as environment. However, the investigation of sub-coercive reversible domain wall vibrational modes requires the development of new tools that enable visualizing domain wall motion under varying applied fields with high temporal and spatial resolution while also accounting for spurious electrostatic effects. Here, scanning oscillator piezoresponse force microscopy extends the investigation of domain wall dynamics to new regimes, providing direct visualization of domain wall position as a function of an external electric field that varies in time and location. In conclusion, this enables studying the energetics of field-driven ferroelectric domain wall motion, which is shown to obey a thermally activated flow regime in the millisecond timescale.

Piezoresponse Force Microscopy↗