Distributed resilient consensus on general digraphs under cyber-attacks
Not Available
SEARCH · Engineering Papers
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Not Available
This report includes two main accomplishments of the peer-to-peer communication control for resilient operation of networked microgrids project in FY24, which include a scheme for cyberattack-aware coordination of networked microgrids for supporting voltages of bulk power systems and a scheme for price signal-based operations of EV-rich networked microgrids with mixed ownership. First, the cyberattack-aware scheme enables networked microgrids to distributedly determine the amount of reactive power injection to support the voltage of bulk power system (BPS) in a fair manner. In this scheme, a risk-informed algorithm is presented to generate the peer-to- peer (P2P) communication graph with minimal risk of attack on communication links. To deal with cyberattacks on MG controllers, the resilient consensus algorithm (CA) is utilized for MG controllers to robustly estimate the total reactive power headroom, from which the MGs can accurately provide the needed amount of reactive power injection for supporting the voltage of BPS. The CA implementation and performance within the P2P communication framework are demonstrated on the IEEE 39-bus system with 6 microgrids contained in the distribution feeder under different cyberattack scenarios. Second, the price-based scheme enables the usage of the real-time price signal for the operations of electric vehicle (EV)-rich networked-microgrids with mixed ownership, in which not all the microgrids can communicate with the distribution system operator (DSO). In this scheme, a max consensus is introduced to enable the real-time price signal to be propagated from the DSO to all the microgrids, from which each microgrid controller will manage the DERs to balance the load demand and the power injection from the EV charging stations within its microgrid. Numerical results over one day with 288 slots of 5-minute intervals on the modified 123-node test feeder including 3 microgrids with high penetration of EV are presented to evaluate how the price signal affects the operations of networked microgrids under different charging strategies of the EV charging stations. The result indicates that our proposed EVCS (dis)charging strategy, which leverages the flexibility of EVs to support the grid through discharging during peak demand, proves to be a cost-effective solution that reduces operational costs while improving the social welfare of EV charging.
Networking of microgrids can provide the operational flexibility needed for the increasing number of DERs deployed at the distribution level and supporting end-use demand when there is loss of the bulk power system. But, networked microgrids are vulnerable to cyber-physical attacks and faults due to the complex interconnections. As such, it is necessary To design resilient control systems to support the operations of networked microgrids in responses to cyber-physical attacks and faults. This paper introduces a resilient communication scheme for interconnecting multiple microgrids to support critical demand, in which the interconnection decision can be made distributedly by each microgrid controller even in the presence of cyberattacks to some communication links or microgrid controllers. This scheme blends a randomized peer-to-peer communication network for exchanging information among controllers and resilient consensus algorithms for achieving reliable interconnection agreement. The network of 6 microgrids divided from a modified 123-node test distribution feeder is used to demonstrate the effectiveness of the proposed resilient communication scheme.
This paper considers a leader-following consensus in the presence of unknown but bounded cyber-attacks. Specifically, we consider the following cyber-attack scenarios: (i) an attacker aims to destabilize the consensus dynamics by injecting exogenous signals to both the actuators of the followers and/or the communication network, (ii) an eavesdropper adversary aims to obtain information on the physical state of the agents. To this end, a novel resilient leader-following consensus algorithm based on a competitive interaction method is proposed. In addition, it is demonstrated that by appropriately choosing the information exchanged between the agents, the proposed control framework also enables the cooperative system to either distributively identify the compromised communication links in real-time or to protect the privacy of the physical state of the agents from the eavesdropper. Here, a numerical example is provided to illustrate the proposed resilient control algorithms.
Wind turbines in a wind farm typically operate individually to maximize their own performance and do not take into account information from nearby turbines. To enable cooperation to achieve farm-level objectives, turbines will need to use information from nearby turbines to optimize performance, ensure resiliency when other sensors fail, and adapt to changing local conditions. A key element of achieving these cooperative wind farms is to develop algorithms that provide necessary information to ensure reliable and efficient operation of turbines in a wind plant using local sensor information that is already being collected, such as supervisory control and data acquisition (SCADA) data, local meteorological stations, and nearby radars/sodars/lidars. This presentation demonstrates a framework for implementing a cooperative wind. Farm that incorporates information from local sensors in real time to better align turbines in a wind farm. Oftentimes, measurements made at an individual turbine are noisy and unreliable. By incorporating measurements from multiple nearby turbines, a more reliable estimate of the wind direction can be obtained at an individual turbine. Results indicate that this estimate of the wind direction can be used to improve the turbine's knowledge of the wind direction and could decrease dynamic yaw misalignment, decrease the amount of time a turbines spends yawing due to a more reliable input to the yaw controller, and increase resiliency to faulty wind-vane measurements. The concept was evaluated on data provided by WindESCo and was evaluated across several other averaging techniques to demonstrate the resiliency of the proposed consensus method.
Here, this paper considers a cooperative control problem in presence of unknown attacks. The attacker aims at destabilizing the consensus dynamics by intercepting the system’s communication network and corrupting its local state feedback. We first revisit the virtual network based resilient control proposed in our previous work and provide a new interpretation and insights into its implementation. Based on these insights, a novel distributed algorithm is presented to detect and identify the compromised communication links. It is shown that it is not possible for the adversary to launch a harmful and stealthy attack by only manipulating the physical states being exchanged via the network. In addition, a new virtual network is proposed which makes it more difficult for the adversary to launch a stealthy attack even though it is also able to manipulate information being exchanged via the virtual network. A numerical example demonstrates that the proposed control framework achieves simultaneously resilient operation and real-time attack identification.
With the increased adoption of distributed energy resources (DER), they are expected to contribute to power system reliability services and enhance power system stability. This paper presents a distributed consensus control approach for the real-time active power reserve estimation and power management in distributed PV (photovoltaic) systems. The proposed method estimates the cumulative active power reserve from numerous PV generators using only the sparse communication network for a DER aggregator to provide active power regulation services. The real-time active power reserve estimation using the proposed approach can be used by DER aggregators to manage curtailment in distributed PV systems to maintain stipulated reserves and further to provide power system frequency regulation. Using the proposed approach, the DER aggregator only requires measurements at the feeder substation and it does not require information from individual DER units, thereby improving system resiliency. The proposed distributed consensus control method is validated on IEEE 123 testbed using PSCAD simulations.
With the increased adoption of distributed energy resources (DER), they are expected to contribute to power system reliability services and enhance power system stability. This paper presents a distributed consensus control approach for the real-time active power reserve estimation and power management in distributed PV (photovoltaic) systems. The proposed method estimates the cumulative active power reserve from numerous PV generators using only the sparse communication network for a DER aggregator to provide active power regulation services. The real-time active power reserve estimation using the proposed approach can be used by DER aggregators to manage curtailment in distributed PV systems to maintain stipulated reserves and further to provide power system frequency regulation. Using the proposed approach, the DER aggregator only requires measurements at the feeder substation and it does not require information from individual DER units, thereby improving system resiliency. The proposed distributed consensus control method is validated on IEEE 123 testbed using PSCAD simulations.
Not provided.
In this project, we developed a leader-follower consensus (LFC) control architecture to coordinate between GFM and GFL inverters with the former being leaders and the latter being followers. The objective is to simultaneously achieve a fast frequency and voltage regulation along with accurate real power and var sharing among all inverters under various disturbances. The distinction of our work is that we consider both GFM and GFL inveters for frequency and voltage regulations. In addition, rather than a standard consensus algorithm, our work utilized a leader-follower consensus algorithm which exploits the physical characteristics of GFM-GFL inverters: (i) the GFM inverters directly control frequency and voltage, and hence, serve as leaders, (ii) the GFL inverters measure frequency/voltage to modulate their outputs, and hence, they should serve as followers. The effectiveness of the proposed LFC coordination was tested on a networked microgrid test system under different disturbances and communication degradation events. We demonstrated that the proposed fully coordinated control is robust to disturbances, while outperforming uncoordinated and GFM-only coordinated approaches. Overall, this work emphasized the necessity and benefits of the GFMGFL coordination in the secondary control of microgrids.
Herein, we investigate the design of a resilient consensus observer that yields correct and continuous state estimates of a nonlinear control system whose state observations are subject to attacks. The observations are assumed to be obtained from multiple sensors and/or communication channels employed to provide redundancy. It is shown that, in an attack-free setting, individual globally convergent observers can be designed for each sensor/channel using the corresponding state-dependent Jacobian system. To counter attacks, a resilient consensus observer is then designed by merging the observers estimates to produce a smooth consensus estimate. Resilient convergence of the consensus estimate to the true state is ensured under the condition that the sparsity of the attacks being less than a half of the number of redundant channels. As an illustrative example, the proposed scheme is successfully applied to the chaotic circuit synchronization problem in which their synchronization has been attacked.
This paper proposes a distributed control method based on a consensus algorithm for distributed energy resources (DERs) using blockchain as a secure communication medium for cyber resilience. Each DER communicates with a local blockchain server that is maintained by the distributed ledger technology to allow for securely sharing local measurements among neighboring assets to achieve the global control objectives, i.e., voltage and frequency regulation as well as accurate power sharing among the DERs, including collective grid-forming capability. To prove that the distributed control can retain system stability under a blockchain-induced variable communication delay, Lyapunov function-based stability analysis is carried out. This paper demonstrates the concept on an 11-bus test case developed in MATLAB Simulink, which has been modified from the IEEE 9-bus test case, to study dynamic operations of the five inverter-based DERs working with a blockchain-induced variable delay. The results validate the superior performance of the proposed control method, compared to heavily compromised operations of the other test cases without the security measure, affected by heavy communication delays and communication interruptions.
This paper proposes a distributed control method based on a consensus algorithm for distributed energy resources (DERs) using blockchain as a secure communication medium for cyber resilience. Each DER communicates with a local blockchain server that is maintained by the distributed ledger technology to allow for securely sharing local measurements among neighbouring assets to achieve the global control objectives, i.e., voltage and frequency regulation as well as accurate power sharing among the DERs, including collective grid-forming capability. To prove that the distributed control can retain system stability under a blockchain-induced variable communication delay, Lyapunov function-based stability analysis is carried out. This paper demonstrates the concept on an 11-bus test case developed in MATLAB Simulink, which has been modified from the IEEE 9-bus test case, to study dynamic operations of the five inverter-based DERs working with a blockchain-induced variable delay. The results validate the superior performance of the proposed control method, compared to heavily compromised operations of the other test cases without the security measure, affected by heavy communication delays and communication interruptions.
Wind turbines in a wind farm typically operate individually to maximize their own performance and do not take into account information from nearby turbines. In an autonomous wind farm, enabling cooperation to achieve farm-level objectives, turbines will need to use information from nearby turbines to optimize performance, ensure resiliency when other sensors fail, and adapt to changing local conditions. A key element of achieving an autonomous wind farm is to develop algorithms that provide necessary information to ensure reliable, robust, and efficient operation of wind turbines in a wind plant using local sensor information that is already being collected, such as supervisory control and data acquisition (SCADA) data, local meteorological stations, and nearby radars/sodars/lidars. This code implements a framework for implementing an autonomous wind farm that incorporates information from local sensors in real time to better align turbines in a wind farm. Oftentimes, measurements made at an individual turbine are noisy and unreliable. By incorporating measurements from multiple nearby turbines, a more robust estimate of the wind direction can be obtained at an individual turbine. Results indicate that this estimate of the wind direction can be used to improve the turbine's knowledge of the wind direction and could decrease dynamic yaw misalignment, decrease the amount of time a turbine spends yawing due to a more robust input to the yaw controller, and increase resiliency to faulty wind-vane measurements.
Abstract. Wind turbines in a wind farm typically operate individually to maximize their own performance and do not take into account information from nearby turbines. To enable cooperation to achieve farm-level objectives, turbines will need to use information from nearby turbines to optimize performance, ensure resiliency when other sensors fail, and adapt to changing local conditions. A key element of achieving a more efficient wind farm is to develop algorithms that ensure reliable, robust, real-time, and efficient operation of wind turbines in a wind farm using local sensor information that is already being collected, such as supervisory control and data acquisition (SCADA) data, local meteorological stations, and nearby radars/sodars/lidars. This article presents a framework for developing a cooperative wind farm that incorporates information from nearby turbines in real time to better align turbines in a wind farm. SCADA data from multiple turbines can be used to make better estimates of the local inflow conditions at each individual turbine. By incorporating measurements from multiple nearby turbines, a more reliable estimate of the wind direction can be obtained at an individual turbine. The consensus-based approach presented in this paper uses information from nearby turbines to estimate wind direction in an iterative way rather than aggregating all the data in a wind farm at once. Results indicate that this estimate of the wind direction can be used to improve the turbine's knowledge of the wind direction. This estimated wind direction signal has implications for potentially decreasing dynamic yaw misalignment, decreasing the amount of time a turbine spends yawing due to a more reliable input to the yaw controller, increasing resiliency to faulty wind-vane measurements, and increasing the potential for wind farm control strategies such as wake steering.
We report that distributed secondary control has been widely used in hierarchical control structures, where multiple distributed generators (DGs) need to coordinate to regulate system voltage and frequency. In these systems, consensus algorithms determine the average of a group of dynamic states (e.g. voltages measured by a group of DGs). To be useful, consensus algorithms must be computationally efficient, stable and accurate. In practice, numerous practical implementation challenges significantly affect the consensus equilibrium. In this paper, we quantify the accuracy deviations of the distributed average observer algorithms proposed in the literature to demonstrate the problems with the state-of-the-art distributed averaging techniques. A novel approach is proposed that achieves accurate average tracking in the presence of time-varying communication delays among agents. In our implementation, time synchronization of all distributed controllers is enabled by a novel software platform, called Resilient Information Architecture Platform for the Smart Grid (RIAPS). The proposed distributed average observer is implemented on hardware controllers and its effectiveness is validated in a controller hardware-in-the-loop testbed.
With the advent of an increasing number of control strategies that seek to optimize wind turbine performance on a farm-level, taking account of individual wind turbine information to achieve wind farm-level objectives has become an increasingly important goal. Methods for controlling wind turbines on an individual and farm level have seen significant development, and an abundance of new implementations for gathering and using data from turbines have created potential for novel control mechanisms which can further optimize the performance and delivery characteristics of a wind farm. A key element of making these wind farms more efficient is to develop reliable algorithms that use local sensor information that is already being collected, such as supervisory control and data acquisition (SCADA) data, local meteorological stations, and nearby radars/sodars/lidars. Making use of information from all wind turbines in a wind farm can enable such approaches as determining the atmospheric conditions across the farm, improving fault-finding, and enabling more efficient overall control of farm-wide optimizations through mechanisms such as wake-steering. However, these approaches typically involve a centralized communications and control center. In order to ensure the resilient operation of the farm, it is necessary to develop an approach which distributes the calculation and communication amongst multiple nodes throughout the farm. In this fashion, a redundant, robust, and secure network can be created, which can tolerate faults in calculation, communication, and even external attacks which seek to disrupt the operation of the wind farm. This paper introduces the use of the Raft Byzantine Fault Tolerance algorithm in the implementation of autonomous control of a wind farm. This implementation will allow for fault tolerance for malfunctioning nodes, sensors, transmitters, and connectors. This approach is equally extensible to account for malicious actors. It will be shown to achieve overall consensus, provided the number of faults/malicious nodes is less than 3$n$+1, where $n$ is the number of turbine cluster faults which may occur, and to be robust in the face of multiple arbitrary faults.
This paper presents a secure reinforcement learning (RL) based control method for unknown linear time-invariant cyber-physical systems (CPSs) that are subjected to compositional attacks such as eavesdropping and covert attack. We consider the attack scenario where the attacker learns about the dynamic model during the exploration phase of the learning conducted by the designer to learn a linear quadratic regulator (LQR), and thereafter, use such information to conduct a covert attack on the dynamic system, which we refer to as doubly learning-based control and attack (DLCA) framework. We propose a dynamic camouflaging based attack-resilient reinforcement learning (ARRL) algorithm which can learn the desired optimal controller for the dynamic system, and at the same time, can inject sufficient misinformation in the estimation of system dynamics by the attacker. The algorithm is accompanied by theoretical guarantees and extensive numerical experiments on a consensus multi-agent system and on a benchmark power grid model.