Engineering PapersSearch

SEARCH · Engineering Papers

Results for “digital real time simulation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Use of Digital Real-Time Simulation and Optimization to Identify Maximum Real Power Injection on the Banshee Distribution Network: Preprint

This study investigates the hosting capacity of the Banshee Distribution Network by optimizing the real power injection at carefully selected Distributed Energy Resource (DER) locations. The analysis is conducted within the framework of power system operational constraints, including bus voltage ranges, thermal line ratings, and transformer loading limits. A Python-based Genetic Algorithm (GA), implemented using the PyGAD library, is employed to iteratively identify the optimal power injection configuration that maximizes network utilization while preserving system reliability. The methodology integrates a real-time simulation environment using the Real-Time Digital Simulator (RTDS), allowing high-fidelity evaluation of power flow and voltage behavior under each proposed injection scenario. By coupling the optimization algorithm with real-time simulation feedback, this approach ensures that both static and dynamic constraints are enforced during the evaluation process. The GA leverages evolutionary operators such as selection, crossover, and mutation to navigate the nonlinear search space efficiently. The results of the study delineate the feasible hosting capacity at three targeted buses, reflecting maximum real power levels that can be injected without causing voltage violations, transformer overloading, or line congestion. These findings provide a decision- support tool for distribution planners and utilities aiming to integrate higher penetrations of DERs in existing infrastructure. Additionally, the work lays the foundation for extending such optimization techniques to multi-objective formulations, including economic dispatch and reactive power coordination, in future studies.

24 POWER TRANSMISSION AND DISTRIBUTION

Use of Digital Real-Time Simulation and Optimization to Identify Maximum Real Power Injection on Banshee Distribution Network

This study investigates the hosting capacity of the Banshee Distribution Network by optimizing the real power injection at carefully selected Distributed Energy Resource (DER) locations. The analysis is conducted within the framework of power system operational constraints, including bus voltage ranges, thermal line ratings, and transformer loading limits. A Python-based Genetic Algorithm (GA), implemented using the PyGAD library, is employed to iteratively identify the optimal power injection configuration that maximizes network utilization while preserving system reliability. The methodology integrates a real-time simulation environment using the Real-Time Digital Simulator (RTDS), allowing high-fidelity evaluation of power flow and voltage behavior under each proposed injection scenario. By coupling the optimization algorithm with real-time simulation feedback, this approach ensures that both static and dynamic constraints are enforced during the evaluation process. The GA leverages evolutionary operators such as selection, crossover, and mutation to navigate the nonlinear search space efficiently. The results of the study delineate the feasible hosting capacity at three targeted buses, reflecting maximum real power levels that can be injected without causing voltage violations, transformer overloading, or line congestion. These findings provide a decision- support tool for distribution planners and utilities aiming to integrate higher penetrations of DERs in existing infrastructure. Additionally, the work lays the foundation for extending such optimization techniques to multi-objective formulations, including economic dispatch and reactive power coordination, in future studies.

24 POWER TRANSMISSION AND DISTRIBUTION

Hardware-in-the-Loop Using Electromagnetic Transient Simulation

Digital real time simulators have the capability to run electromagnetic transient simulations in real time. This capability allows users to leverage the hardware-software combination to evaluate controller performance, protection device performance, and power device performance. This has helped many field deployment projects to be successful and be cost-effective. In this talk, we will present current state-of-art, and future of real time electromagnetic transient simulation and its impacts on field deployment.

08 HYDROGEN

Digital Real-Time Simulation and Power Quality Analysis of a Hydrogen-Generating Nuclear-Renewable Integrated Energy System

This paper investigates the challenges and solutions associated with integrating a hydrogen-generating nuclear-renewable integrated energy system (NR-IES) under a transactive energy framework. The proposed system directs excess nuclear power to hydrogen production during periods of low grid demand while utilizing renewables to maintain grid stability. Using digital real-time simulation (DRTS) in the Typhoon HIL 404 model, the dynamic interactions between nuclear power plants, electrolyzers, and power grids are analyzed to mitigate issues such as harmonic distortion, power quality degradation, and low power factor caused by large non-linear loads. A three-phase power conversion system is modeled using the Typhoon HIL 404 model and includes a generator, a variable load, an electrolyzer, and power filters. Active harmonic filters (AHFs) and hybrid active power filters (HAPFs) are implemented to address harmonic mitigation and reactive power compensation. The results reveal that the HAPF topology effectively balances cost efficiency and performance and significantly reduces active filter current requirements compared to AHF-only systems. During maximum electrolyzer operation at 4 MW, the grid frequency dropped below 59.3 Hz without filtering; however, the implementation of power filters successfully restored the frequency to 59.9 Hz, demonstrating its effectiveness in maintaining grid stability. Future work will focus on integrating a deep reinforcement learning (DRL) framework with real-time simulation and optimizing real-time power dispatch, thus enabling a scalable, efficient NR-IES for sustainable energy markets.

22 GENERAL STUDIES OF NUCLEAR REACTORS

Experimentation in Exploring Photovoltaic Inverter Dynamics Under Different Irradiance Levels Through a Data-Driven Approach

As conventional direct connections of synchronous generators are being phased out, inverter-based resources (IBRs) with grid support functions are increasingly being integrated into power systems. This transition requires the development of accurate dynamic models for IBRs to predict how power systems will adapt to varying levels of IBRs penetration, establish grid code requirements, and ensure compliance. Here, this study introduces an active probing signal-based data-driven modeling technique to accurately derive the dynamics model of a smart photovoltaic inverter operating in Volt-Watt and Freq-Watt modes, in compliance with the IEEE 1547–2018 standard. The paper focuses on investigating how the dynamics of the PV inverter model respond to fluctuations in solar irradiance, utilizing real-time digital simulator experimentation. The experimental analysis demonstrates that the amplitude of dynamics fluctuates with changes in irradiance across both operational modes and confirms the active power’s dependence on irradiance levels. Furthermore, the nature of inverter dynamics varies distinctly between the different modes of activation. Critically, our findings indicate that dynamic models require DC-gain adjustments to accommodate contrasting irradiance levels, highlighting a negative gradient linear relationship between the DC-gain of each model and the irradiance.

14 SOLAR ENERGY

High-Fidelity Modeling of a Type-5 Wind Turbine Gearbox (Intern Poster) [Poster]

Type-5 wind turbines are unique in their use of a permanent magnet synchronous generator, as well as their use of a hydraulic torque converter. This architecture presents an opportunity to provide steady and grid-ready energy without the need for a power converter. With infrastructure continuity and reliability being an important topic amongst renewable energies, researchers have been prompted to further investigate the benefits of type-5 turbines’ unique electromechanical configuration on stable electricity generation. Researchers involved in the WindSG project, SG standing for synchronous generator, are aiming to model a type-5 turbine using Real Time Digital Simulation (RTDS) to evaluate its efficacy in the grid. RSCAD, the software run on the RTDS, comes pre-loaded with electrical and electromechanical components to help simulate electrical generation and grid conditions. However, within this repertoire there is a lack of a component to represent a gearbox with high-fidelity. Within RSCAD’s case studies, the gearbox is often represented simply by a gear ratio value. This presented the task of developing a high-fidelity gearbox model in RSCAD for use in the larger RTDS type-5 wind turbine model. This poster describes a method of developing a lumped parameter mathematical model to represent a planetary-parallel-parallel gearbox in RSCAD for use in RTDS.

17 WIND ENERGY

Enabling Grid-Forming Control with Fault Ride-Through in Unbalanced Distribution Networks

Distribution networks are often unbalanced, causing oscillatory responses in inverter control designed for balanced conditions. Here, to address this problem, this paper proposes a novel time-domain transformation appropriate for inverter control and enables the decomposition of three-phase unbalanced signals into constant positive and negative components. Relations useful for calculating unbalanced active and reactive power are derived from first principle, providing insight into vector products of unbalanced three-phase signals. Furthermore, a grid-forming control effective under unbalanced conditions is developed, which delivers superior performance while meeting UNIFI1 specifications for grid-forming control under unbalanced conditions. specifications applicable to category 4 inverter-based resource, like setting and regulating frequency/voltage, providing voltage support, sharing active power, injecting negative sequence current, and riding through faults. A current limiter is proposed for safe fault ride-through and integrates with the grid-forming control featuring frequency/voltage droop controllers and current and voltage control loops. The transformation of interconnected inverters is formulated and stability of the proposed control analyzed to support robust parameter selections. The effectiveness of the proposed transformation and grid-forming control is demonstrated through analytical results and real-time simulation of a IEEE 123 distribution network on the Real-Time Digital Simulator. Comparison with existing methods shows that the proposed strategy satisfies the UNIFI specifications with a much better performance.

24 - POWER TRANSMISSION AND DISTRIBUTION

Study of the Protection Improvements for a Weak Grid Area With High Inverter-Based Resources (IBRs)

This project designs enhanced protection scheme for the real-world weak grid area with a high penetration of IBRs. As the existing protection schemes are originally designed for traditional synchronous machines, we first evaluate if the protection scheme will continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with IBR original equipment manufacturer black-box models is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. Enhanced protection is designed to address the challenge of lack of negative sequence current from IBRs, including increased restraining factors a2 and k2 to block 32Q or using V instead QV ORDER for ground faults, enhanced mho distance element with voltage and phase angle supervision for L-L faults. The efficacy of enhanced protection logic is validated and proven to work reliably. Additionally, IEEE Std. 2800-2022 negative sequence current compliant GFL and GFM IBRs from another vendor are tested and proven to work reliably without need for enhanced logic. Therefore, this work provides valuable decision-making for utilities facing protection system challenges due to IBRs, either designing enhanced protection scheme or requesting their IBRs being IEEE Std. 2800-2022 compliant to produce regulated negative sequence current for protection relay to make correct decision.

24 POWER TRANSMISSION AND DISTRIBUTION

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources: Preprint

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION

Real-Time Testbed for Studying Cyberattacks and Defense in DER-integrated Smart Inverter Systems

In this paper, we propose a Hardware-in-the-Loop (HIL) simulation testbed suitable for the implementation and testing of realistic cyberattacks on grid-tied smart inverter systems integrated with Distributed Energy Resources (DER) that use the Distributed Network Protocol-3 (DNP3) protocol for communications between grid components. Specifically, our testbed combines a Real-Time Digital Simulator (RTDS) NovaCor device, outfitted with GNETx2 network interface cards, a gridtied DER topology implemented via the RTDS software package RSCAD, and a custom virtual network that emulates a man in the middle attacker. The Man-in-the-Middle (MITM) attacker captures DNP3 traffic and falsifies telemetry data in DNP3 packets to trigger unwarranted commands from a DNP3 controller that exploit smart inverter grid support functions. We choose DNP3 and implement grid support functions according to the IEEE Std. 1547-2018 mandated for the interconnection and interoperability of DER power systems with associated power components. Furthermore, we develop a protocol payload agnostic attack detection framework that leverages the round-trip time (RTT) anomalies between DNP3 requests and responses and can detect the presence of attacks without having to analyze the payload’s contents, while balancing trade-offs between false alarm counts, missed detections, and time to detection. To facilitate further research, we publicly release benign and attack network traffic exchanged between various sensors, controllers, and actuators in our grid-tied inverter testbed.

24 POWER TRANSMISSION AND DISTRIBUTION

Real-Time Testbed for Smart Grid Recloser Controller

The growing need for a low voltage recloser has become apparent due to the rise in requirements for a smart grid. This includes more detailed management of power flow forward (towards load) and backward (towards generation), source synchronization in real time, more indepth fault responses, and the use of green energy. The SEL-651R-2 relay is a device that can manage these needs, especially in fault response and synchronization, and is commonly used in systems called microgrids. Microgrids are distribution level systems that are able to operate separated from the main grid, are typically installed much closer to the load(s), and are fed by distributed energy resources (DERs), such as wind, solar or diesel generators. The SEL-651R-2 is normally used in the field with presets operative settings, but the Western Michigan University (WMU) Center for Interdisciplinary Research on Secure, Efficient and Sustainable Energy Technology (WMU InterEnergy Center) wished to test this device in its range of capabilities for microgrid application. A Hardware-In-the-Loop (HIL) testbed was implemented and used through the Real Time Digital Simulator (RTDS) using the RSCAD software to test the SEL-651R-2's use cases and functions. The testbed includes a microgrid with interconnection to a larger main grid, and the relay is meant to control the recloser at the point of common coupling (PCC) between the main grid and microgrid. The testbed shows how basic protections, reclosing, and synchronization checks function when handling faults that affect both the microgrid and the main grid.

24 POWER TRANSMISSION AND DISTRIBUTION

Demonstrating the data center as a flexible grid asset using a C-HIL setup

Increasing data center demand is outpacing grid infrastructure development. Artificial intelligence workloads and hyperscale cloud growth are creating unprecedented demand for power, while traditional grid expansion faces multiyear development timelines. Verrus is developing an innovative datacenter solution for this challenge, data centers that act as active grid-supportive assets rather than passive loads. Our approach integrates a novel grid-aware power flow management system with battery energy storage systems(BESS) into a microgrid-controlled, medium-voltage power distribution architecture that delivers critical capabilities, such as: * Fast response to grid disturbances such over/ under voltage or over/ under frequency * Demand flexibility that can service requests from the utility within 10 s * Uninterrupted transition to islanded operation during grid outages * Continuous uptime assurance for compute loads while maintaining all customer service level agreements. Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), these capabilities were validated using NREL's Advanced Research on Integrated Energy Systems (ARIES) virtual emulation environment to model a 70-MW grid-interactive data center. This paper outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can provide both critical load resilience and ancillary grid support without compromising uptime requirements. Specifically, we present a digital real time simulation of a 70 MW data center integrated with a physical microgrid controller, and demonstrate the data center response in the event of a grid voltage and frequency event, utility demand response request and utility outage.

24 POWER TRANSMISSION AND DISTRIBUTION

Scalability analysis of heavy-duty gas turbines using data-driven machine learning

With the increasing integration of variable renewable energy sources into power systems, the role of flexible power generation technologies like gas turbines (GT) in rapid grid balancing remains crucial. This sustained importance underscores the need for scaled and precise modeling of GT to ensure effective integration within evolving energy frameworks. While physics-driven GT models integrate thermodynamics, fluid dynamics, and combustion principles, they often rely on approximate mathematical representations to accommodate scaling that may not capture the actual complex dynamics for GTs and inertial effects associated to GTs with different ratings. In this study, a data-driven model is proposed using machine learning (ML) techniques to conduct GT scalability analysis and performance evaluation with high accuracy. The ML model, trained on data from various operating conditions and performance parameters, aims to uncover intricate relationships and patterns, resembling GT characteristics at different scales (ratings). The model is developed to capture complex system interaction and to adapt to changing operational scenarios at different capacities, providing valuable insights of power system dynamics. In this study, the real-time digital simulator platform was employed to generate training data for the ML model and assess its dynamic characteristics. The ultimate objective was to develop a detailed modeling framework based on governing equations and data-driven ML capable of predicting key performance indicators, in thermal systems such as GTs, including power output, speed, fuel consumption, and exhaust temperature under diverse operating conditions at different scales. The developed ML framework demonstrated high accuracy, with mean relative errors for GT power prediction, reference speed, exhaust temperature, and compressor pressure ratio (CPR) parameters consistently below 0.1% across typical load fluctuation scenarios. Maximum deviations were limited to approximately 0.5 K for exhaust temperature and 0.009 for CPR, underscoring the model’s ability to replicating dynamic GT behavior with high precision. The adaptability of the ML model enables its application across diverse operational conditions and its extension to other thermal systems. By leveraging advanced ML techniques, this study presents a robust and scalable modeling framework that enhances GT simulation precision, facilitating improved integration into evolving power systems.

24 POWER TRANSMISSION AND DISTRIBUTION

Testing and Analysis of Grid Forming Inverter Control for Achieving Resilient and Economic Operation of an Islanded Microgrid

This investigation examines the feasibility of operating a battery energy storage system (BESS) in parallel with synchronous generation by using grid forming (GFM) control in order to achieve frequency control objectives while mitigating increases to operating costs in the context of an islanded microgrid. The BESS GFM control system, which is based on conventional droop techniques, is modeled along with the overall microgrid using the Real Time Digital Simulator (RTDS) to allow for integration of genset controller hardware. A series of simulations are performed to test the voltage and frequency regulation capability of the BESS control system when the primary frequency regulating genset is tripped offline. The results of the simulations suggest that the GFM control scheme will successfully maintain frequency and voltage stability, which will enable operation without a back-up genset while not compromising the microgrid resiliency to contingencies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI

High-Fidelity Modeling of a Type-5 Wind Turbine Gearbox (Intern Technical Presentation) (Poster)

Type-5 wind turbines are unique in their use of a permanent magnet synchronous generator, as well as their use of a hydraulic torque converter. This architecture presents an opportunity to provide steady and grid-ready energy without the need for a power converter. With infrastructure continuity and reliability being an important topic amongst renewable energies, researchers have been prompted to further investigate the benefits of type-5 turbines’ unique electromechanical configuration on stable electricity generation. Researchers involved in the WindSG project, SG standing for synchronous generator, are aiming to model a type-5 turbine using Real Time Digital Simulation (RTDS) to evaluate its efficacy in the grid. RSCAD, the software run on the RTDS, comes pre-loaded with electrical and electromechanical components to help simulate electrical generation and grid conditions. However, within this repertoire there is a lack of a component to represent a gearbox with high-fidelity. Within RSCAD’s case studies, the gearbox is often represented simply by a gear ratio value. This presented the task of developing a high-fidelity gearbox model in RSCAD for use in the larger RTDS type-5 wind turbine model. This presentation describes a method of developing a lumped parameter mathematical model to represent a planetary-parallel-parallel gearbox in RSCAD for use in RTDS.

17 WIND ENERGY

Experiments and Project-Based Enhancements for STEM Learning: Preprint

Motivating k-12 students to pick a career in science, technology, engineering, and mathematics (STEM) is an effort that requires consistent attention. At different points in time, STEM educators need to pivot themselves and update educational materials to consistently motivate the next generation of k-12 students to enter into STEM careers. Once they enter undergraduate education, universities need to motivate their undergraduates students to consider graduate studies to ensure qualified human resources can be developed for research, and teaching. We present in this paper, our work on developing STEM materials for k-12 students targeting grid integration of hydrogen assets. This paper also presents our work on leveraging open source distribution system model, digital real time simulation tool to create projects for undergraduate students and motivate their interest in research topics, and enter into graduate level education.

electro-magnetic transients

High-Fidelity Modeling of a Type-5 Wind Turbine Gearbox

Type-5 wind turbines are characterized by their use of a hydraulic torque converter and permanent synchronous generator. This combination promotes steady and grid-ready energy without the use of a power converter. Thus, researchers were prompted to study the potential impact on grid reliability, stability, and resilience using a Real Time Digital Simulator (RTDS) model of the type-5 turbine, including a high-fidelity model of its gear box.

13 - HYDRO ENERGY

PHIL Interface Design for Use With a Voltage-Regulated Amplifier

Power hardware-in-the-loop (PHIL) has emerged as a leading strategy to thoroughly assess the impact of proprietary inverter controls on a specific power system. The development of a PHIL test bed typically involves an inverter under test, a power amplifier, controllable DC supply, and a digital real-time simulator (DRTS) to simulate the power system under study. As a result of PHIL nonidealities, a form of digital compensation within the DRTS is used, which is commonly referred to as a PHIL interface. Many existing methods use legacy power amplifiers that do not contain internal voltage regulation. These existing interface methods are based around a voltage regulator within the DRTS and do not consider the interaction with the controls in newer amplifiers. In this study, a three-step approach of PHIL interface development for modern power amplifiers with built-in voltage regulation is introduced and is validated in hardware with a 30-kW grid-following inverter.

DRTS