Hybrid Cooling and Water Treatment for Resilient, Water-Self-Sufficient Data Centers
The continued growth of data center infrastructure is intensifying demand for freshwater resources, particularly in water-stressed regions, and is increasingly limiting sustainable capacity expansion. This work investigates a conceptual hybrid system that integrates freeze desalination with ultrasonic-assisted ice separation to enable on-site production of pure water from diverse sources, including seawater, brackish groundwater, and reclaimed industrial or agricultural wastewater. Simultaneously, the system produces low-temperature cooling streams that enhance heat removal in high power density computing environments. A process-level thermodynamic analysis is performed across a range of boundary and operating conditions, including variations in feed concentration, freezing temperature, and mass flow rate. The results are presented as performance curves relating feedwater concentration and target purified water output to the corresponding intake flow requirements, enabling estimation of source water demand per unit of Information Technology Equipment (ITE) energy consumption (kWh) across varying data center scales and operational scenarios. The corresponding electrical energy consumption for integrated cooling and water treatment is also evaluated as a function of system operating parameters and target water production levels. These results provide a basis for evaluating system feasibility across different conditions and for identifying parameter ranges in which integrated water treatment and cooling improve resource efficiency, thermal performance, and operational flexibility in data centers.