Model Improvement for ADMS Deployment

The objective of this research is to evaluate the performance of the advanced distribution management system (ADMS) Volt/VAR Optimization (VVO) application for different levels of model quality and different levels of measurement density -- using 4 different load days VVO optimized for conservative voltage regulation (CVR) and six feeders from Xcel Energy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Evaluation of Next-Generation Grid Automation and Controls with High PV Penetration

This paper presents a hardware-in-the-loop (BIL) simulation to evaluate the performance of an advanced grid automation architecture, referred to as data-enhanced hierarchical control (DEHC), in achieving voltage regulation and conservation voltage reduction (CVR) in distribution networks with very high photovoltaic (PV) generation. This architecture comprises an advanced distribution management system (ADMS), a distributed energy resource management system (DERMS), and grid-edge devices working synergistically to provide the grid benefits. The HIL setup used for the evaluation includes ADMS, DERMS, and grid-edge devices. The DEHC performance is evaluated in two representative scenarios considering loose and tight constraints of the power factor at the substation. The results show that the DEHC architecture is effective in achieving voltage regulation and CVR and thus enables the grid integration of high levels of PV generation.

ADMS↗

Optimal Energy Dispatch of Distributed PVs for the Next Generation of Distribution Management Systems

Advanced Distribution Management Systems (ADMS) are being widely adopted by electric utilities for managing and optimizing the operations of their distribution systems. Distributed photovoltaic (DPV) systems with smart inverters can be controlled to adjust active power and reactive power outputs, and they are envisioned to become a part of (centrally or distributed) controllable assets managed by the ADMS for optimizing grid operations. This paper proposes an optimal energy dispatch strategy controlling DPV systems for regulating distribution voltages and achieving conservation voltage reduction. A convex optimization model is proposed with the use of linearized power flow, and the gradient projection algorithm is used to solve the optimal active power and reactive power outputs of smart inverters. The proposed optimal energy dispatch is implemented using an open-source ADMS platform, and simulation results have demonstrated the effectiveness of the proposed approach on improving distribution grid operations.

42 ENGINEERING↗

Learning with Adaptive Conservativeness for Distributionally Robust Optimization: Incentive Design for Voltage Regulation

Information asymmetry between the Distribution System Operator (DSO) and Distributed Energy Resource Aggregators (DERAs) obstructs designing effective incentives for voltage regulation. To capture this effect, we employ a Stackelberg game-theoretic framework, where the DSO seeks to overcome the information asymmetry and refine its incentive strategies by learning from DERA behavior over multiple iterations. We introduce a model-based online learning algorithm for the DSO, aimed at inferring the relationship between incentives and DERA responses. Given the uncertain nature of these responses, we also propose a distributionally robust incentive design model to control the probability of voltage regulation failure and then reformulate it into a convex problem. This model allows the DSO to periodically revise distribution assumptions on uncertain parameters in the decision model of the DERA. Finally, we present a gradient-based method that permits the DSO to adaptively modify its conservativeness level, measured by the size of a Wasserstein metric-based ambiguity set, according to historical voltage regulation performance. The effectiveness of our proposed method is demonstrated through numerical experiments.

adaptation models↗

Learning with Adaptive Conservativeness for Distributionally Robust Optimization: Incentive Design for Voltage Regulation: Preprint

Information asymmetry between the Distribution System Operator (DSO) and Distributed Energy Resource Aggregators (DERAs) obstructs designing effective incentives for voltage regulation. To capture this effect, we employ a Stackelberg game-theoretic framework, where the DSO seeks to overcome the information asymmetry and refine its incentive strategies by learning from DERA behavior over multiple iterations. We introduce a model-based online learning algorithm for the DSO, aimed at inferring the relationship between incentives and DERA responses. Given the uncertain nature of these responses, we also propose a distributionally robust incentive design model to control the probability of voltage regulation failure and then reformulate it into a convex problem. This model allows the DSO to periodically revise distribution assumptions on uncertain parameters in the decision model of the DERA. Finally, we present a gradient-based method that permits the DSO to adaptively modify its conservativeness level, measured by the size of a Wasserstein metric-based ambiguity set, according to historical voltage regulation performance. The effectiveness of our proposed method is demonstrated through numerical experiments.

distribution system operator↗

Coordinated Use of Smart Inverters with Legacy Voltage Regulating Devices in Distribution Systems with High Distributed PV Penetration — Increase CVR Energy Savings

This paper studies the coordinated use of smart inverters with legacy voltage regulating devices to help increase the energy savings from conservation voltage reduction (CVR) in distribution systems with high photovoltaic penetration. Two voltage optimization algorithms are developed to evaluate the CVR benefit by considering two types of smart inverter functions: aggregated reactive power control and autonomous volt/VAR control. In each algorithm, smart inverters are coordinately controlled with the operation of legacy voltage regulating devices including load tap changers and capacitor banks. Both algorithms are tested on representative utility distribution system models. In conclusion, simulation results demonstrate that the proposed algorithms can achieve around 1.8-3.6% energy savings when only using legacy voltage regulating devices and an additional 0.3-0.9% when adding smart inverters.

14 SOLAR ENERGY↗

Distribution-Agnostic Stochastic Optimal Power Flow for Distribution Grids

This paper outlines a data-driven, distributionally robust approach to solve chance-constrained AC optimal power flow problems in distribution networks. Uncertain forecasts for loads and power generated by photovoltaic (PV) systems are considered, with the goal of minimizing PV curtailment while meeting power flow and voltage regulation constraints. A data- driven approach is utilized to develop a distributionally robust conservative convex approximation of the chance-constraints; particularly, the mean and covariance matrix of the forecast errors are updated online, and leveraged to enforce voltage regulation with predetermined probability via Chebyshev-based bounds. By combining an accurate linear approximation of the AC power flow equations with the distributionally robust chance constraint reformulation, the resulting optimization problem becomes convex and computationally tractable.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Photovoltaic Impact Assessment of Smart Inverter Volt-VAR Control on Distribution System Conservation Voltage Reduction and Power Quality

This report presents an impact assessment study of distributed photovoltaic (PV) with smart inverter Volt-VAR control on conservation voltage reduction (CVR) energy savings and distribution system power quality. CVR is a methodology of flattening and lowering a distribution system voltage profile in order to conserve energy. Traditional CVR relies on operating utility voltage regulators and switched capacitors. However, with the increased penetration of distributed PV systems, smart inverters provide the new opportunity to control local voltage and power factor by regulating the reactive power output, leading to a potential increase in CVR energy savings. This report proposes a methodology to implement CVR scheme by operating voltage regulators, capacitors, and autonomous smart inverter Volt-VAR control in order to achieve increased CVR benefit. Power quality is an important consideration when operating a distribution system, especially when implementing CVR. It is easy to measure the individual components that make up power quality, but a comprehensive method to incorporate all of these values into a single score has yet to be undertaken. As a result, this report proposes a power quality scoring mechanism to measure the relative power quality of distribution systems using a single number, which is aptly named the 'power quality score' (PQS). Both the CVR and PQS methodologies were applied to two distribution system models, one obtained from the Hawaiian Electric Company (HECO) and another obtained from Pacific Gas and Electric (PG&E). These two models were converted to the OpenDSS platform using previous model conversion tools that were developed by NREL. Multiple scenarios including various PV penetration levels and smart inverter densities were simulated to analyze the impact of smart inverter Volt-VAR support on CVR energy savings and feeder power quality. In order to analyze the CVR benefit and PQS, an annual simulation was conducted for each scenario.

14 SOLAR ENERGY↗

Evaluation of Conservation Voltage Reduction (CVR) on a National Level

Conservation Voltage Reduction (CVR) is a reduction of energy consumption resulting from a reduction of feeder voltage. While there have been numerous CVR systems deployed in North America there has been little substantive analytic analysis of the effect; the majority of the published results are based on empirical field measurements. Since these results are based on empirical measurements it is difficult to extrapolate how this technology will behave on the various types of distribution feeders found throughout the nation. This report has utilized the Taxonomy of Prototypical feeder developed under the Modern Grid Initiative (MGI), now the Modern Grid Strategy (MGS), in order to estimate the benefits of CVR on multiple distribution feeder types. This information will then be used to determine an estimate of the national benefits of a wide scale deployment of CVR.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Conservation Voltage Reduction with Distributed Energy Resource Management System, Grid-Edge, and Legacy Devices

Distribution utilities use conservation voltage reduction (CVR) to obtain energy savings and lower peak demand by reducing bus voltages. Traditionally, the CVR is accomplished by controlling the legacy assets such as load tap changers, voltage regulators, and capacitor banks. The deployment of the advanced distribution management system (ADMS) and distributed energy resource management system (DERMS) enables the integration of distributed energy resources into the distribution networks and provide the grid services including CVR. This paper studies the coordinated operation of an ADMS and a DERMS in achieving CVR and voltage regulation. A commercial ADMS uses legacy devices and Edge-of-Network Grid Optimization (ENGO) devices to obtain energy savings through CVR. A prototype DERMS dispatches the photovoltaic smart inverters based on real-time optimal power low to ensure voltage regulation across the feeder. The results show that the coordinated operation of ADMS and DERMS is effective in achieving CVR and voltage regulation. Specifically, energy savings of up to 4.7% are observed in the real utility distribution system used in this study.

advanced distribution management system↗

Conservation Voltage Reduction with Distributed Energy Resource Management System, Grid-Edge, and Legacy Devices

Distribution utilities use conservation voltage reduction (CVR) to obtain energy savings and lower peak demand by reducing bus voltages. Traditionally, the CVR is accomplished by controlling the legacy assets such as load tap changers, voltage regulators, and capacitor banks. The deployment of the advanced distribution management system (ADMS) and distributed energy resource management system (DERMS) enables the integration of distributed energy resources into the distribution networks and provide the grid services including CVR. This paper studies the coordinated operation of an ADMS and a DERMS in achieving CVR and voltage regulation. A commercial ADMS uses legacy devices and Edge-of-Network Grid Optimization (ENGO) devices to obtain energy savings through CVR. A prototype DERMS dispatches the photovoltaic smart inverters based on real-time optimal power low to ensure voltage regulation across the feeder. The results show that the coordinated operation of ADMS and DERMS is effective in achieving CVR and voltage regulation. Specifically, energy savings of up to 4.7% are observed in the real utility distribution system used in this study.

advanced distribution management system↗

Recovery Act: Integrated DC-DC Conversion for Energy-Efficient Multicore Processors

In this project, we have developed the use of thin-film magnetic materials to improve in energy efficiency of digital computing applications by enabling integrated dc-dc power conversion and management with on-chip power inductors. Integrated voltage regulators also enables fine-grained power management, by providing dynamic scaling of the supply voltage in concert with the clock frequency of synchronous logic to throttle power consumption at periods of low computational demand. The voltage converter generates lower output voltages during periods of low computational performance requirements and higher output voltages during periods of high computational performance requirements. Implementation of integrated power conversion requires high-capacity energy storage devices, which are generally not available in traditional semiconductor processes. We achieve this with integration of thin-film magnetic materials into a conventional complementary metal-oxide-semiconductor (CMOS) process for high-quality on-chip power inductors.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Control, Fault Management, and Grid Support Functionality of an MV AC-DC Solid State Transformer based EV Extreme Fast Charging Station

Electric vehicles (EVs) have become increasingly popular in recent times while revolutionizing the consumer and commercial transportation market. The development of charging infrastructure has become one of the priorities for increasing the adoption of EVs. Extreme fast charging (XFC) technology can reduce the so-called ’range anxiety’ of consumers as they significantly reduce the charging time. With the advent of wide band-gap (WBG) power devices and improvement in power electronic converters, medium voltage (MV) solid state transformer (SST) based XFC system has the potential to replace the traditional XFC stations because of the lower footprint, ease of installation, enhanced control feature, and better system efficiency. The control system design is one of the critical aspects of the SST development process. Careful consideration and detailed analysis are required to find out suitable control method for the SST based on its topology among different centralized and decentralized control architectures. Also, the control parameters selection and potential improvement to the transient response of the controller ought to be investigated. Another major concern of the SST is different types of internal fault which reduces the overall reliability of the XFC system. As a result, designing a robust protection system is essential. Among different fault modes, open circuit switch faults have received significant attention as an active research area because of their likelihood and severe effects on converters. Therefore, the power stages used in the XFC system require functional and accurate open circuit switch fault management methods. An equally significant aspect of this SST based XFC is its compatibility in a microgrid where there is no synchronous generator present. When the grid is not available, the XFC SSTs can provide grid forming capability and continue supplying the critical loads in islanded mode. The transition between grid connected and islanded mode, especially the grid resynchronization process has to be carefully performed for the safety of the microgrid components. The challenges posed by the aforementioned issues have inspired the work done in this dissertation. Here, a 13.2 kV, 1 MVA, AC/DC SST for the XFC system is examined and a comparative analysis is conducted to select the control architecture based on feasibility of implementation and performance. A detailed control parameter design process is demonstrated considering the sensor dynamics and delay. The selected decentralized control method is augmented by introducing a novel sensor-less load current feedforward method to provide better voltage regulation at the DC bus during a change of load. Next, in the fault management section, a hierarchical failure mode effect analysis (FMEA) is proposed to enable a systematic design of the internal fault protection of the XFC SST as there are limited examples in the literature regarding the analysis of the safety and design of the protection of a power electronic converter system. Novel open circuit switch fault management methods for the converters in the system are presented. Finally, XFC SST based MV microgrid operations in grid connected mode and islanded mode are explored. A secondary control method for grid resynchronization is presented and a design process of control parameters is shown to ensure the stability of the secondary voltage and frequency regulation.

30 DIRECT ENERGY CONVERSION↗

A Bidirectional High-Power-Quality Grid Interface With a Novel Bidirectional Noninverted Buck Boost Converter for PHEVs

Plug-in hybrid electric vehicles (PHEVs) will play a vital role in future sustainable transportation systems due to their potential in terms of energy security, decreased environmental impact, improved fuel economy, and better performance. Moreover, new regulations have been established to improve the collective gas mileage, cut greenhouse gas emissions, and reduce dependence on foreign oil. This paper primarily focuses on two major thrust areas of PHEVs. First, it introduces a grid-friendly bidirectional alternating current/direct current ac/dc dc/ac rectifier/inverter for facilitating vehicle-to-grid (V2G) integration of PHEVs. Second, it presents an integrated bidirectional noninverted buck boost converter that interfaces the energy storage device of the PHEV to the dc link in both grid-connected and driving modes. The proposed bidirectional converter has minimal grid-level disruptions in terms of power factor and total harmonic distortion, with less switching noise. The integrated bidirectional dc/dc converter assists the grid interface converter to track the charge/discharge power of the PHEV battery. In addition, while driving, the dc/dc converter provides a regulated dc link voltage to the motor drive and captures the braking energy during regenerative braking.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Distinct cellular expression and subcellular localization of Kv2 voltage‐gated K + channel subtypes in dorsal root ganglion neurons conserved between mice and humans

Abstract The distinct organization of Kv2 voltage‐gated potassium channels on and near the cell body of brain neurons enables their regulation of action potentials and specialized membrane contact sites. Somatosensory neurons have a pseudounipolar morphology and transmit action potentials from peripheral nerve endings through axons that bifurcate to the spinal cord and the cell body within ganglia including the dorsal root ganglia (DRG). Kv2 channels regulate action potentials in somatosensory neurons, yet little is known about where Kv2 channels are located. Here, we define the cellular and subcellular localization of the Kv2 paralogs, Kv2.1 and Kv2.2, in DRG somatosensory neurons with a panel of antibodies, cell markers, and genetically modified mice. We find that relative to spinal cord neurons, DRG neurons have similar levels of detectable Kv2.1 and higher levels of Kv2.2. In older mice, detectable Kv2.2 remains similar, while detectable Kv2.1 decreases. Both Kv2 subtypes adopt clustered subcellular patterns that are distinct from central neurons. Most DRG neurons co‐express Kv2.1 and Kv2.2, although neuron subpopulations show preferential expression of Kv2.1 or Kv2.2. We find that Kv2 protein expression and subcellular localization are similar between mouse and human DRG neurons. We conclude that the organization of both Kv2 channels is consistent with physiological roles in the somata and stem axons of DRG neurons. The general prevalence of Kv2.2 in DRG as compared to central neurons and the enrichment of Kv2.2 relative to detectable Kv2.1 in older mice, proprioceptors, and axons suggest more widespread roles for Kv2.2 in DRG neurons.

Neurosciences & Neurology↗

The spacecraft power supply system

The power supply system in the Telstar spacecraft consists of a solar cell plant to convert solar radiation to electrical energy when the satellite is illuminated by the sun, a 19-cell nickel-cadmium battery to store energy, and a regulation circuit to supply constant output voltages over a wide variation in input voltages. Additionally, the power supply system provides switching to conserve power and allow battery recharging during periods between communications experiments.

POWER SUPPLY↗

Optimal Power Flow for Distribution Systems under Uncertain Forecasts

The paper focuses on distribution systems featuring renewable energy sources and energy storage devices, and develops an optimal power flow (OPF) approach to optimize the system operation in spite of forecasting errors. The proposed method builds on a chance-constrained multi-period AC OPF formulation, where probabilistic constraints are utilized to enforce voltage regulation with a prescribed probability. To enable a computationally affordable solution approach, a convex reformulation of the OPF task is obtained by resorting to i) pertinent linear approximations of the power flow equations, and ii) convex approximations of the chance constraints. Particularly, the approximate chance constraints provide conservative bounds that hold for arbitrary distributions of the forecasting errors. An adaptive optimization strategy is then obtained by embedding the proposed OPF task into a model predictive control framework.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Developing Fuel Cell Electric Powertrain Architectures for Commercial Vehicles

Here, this article addresses the architecture development for a commercial vehicle fuel cell electric powertrain by establishing a clear multi-step formalized workflow that employs a unique technoeconomic solution for architecture selection. The power capability of the fuel cell, the energy capacity and chemistry of the electrical energy storage (battery), the DC-DC converter (including the input current rating and isolation resistance requirements), the traction drive solution, the on-board hydrogen storage solution, and the real-time power-split management of the fuel cell and the battery are all considered and developed in this effort. The methods were used to select architecture for Class 8 urban, regional, and line haul applications. When compared to traditional load-following power-split controllers, an energy management power-split controller can increase system energy efficiency by up to 19.5%. The energy-efficient power-split controller may increase the required battery capacity for an equivalent life by up to 2.6 times. The impact on the total cost of ownership (TCO) for a variety of financial cases demonstrates that high C-rate capable batteries have the potential to provide better TCO solutions over a six-year vehicle life than low C-rate capable batteries. To achieve TCO parity with the 600 A non-isolated DC-DC converter case, the specific choice of the fuel cell DC-DC converter to achieve a target power output based on current levels (from 500 A to 2400 A) shows that efficiency decreases and cost increases due to the higher current, requiring fuel cell prices to decrease by $50–$100/kW, $60–$110/kW, and $100–$220/kW for urban, regional, and line haul applications, respectively. Key recommendations for powertrain system architectures are provided, with specifics based on vehicle dynamics, mission and application characteristics, end customer use-case profile, critical powertrain component costs, and architecture selection cost function. This study rigorously demonstrates the interplay of the above parameters, with a focus on TCO, and provides application decision-makers with a mechanism and well-defined set of impact factors to consider as part of their architecture selection process.