At least 19 records

A systematic feature extraction and selection framework for data-driven whole-building automated fault detection and diagnostics in commercial buildings

In data-driven automated fault detection and diagnostics (AFDD) modeling for building energy systems, feature engineering is a critical process of extracting information from high-dimensional and noisy sensor measurement and turning it into informative and representative inputs or features for data-driven modeling. However, few studies specifically discuss the feature engineering, especially the interactions between feature extraction and feature selection in whole-building AFDD. We developed a systematic feature extraction and selection framework for whole-building AFDD. In this framework, features are aggressively extracted from raw sensor data using statistical feature extraction techniques with various window sizes and statistics. With many features extracted, a hybrid feature selection algorithm that combines the filter and wrapper method then selects the best feature set. The framework considers diversity in the duration of fault behavior among fault types in whole-building AFDD, thus achieving high model generalization. We implemented our developed framework in a virtual testbed calibrated with measured data from Oak Ridge National Laboratory's Flexible Research Platform designed to mimic the operation of a typical small commercial building. The AFDD model is trained by the simulation data generated from the virtual testbed. The results show that (1) the developed framework improves the generalization of the AFDD model by 10.7% compared with literature-reported feature extraction and selection methods and (2) features with diverse window sizes and statistics are selected, providing insight into physical systems beyond the current understanding of buildings and faults and improving the detection and diagnostics of multiple fault types.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensor cost-effectiveness analysis for data-driven fault detection and diagnostics in commercial buildings

Data-driven building fault detection and diagnostics (FDD) is heavily dependent on sensors. However, common sensors from Building Automation Systems are not optimized to maximize accuracy in FDD. Installing additional sensors that provide more detailed building system information is key to maximizing the performance of FDD solutions. Here in this paper, we present a sensor cost analysis workflow to quantify the economic implications of installing new sensors for FDD using the concept of sensor threshold marginal cost (STMC). STMC does not represent actual sensor cost. Rather, it represents a target cost based on the economic benefit that would be realized through improved FDD performance and one or more specified economic criteria. We calculate STMCs for multiple possible fault types and use fault prevalence information to aggregate STMCs into a single dollar value to determine the cost-effectiveness of a potential sensor investment. We conducted a case study using Oak Ridge National Laboratory's Flexible Research Platform (FRP) test facility as a reference. The case study demonstrates the feasibility of the analysis and highlights the key cost considerations in sensor selection for FDD. The results also indicate that identifying and installing the few key sensor(s) is critical to cost-effectively improve FDD performance.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Evaluate the impact of sensor accuracy on model performance in data-driven building fault detection and diagnostics using Monte Carlo simulation

The performance of data-driven fault detection and diagnostics (FDD) is heavily dependent on sensors. However, sensor inaccuracy and sensor faults are pervasive in building operation: inaccurate and missing sensor readings deteriorate FDD performance; sensor inaccuracy will also affect the selection of sensor for data-driven FDD in the model training process, which is another key factor of data-driven FDD performance. Sensor accuracy and sensor selection individually are well-studied research topics in this field, but the impact of sensor accuracy on sensor selection and its further impact on FDD performance has not been evaluated and quantified. In this paper, we developed a novel analysis methodology that comprehensively evaluates sensor fault on sensor selection and FDD accuracy. Monte Carlo simulation is applied to deal with multiple stochastic sensor inaccuracy and provide probabilistic analysis results of the impact of sensor inaccuracy on sensor selection and FDD accuracy. This methodology focuses on the net impact of fault states across a full sensor set. The developed methodology can be used for the early-stage sensor design and operation-stage sensor maintenance. Furthermore, a case study is conducted to demonstrate the analysis methodology using a commercial building model crated to Flexible Research Platform located at Oak Ridge National Laboratory, USA.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensor impact evaluation and verification for fault detection and diagnostics in building energy systems: A review

Sensors are the key information source for fault detection and diagnostics (FDD) in buildings. However, sensors are often not properly designed, installed, calibrated, located, and maintained, which negatively impacts FDD performance. Several sensor-related FDD topics have been widely studied, covering a wide range of fault types and applications. However, it is difficult to get a clear picture of the technical development of sensor-related topics in FDD. A systematic review of sensor topics is needed to summarize the existing research in a logical way, draw conclusions on the current development, and predict the future development of sensors in building FDD. To address this gap, we conducted a comprehensive literature review of more than 100 FDD-sensor-related papers. In this article, we subdivide the FDD tasks into building-level, system-level, and component-level FDD, and review sensor-related topics in each category. Our major conclusions are: (a) current data-driven FDD research focuses more on FDD algorithms than sensors, (b) sensor “hardware” research topics are less studied than sensor “software” topics, (c) very few papers focus on sensor engineering as an integral aspect of FDD development, and (d) some important sensor topics, such as sensor cost-effectiveness and sensor schema/layout/location, are not well studied. Finally, we discuss the need for a systematic framework of FDD sensors and models to integrate sensor design/selection, sensor data analysis/mining, feature selection, physics-based or data-driven algorithm development, sensor fault detection, sensor calibration, and sensor maintenance. Finally, expert interviews are conducted to validate the above findings and conclusions.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Building fault detection data to aid diagnostic algorithm creation and performance testing

It is estimated that approximately 4-5% of national energy consumption can be saved through corrections to existing commercial building controls infrastructure and resulting improvements to efficiency. Correspondingly, automated fault detection and diagnostics (FDD) algorithms are designed to identify the presence of operational faults and their root causes. A diversity of techniques is used for FDD spanning physical models, black box, and rule-based approaches. A persistent challenge has been the lack of common datasets and test methods to benchmark their performance accuracy. This article presents a first of its kind public dataset with ground-truth data on the presence and absence of building faults. This dataset spans a range of seasons and operational conditions and encompasses multiple building system types. It contains information on fault severity, as well as data points reflective of the measurements in building control systems that FDD algorithms typically have access to. The data were created using simulation models as well as experimental test facilities, and will be expanded over time.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Market Barriers and Drivers for the Next Generation Fault Detection and Diagnostic Tools

Commercial buildings in the U.S. consume as much as 30% excess energy compared to buildings that operate fault free and efficiently. Fault detection and diagnostic (FDD) platforms help to continually identify operational inefficiencies and maintain low-carbon performance. However, the recommendations generated by FDD tools need to be implemented by technicians, resulting in delays or lost savings opportunities. Recent research advances showed fault AUTOcorrection integrating with commercial FDD offerings filled this gap. Seven innovative AUTOcorrection algorithms were integrated into two FDD platforms and deployed across four buildings. The enhanced tools successfully correct faults focusing on incorrectly programmed schedules, override not released, control hunting, rogue zone, and suboptimal setpoints. Although its technical efficacy has been proven in the field, fault AUTO-correction is still early in the deployment cycle and opportunities and barriers need to be understood to reach its full potential in market transformation. This paper broadly introduces the new technology that automatically corrects HVAC faults. The authors describe in detail technology potential, market barriers, and enablers for scalability based on field testing results and interviews with the FDD providers and facility managers. The interviewees agreed that AUTO-correction can reduce the extent to which savings are dependent upon human intervention, scale building operators’ ability to act on FDD findings (especially for facilities with small operation teams), and achieve significant savings. To enable scalable deployment, future efforts are needed to overcome the barriers such as cybersecurity and accountability concerns from building operators and standardization of control parameters used in building automation systems.

Pritoni, Marco↗

Analysis of Fault Data Collected from Automated Fault Detection and Diagnostic Products for Packaged Rooftop Units

Rooftop units (RTUs) and other packaged systems are very common in commercial buildings in the U.S., and they often have minimal controls and poor performance. Automated fault detection and diagnostics (AFDD) is a powerful tool that can continuously monitor operating equipment, detect abnormal performance, diagnose problems, and report findings to building operators. AFDD technologies for RTUs have been under development for many years and have recently begun to enter the market in a significant way. There are several AFDD systems available for RTUs that feature a wide range of designs, capabilities, and reporting. Unfortunately, there is little consistency among the AFDD applications and little understanding of the performance and value of these systems. This study presents analysis of AFDD data provided by four companies from over 28,000 RTUs, five building types, and multiple climate zones. The objectives of this investigation were to gain a better understanding of how RTU AFDD systems operate, the types and frequencies of faults identified, and how building operators interact with these systems. The monitoring of a variety of RTUs provides insights into the AFDD monitoring inputs, faults, and diagnostics from which these tools are capable of informing building owners about the status of their HVAC systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Analysis of Fault Data Collected from Automated Fault Detection and Diagnostic Products for Packaged Rooftop Units

Rooftop units (RTUs) and other packaged systems are very common in commercial buildings in the U.S., and they often have minimal controls and poor performance. Automated fault detection and diagnostics (AFDD) is a powerful tool that can continuously monitor operating equipment, detect abnormal performance, diagnose problems, and report findings to building operators. AFDD technologies for RTUs have been under development for many years and have recently begun to enter the market in a significant way. There are several AFDD systems available for RTUs that feature a wide range of designs, capabilities, and reporting. Unfortunately, there is little consistency among the AFDD applications and little understanding of the performance and value of these systems. This study presents analysis of AFDD data provided by four companies from over 28,000 RTUs, five building types, and multiple climate zones. The objectives of this investigation were to gain a better understanding of how RTU AFDD systems operate, the types and frequencies of faults identified, and how building operators interact with these systems. The monitoring of a variety of RTUs provides insights into the AFDD monitoring inputs, faults, and diagnostics from which these tools are capable of informing building owners about the status of their HVAC systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Cloud-Control of Legacy Building Automation System: A case study

As Internet of Things devices and cloud-based platforms become more mature, Energy Management and Information Systems (EMIS) are increasingly gaining momentum in the building industry. In large commercial buildings, Fault-Detection and Diagnostic (FDD) and energy information systems (EIS) are now established technologies with tens of providers and thousands of deployment sites across North America. The new frontier for the EMIS technology is now represented by control systems that use advanced system optimization (ASO) methods to improve the operations of the HVAC system. Given the complexity of the integration of such systems with the existing building automation systems (BAS) and the higher risk involved with direct control of the HVAC, these systems are still emerging in the market. This paper presents the results of a project in which a start-up company partnered with a research institution to develop a cloud-based software EMIS solution and deployed it in a university campus in California. The software system included advanced sensing, data acquisition, storage and advanced control and analytics applications developed on top of the native BAS. The new platform controls ten buildings on the campus and the FDD and the ASO applications deployed on this platform were able to generate energy savings of up to 35% and 25% in certain buildings for each functionality respectively. Where the platform did not save energy, it improved building service (air quality). Lessons learned include the importance of collaborating with and training the building operators and evaluating whether the legacy system can work reliably with the new technology.

Prakash, Anand Krishnan↗

Literature Review for Sensor Impact Evaluation and Verification Use Cases - Building Controls and Fault Detection and Diagnosis (FDD)

This report summarizes a comprehensive literature review for the selected sensor suites used in building controls and fault detection and diagnostics (FDD), which is a Q2 deliverable of the Sensor Impact Evaluation and Verification project. The project’s overarching goal is to develop a framework for investigating the impact of sensor deployment and configuration for building energy optimization, fault detection and diagnosis (FDD), occupants’ thermal comfort, and potential grid efficiency. While the first phase of the literature review performed in Q1 reviewed the current methods of various sensor selection and placements and their impact, this report focuses on high impactful potential use cases for the selected sensor suites in building control and FDD. The use cases identified in this literature review will be further investigated and be included in the final sensor impact evaluation framework. For the review, the multi-laboratory team reviewed 241 research papers, technical reports, and books to identify existing technologies, the potential impact on energy savings and thermal comfort, and future research opportunities for the selected use cases in building controls and FDD. Along with the literature review, the team conducted a series of interviews with experts in sensors and controls area to identify the state-of-art sensor technologies, and the most impactful use cases in controls and FDD areas. The interview results will also be incorporated with the findings from the literature review in the next quarter, and the final use cases to be evaluated will be selected.

47 OTHER INSTRUMENTATION↗

Implementation and test of an automated control hunting fault correction algorithm in a fault detection and diagnostics tool

Control hunting due to improper proportional–integral–derivative (PID) parameters in the building automation system (BAS) is one of the most common faults identified in commercial buildings. It can cause suboptimal performance and early failure of heating, ventilation, and air conditioning (HVAC) equipment. Commercial fault detection and diagnostics (FDD) software represents one of the fastest growing market segments in smart building technologies in the United States. Implementation of PID retuning procedures as an auto-correction algorithm and integration into FDD software has the potential to mitigate control hunting across a heterogeneous portfolio of buildings with different BAS in a scalable way. This paper presents the development, implementation, and field testing of an automated control hunting fault correction algorithm based on lambda tuning open-loop rules. The algorithm was developed in a commercial FDD software and successfully tested among nine variable air volume boxes in an office building in the United States. The paper shows the feasibility of using FDD tools to automatically correct control hunting faults, discusses scalability considerations, and proposes a path forward for the HVAC industry and academia to further improve this technology.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Building Analytics Tool Deployment at Scale: Benefits, Costs, and Deployment Practices

Buildings are becoming more data-rich. Building analytics tools, including energy information systems (EIS) and fault detection and diagnostic (FDD) tools, have emerged to enable building operators to translate large amounts of time-series data into actionable findings to achieve energy and non-energy benefits. To expedite data analytics adoption and facilitate technology innovation, building owners, technology developers, and researchers need reliable cost–benefit data and evidence-based guidance on deployment practices. This paper fulfills these needs with the energy use and survey data from a wide-ranging research and industry partnership program that covers thousands of buildings installed with analytics tools. The paper indicates that after two years of implementation, organizations using FDD tools and EIS tools achieved 9% and 3% median annual energy savings, respectively. The median base cost and annual recurring cost for FDD are USD 0.65 per square meter (m2) (USD 0.06 per square foot [ft2]) and USD 0.22 per m2 (USD 0.02 per ft2), and are USD 0.11 per m2 (USD 0.01 per ft2) and USD 0.11 per m2 (USD 0.01 per ft2) for EIS. The common metrics and analyses that are used in the tools to support the discovery of energy efficiency measures are summarized in detail. Two best practice examples identified to maximize the benefits of tool implementation are also presented. Opportunities to advance the state of technology include simplified data integration and management, and more efficient processes for acting on analytics outputs. Compared with previous efforts in the literature, the findings presented in this paper demonstrate the effectiveness of building analytics tools with the largest known dataset.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Bringing Automated Fault Detection and Diagnostics Tools for HVAC&R Into the Mainstream

Heating, ventilation, and air-conditioning (HVAC) systems consume over 5 quads of energy annually, representing 30% of energy consumption in the U.S. commercial buildings. Additionally, commercial refrigeration (R) systems add about 1 quad to commercial buildings energy consumption. Most HVAC systems operate with one or more faults that result in increased energy consumption. Fault detection and diagnostics (FDD) tools have been developed to address this national issue, and many tools are commercially available. FDD tools have the potential to save considerable energy for an existing commercial rooftop unit (RTU) and refrigeration systems. These devices can be used for both retro commissioning and, when faults are addressed, continuous commissioning. However, there appears to be multiple market barriers for this technology. Although there are efforts to develop FDD tool standards, currently there are no standards and methods to define functions, capabilities, accuracy, and reliability of FDD tools in the field. Moreover, most of the commercial FDD tools have not been verified in the field independently. This paper presents a comprehensive approach for bringing HVAC FDD tools into the mainstream. The approach involves demonstrating ten commercially available FDD tools installed at ten different sites, independent testing and evaluation of the FDD tools, communication with various stakeholders, identifying and assessing market barriers, creating a process evaluation methodology, and assisting utility companies in developing incentive programs. Furthermore, the preliminary baseline results from the case study demonstrate how the use of an independent monitoring system (IMS) can be used for ground-truth in evaluating FDD tools in the field.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensor Impacts Evaluation and Verification: Expert Interview Responses

The sensor configuration/deployment method has critical impacts on energy efficient building control and thermal comfort. However, traditional sensor techniques for building operation and fault detection and diagnostics (FDD) are not necessarily optimal in terms of energy efficiency and thermal comfort, and their global effects are not thoroughly investigated. In an effort to address and overcome this limitation, a multilaboratory and multiyear project, “Sensor Impact Evaluation and Verification,” was proposed. Its purpose is to develop a framework to investigate the impacts of sensor deployment and configuration on building energy optimization, FDD, occupant thermal comfort, and potentially grid efficiency. The first project task was a literature review to establish a solid knowledge of and a background related to sensor technologies and placement. To accomplish this task, an extensive review of previous research literature was performed. A series of expert interviews were conducted to augment the findings of the literature review. This report summarizes the interview design and interview results and findings. The interview was designed and performed to (1) investigate the current status and limitations of sensor configuration, (2) identify the research gaps and expectations for potential improvements in sensor configuration and deployment, and (3) integrate expert (e.g., researcher, building operation practitioner) knowledge and experience to develop use-case scenarios.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Development of a Unified Taxonomy for HVAC System Faults

Detecting and diagnosing HVAC faults is critical for maintaining building operation performance, reducing energy waste, and ensuring indoor comfort. An increasing deployment of commercial fault detection and diagnostics (FDD) software tools in commercial buildings in the past decade has significantly increased buildings’ operational reliability and reduced energy consumption. A massive amount of data has been generated by the FDD software tools. However, efficiently utilizing FDD data for ‘big data’ analytics, algorithm improvement, and other data-driven applications is challenging because the format and naming conventions of those data are very customized, unstructured, and hard to interpret. This paper presents the development of a unified taxonomy for HVAC faults. A taxonomy is an orderly classification of HVAC faults according to their characteristics and causal relations. The taxonomy includes fault categorization, physical hierarchy, fault library, relation model, and naming/tagging scheme. The taxonomy employs both a physical hierarchy of HVAC equipment and a cause-effect relationship model to reveal the root causes of faults in HVAC systems. A structured and standardized vocabulary library is developed to increase data representability and interpretability. The developed fault taxonomy can be used for HVAC system ‘big data’ analytics such as HVAC system fault prevalence analysis or the development of an HVAC FDD software standard. A common type of HVAC equipment-packaged rooftop unit (RTU) is used as an example to demonstrate the application of the developed fault taxonomy. Two RTU FDD software tools are used to show that after mapping FDD data according to the taxonomy, the meta-analysis of the multiple FDD reports is possible and efficient.

96 KNOWLEDGE MANAGEMENT AND PRESERVATION↗

Sensor Impact Evaluation and Verification Technical Advisory Group Meeting Minutes

This report provides the technical advisory group meeting minutes and summary of detailed discussions for future development of sensor impact evaluations and verifications. Methods for sensor configuration/deployment have critical impacts on energy-efficient building control and thermal comfort. However, traditional sensor techniques for building operation and fault detection and diagnostics (FDD) are not optimal in terms of energy efficiency and thermal comfort, and their global effects are not thoroughly investigated. In an effort to address and overcome this limitation, a 3 year project, Sensor Impact Evaluation and Verification, was proposed. The multi-laboratory team—the US Department of Energy’s Oak Ridge National Laboratory (ORNL), Pacific Northwest National Laboratory (PNNL), and the National Renewable Energy Laboratory (NREL)—is conducting early-stage R&D to provide technical supports and guidelines for sensor design in building/HVAC systems to optimize building energy use, FDD, thermal comfort, and grid efficiency. The overall goal of this project is to develop a framework that enables quantitative evaluation of the impact of sensors on building HVAC control, FDD, and consequently, building energy efficiency and thermal comfort.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Advanced control sequences and FDD technology. Just shiny objects, or ready for scale?

Innovations in commercial building control sequences (ASHRAE guideline 36) and fault detection and diagnostics (FDD) technology have the potential to transform existing building operational efficiency by realizing whole-building level savings on the order of 15% and higher. However, several technical and market barriers related to up-front estimation of achievable savings, verifying implementation, and ensuring persistence are slowing down their adoption as a core offering through diverse owner-funded initiatives and rate-payer funded programs. This paper describes a suite of solutions to overcome these barriers to program delivery of advanced HVAC controls integrated with FDD energy management and information system (EMIS) technology. First, the Guideline 36 conformance test offers an automated method to confirm correct sequence implementation by the manufacturer, before field deployment. A successful test of a controller was conducted using a new manufacturer-independent hardware-in-the-loop testbed demonstrating the viability and scalability of this approach. Second, the Guideline 36 energy savings calculator uses modeling paired with high-level user inputs to estimate building-specific savings potential, target cost effective implementation and minimize uncertainty. Initial results indicate the baseline control sequences significantly impact energy savings, however, as much as 50% savings may be possible for the worst-case baseline scenario. Third, a functional specification provides minimum recommended EMIS-FDD capabilities, and best practices to integrate the technology into organizational practice and ensure that advanced control sequences provide persistent savings.

Pritoni, Marco↗

Metadata Schemas and Ontologies for Building Energy Applications: A Critical Review and Use Case Analysis

With the increasing digitalization of processes throughout the lifecycle of buildings, data exchanged between stakeholders and between building systems has grown significantly. However, a lack of semantic interoperability between data in different systems is still prevalent, hindering the development of applications that can be reused across buildings and limiting the scalability of innovative solutions. Semantics refers to the description of the meaning of the data in a way that can be consistently understood by applications. Recently, several competing initiatives have been developing metadata schemas and ontologies to express this semantic information for different applications in the building domain. This paper systematically reviews these schemas and conducts an analysis of five of them to evaluate their applicability to three high-value use cases for building operations: energy audits, automated fault detection and diagnostics and optimal control. The survey finds 40 schemas published in the last 10 years but but their actual use in industry is difficult to estimate. Among the five selected ontologies, several gaps are highlighted in relation to the three use cases. Recommendations for the future include better harmonization of these initiatives, more centralized repositories and search engines for these schemas as well as better industry engagement to facilitate their adoption.

Smart Building, Sematic, Metadata, Ontology, Data ↗