Flexible Transformers for Resilient and Adaptable Power Systems

This paper presents experience with grid ready flexible transformer unit, which is in service for two years without any difficulty. Transformer unit is capable of changing short circuit impedance on load and it is equipped with state-of-the-art monitoring system.

field validation↗

Advanced Flexible Transformers

Advanced grid solutions are comprised of advanced transmission technologies and grid enhancing technologies. In this webinar, experts will provide participants with insights into eight advanced grid solutions. The advanced transmission technologies that will be discussed include point-to-point high voltage direct current and advanced conductoring and the grid enhancing technologies that experts will explore include topology optimization, advanced power flow control, dynamic line rating, energy storage, virtual power plants, and advanced flexible transformers

flexible power transformer, power flow controller,↗

Grid-Ready Flexible Transformers for Resilient Transmission Networks

Today’s transmission networks extend for hundreds of kilometers, transferring significant amounts of electrical energy. For every country, there are sort of “back- bone” lines, where a massive failure of transformers would create serious challenges to sustain a reliable energy supply. Natural phenomena and human driven actions could be triggers of such catastrophic events. For large utilities, or groups of utilities, it would be highly convenient to count with “flexible transformers”, which could be used as replacements for different voltage levels and with impedance adjustable to match optimum local requirements of impacted substations. Currently applied “emergency transformers” are fixed-impedance devices. In this contribution, a new concept of flexible, “future-grid ready” type of power transformers, specially devised for transmission networks is explained. This transformer has adjustable impedance features, which could be on-line operated. The concept has been proven to be functional and stable in the factory lab and in the field, by means of a prototype autotransformer of of 100 MVA, 165/69 Kv.

impedance of transformers↗

Distributed Embedded Energy Converters for Ocean Wave Energy Harvesting: Enabling a Domain of Transformative Flexible Technologies

Distributed embedded energy conversion technology (DEEC-Tec) is a very promising - but underdeveloped - domain in marine renewable energy research. The technology utilizes small distributed embedded energy converters (DEECs) that, in aggregate, form a much larger energy harvesting-converting structure. Each DEEC is a small transducer - an individual mechanism that converts one form of energy into another. A transducer's specific mode of operation can be based upon any number of physical phenomena, including variable capacitance, variable magnetic fields, or piezoelectrics. It is the dynamic deformation of a structure made from such DEECs (a DEEC-Tec structure) that provides the needed physical phenomena (the external energy source) for the underlying transducers to intake and convert energy into another form, such as electricity. DEEC-Tec structures designed specifically to dynamically deform in the presence of ocean wave energy - for the purpose of harvesting and converting that energy - can be called flexWECs. A flexWEC's gross shape (topology) and its compliant characteristics (morphologies) are chiefly determined by how the DEECs making up its structure are arranged and implemented. In turn, those corresponding topologies and morphologies will largely determine how a flexWEC interacts with - and dynamically deforms within - the presence of ocean wave energy. FlexWECs appear to have many attractive features, including broad-banded ocean energy conversion, in situ energy conversion throughout an entire flexWEC structure, inherent redundancy, and appealing material and manufacturing costs. To this end, the design and development of any particular flexWEC or flexWEC feature is a revolutionary opportunity for how we conceptualize and envision the future of ocean wave energy conversion.

DEEC↗

Flexible transformer system

A system includes conductive windings extending around a magnetic core and impedance-varying windings extending around the magnetic core. The impedance-varying windings include positive windings and negative windings. The conductive windings and the impedance-varying windings conduct electric current around the magnetic core. The system includes a first impedance tap changer that is electrically coupled with the positive windings of the impedance-varying windings and a second impedance tap changer electrically coupled with the negative windings of the impedance-varying windings. A controller controls the first impedance tap changer and the second impedance tap changer to change an impedance of the system by changing which portion of the positive windings and which portion of the negative windings are conductively coupled with the conductive windings, and which portion of the positive windings and which portion of the negative windings are disconnected from the conductive windings.

Ndiaye, Ibrahima↗

FLEXIBLE POWER TRANSFORMERS TO IMPROVE RESILIENCY OF TRANSMISSION NETWORKS

For decades, transformer flexibility of operation has been limited to adjustable voltage ratio and, in some cases, several ratings with staged cooling. Transformers reconnectable to multiple voltage ratings have been primarily applied as emergency replacements. Other versions of “flexible transformers” were developed for continuous, long-term operation at specific sites, with application limited to large utilities. A new technology that supports today’s power systems adaptability requirements has been developed to provide not only voltage and power rating flexibility, but also an adjustable short-circuit impedance. This last, unique feature allows for a closer match to actual system operational requirements and could be used in the future to enhance resiliency and improve dynamic control of electrical grids. While the solution’s fundamentals have already been introduced in several technical forums, the intention of this article is to focus on the potential benefits of this new type of transformer and share the deployment experience of a full-scale prototype that has been in operation in a major U.S. utility since 2021

flexible transformer, resilient grid, variable lea↗

Transformer system

A flexible transformer system includes conductive windings extending around a magnetic core of a transformer phase and impedance-varying windings extending around the magnetic core of the transformer phase. The conductive windings and the impedance-varying windings are configured to conduct electric current around the magnetic core of the transformer phase. The system includes an impedance switch coupled with the impedance-varying windings and with the conductive windings. The impedance switch is configured to change an impedance of the system by changing which impedance-varying winding of the impedance-varying windings is conductively coupled with the conductive windings and which impedance-varying winding of the impedance-varying windings is disconnected from the conductive windings.

Premerlani, William James↗

Design, Deployment, and Characterization of the World’s First Flexible Large Power Transformer

GE Research and its partner Prolec GE have designed, built and deployed in the field the world’s first flexible power transformer. The flexible power transformer is a transmission class 3-phase autotransformer configurable in impedance and in voltage which allows it to serve as a universal spare for multiple units in a given fleet. However, the key innovation in this new concept is the online adjustable leakage impedance which allows the transformer to change its impedance without interrupting the transmission line operation. The flexible power transformer can be designed with up to three low voltage transmission class ratings and up to 12 impedance values changeable both online and offline. This report provides an overview of the design, manufacturing, testing, and commissioning of the 165kV, 60MVA prototype built including the results of the field performance validation tests. The prototype was specified in collaboration with Cooperative Energy, the utility host. It was designed and tested in the factory according to IEEE standard C57.12.00 and followed all protocols for transportation, installation, and commissioning of a power transformer. In addition to the prototype, a flexible protection system capable of automatically adjusting its settings upon the transformer impedance was also developed and deployed in the for testing and validation. On September 3, 2021 the prototype was energized in Cooperative Energy’s substation in Columbia, Mississippi to become the world’s first flexible power transformer in operation. Its performances and impact on the grid operation were demonstrated through different field tests. Results obtained confirm that the impedance of the flexible transformer can be varied under load through its full range, from 4.3% to 9.3%, without adverse impacts on the line operation, the protection system, the transformer stability and health condition. Results also proved that the flexible transformer is very effective in controlling power transfer through the line or load sharing between units operating in parallel. Indeed, it was proven that higher impedances decrease the thruput power of the transformer while lower impedances increase it. Up to 26MW was controllable on a line loading of 45MVA. It was also possible to demonstrate that the variation of the transformer impedance has no effect on the circulating current between units in parallel, except a minor transient during the impedance change. It was also proven that the flexible protection relay can update its protection settings automatically when the impedance change was detected. The prototype has operated continuously for more than 12 months now with a peak load exceeding 50MVA corresponding to >80% of its ONAN power rating. No alarm, trip or sign of failure has been reported by the utility. In addition to the development and deployment of the flexible transformer prototype, investigations were carried out on new nanodielectric fluids to replace the mineral oil used in power transformers with the goal of reducing their footprint and weight. The key parameters that were targeted for improvement included the breakdown voltage to reduce clearances between windings and tank hence the footprint; viscosity and thermal conductivity to increase the cooling efficiency and therefore to reduce the winding material. Several nanodielectric mixtures with mineral oil including with alumina (Al2O3), titania (TiO2) and Borum Nitrate (BN) with different surfactants have been analyzed and tested. Unfortunately, despite encouraging results no nanofluid candidate has been found viable to replace mineral oil. With the formulations tested, breakdown voltages are generally similar to mineral oil at lower particle contents and worse at higher particle contents. Viscosity appreciably increased at particles concertation over 2 wt% and thermal conductivity increased slightly at 5wt% and appears to be 10-15% higher at 10 wt% particle content. It is recommended to continue investigations to find solutions that can help increase the power density of future flexible power transformers. Flexible power transformers can significantly help the future power grid by providing more flexibility and resiliency. Indeed, by providing voltage and impedance flexibility, flexible power transformers reduce the need for multiple spares, hence inventory costs for utilities. With their online controllable impedance, they can provide support to the grid and help manage short-circuit currents, power flow, line congestion, and grid stability which will become more important with higher penetrations of intermittent renewable resources. During the field validation tests, it was demonstrated that up to 26MW was controllable on a line loading of 45MVA when the transformer impedance was varied from its minimum to its maximum range. Also, with the impedance range, the short-circuit currents could be reduced by up to 38% at the load side of the transformer. With its controllable impedance, flexible transformers can be used in future strategies of grid resilience to help better prepare the grid to face forecasted severe events including storms, heat waves and contingencies. The flexible power transformers can also find role in other applications including high voltage transmission cables such as offshore wind farms where solutions for energizing the cables and managing the reactive power are of critical importance. The designed flexible power transformer is now fully validated and ready for commercialization. Further analysis on the benefits of flexible power transformers for grid stability and short-circuit management including current limiting capability, reclosure and line restoration, control of inrush current, sizing of flexible AC components (FACTS) would help its rapid adoption by the industry.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design, Deployment, and Characterization of the World’s First Flexible Large Power Transformer

As we know, power transformers are the most critical asset of the transmission network. Although highly reliable, they still can fail prematurely or ultimately retire at the end of their service life. In today’s design practices, transformers are tailored to their specific application and therefore cannot replace each other unless identical. Additionally, they provide minimal support to the grid operation and therefore limit the grid flexibility and resiliency when facing severe conditions. In this presentation, we will introduce the concept of flexible power transformer and demonstrate how one single unit can serve as a spare to multiple units in a given fleet, allow to control the power flow between transformers or lines operating in parallel and ultimately be used to limit subsequent faults in transmission lines. We will also introduce the world’s first prototype in operation, a 60MVA, 165kV flexible autotransformer.

flexible power transformer, autotransformer, varia↗

A Multiport DC Transformer to Enable Flexible Scalable DC as a Service

The rapid adoption of new DC loads and sources, including photovoltaic arrays, DC fast charging of electric vehicle, battery energy storage and data centers, requires a large amount of DC power conversion. A majority of new deployments also necessitate the integration of multiple DC loads and sources at one site. The traditional approach to serve these new applications relies on multiple standard power converters, each dedicated to a source or load, and results in highly customized systems, with challenging control coordination, complex protection strategies, and poor scalability. Instead, this paper proposes the concept of a multiport DC transformer (MDCT) as a modular building block for realizing a flexible, scalable DC as a Service system and address this rapidly growing need. The MDCT uses the S4T to achieve very tight control of cycle-by-cycle energy exchange between multiple ports, with high efficiency. A single multiport converter replaces 4-6 distinct converters, integrates all energy flows and manages protection. As a result, a new layered control architecture is introduced to ensure stability and scalability of the MDCT, with multiple S4T power converter building blocks connected in parallel to realize a fully modular system and reach the target power levels.

30 DIRECT ENERGY CONVERSION↗

Modular Hybrid Solid State Transformer (H-SST) for Next Generation Flexible and Adaptable Large Power Transformer (LPT) (Final Technical Report)

A 500 kVA HSST, the world first of such system, has been successfully developed. The HSST has the capability to regulate the power flow of the transmission or distribution power lines, or provide voltage regulation. The HSST design is modular therefore it has the ability to be connected in series of parallel to form a large power transformer with smart controllability. The project has enabled a high TRL level prototype be demonstrated at University of Texas at Austin which can lead to additional commercialization and demonstration opportunities. A large number of students were trained under this program that will benefit the power grid industry. A number of publications are published at well known international conferences and journals, further accomplish the mission of knowledge development and dissemination.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Defining a Platform Approach and Market Participation: Data Driven Business Models for Solid State Transformer-Based Synthetic Inertia and Voltage Stability Controls (CRADA Final Report, Project 1, Mod 1)

The primary objective of this project is to determine the incremental value created with the medium voltage solid-state transformer (MV SST) technology to different stakeholders in view of the updated DER grid regulations. This includes studying the benefits of the MV SST technology in a range of use cases for EV and DER penetration including (1) “corridor charging” for EVs and (2) solar plus storage (FERC 2222). The potential customers of this technology include utilities for EV charging, DER installers who must meet utility interconnection requirements, balancing authorities, and DER aggregators. The traditional transformers on the grid could be a limiting factor for the EV-grid integration as the distribution transformers were not designed to handle the dynamic and fluctuating EV charging loads. Thus, the issues such as voltage fluctuations, increased losses and reduced efficiency [1] can negatively impact the grid operation. To address these challenges, transformers with flexibility and adaptability become imperative to meet the evolving energy demands. In this regard, the concept of Medium Voltage Solid-State Transformers.

14 SOLAR ENERGY↗

An Efficient Power Flexibility Aggregation Framework via Coordinate Transformation and Chebyshev Centering Optimization

The large-scale integration of distributed energy resources (DERs) converts the role of a distribution system from a customer to a prosumer. In this context, the controllable DERs are expected to provide capacity support for the transmission system, which can be considered as power flexibility aggregation. Specifically, it is a process of controlling the power output of DERs to fulfill the desired capacity or flexibility. However, the power output of DERs as control variables is redundant. That is, a power flexibility command can be realized by multiple dispatch alternatives, which may hinder efficient design of control rules and flexibility evaluation schemes. Therefore, this paper introduces a conception of the artificial power flexibility controller to avoid the redundancy issue, which is a converted control variable after reconstructing the DER power region. Through this reconstruction, the DERs can be indirectly controlled by the proposed artificial power flexibility controller. In addition, a Chebyshev centering optimization model is developed to approximate the power flexibility region. At last, the proposed method is verified on an artificially-designed network with multiple DERs.

Chebyshev centering optimization↗

Cross-cutting concepts to transform agricultural research

Agriculture is an important link to many issues that challenge society today, including adaptation to and mitigation of climate change, food security, and communicable and non-communicable diseases in animals and humans. Transformation of agriculture and food systems has become a priority for a range of federal agencies and global organizations. It is imperative that food and agricultural researchers effectively harness the global convergence of priorities to overcome research “silos” through deep and sustained systemic change. Herein, we identify intersections in federal and global initiatives encompassing climate adaptation and mitigation; human health and nutrition; animal health and welfare; food safety and security; and equity and inclusion. Many agencies and organizations share these priorities, but efforts to address them remain uncoordinated and opportunities for collaboration untapped. Based on the interconnectedness of the identified priority areas, we present a research framework to catalyze agricultural transformation, beginning with the research enterprise. We propose that transformation in agricultural research should incorporate (1) innovation, (2) integration, (3) implementation, and (4) evaluation. This framework provides approaches for food and agricultural research to contribute to sustainable, flexible, and coordinated transformation in the agricultural sector.

60 APPLIED LIFE SCIENCES↗

SiC Based Modular Transformer-less MW-Scale Power Conditioning System and Control for Flexible CHP System

This project aims at developing a SiC-based, modular, transformer-less (60-Hz-transformers-free), MW-scale, four-wire DC/AC power conditioning system (PCS) converter, and a corresponding control system for flexible-CHP (F-CHP) systems. With the help of an F-CHP controller and power electronics converters, different CHP sources, renewable sources, and batteries can be assembled to the DC grid, which is then connected to the medium voltage (MV) AC grid through the PCS converter. To meet grid support and performance requirements, the F-CHP controller design and PCS converter design follow IEEE 1547 and IEEE 2030.7 standards. Five main tasks, including PCS converter design, F-CHP controller development, PCS converter prototype building and testing, F-CHP controller testing, and PCS paralleling, have been carried out. In this project, the F-CHP controller testing has been completed in simulation, HIL and HTB, and the PCS converter prototypes have been successfully built and tested.

24 POWER TRANSMISSION AND DISTRIBUTION↗