DC wiring system grounding and ground fault protection issues for central station photovoltaic power plants

The DC wiring system for a photovoltaic power plant presents a number of unique challenges to be overcome by the plant designers. There are a number of different configurations that the grounding of the DC wiring system can take, and the choice will affect the number and type of protective devices required to ensure safety of personnel and protection of equipment. The major grounding and fault protection considerations that must be taken into account when selecting the basic overall circuit configuration are summarized. The inherent advantages and disadvantages of each type of circuit grounding (resistance or solid) along with the personnel safety and equipment protection issues for each of these grounding methods are presented.

Simburger, E. J.↗

An initial comparative assessment of orbital and terrestrial central power systems

Orbital solar power plants, which beam power to earth by microwave, are compared with ground-based solar and conventional baseload power plants. Candidate systems were identified for three types of plants and the selected plant designs were then compared on the basis of economic and social costs. The representative types of plant selected for the comparison are: light water nuclear reactor; turbines using low BTU gas from coal; central receiver with steam turbo-electric conversion and thermal storage; silicon photovoltaic power plant without tracking and including solar concentration and redox battery storage; and silicon photovoltaics.

Caputo, R.↗

Sacremento Municipal Utility District 100-MW sub e photovoltaic plant

A status report on plans for the Sacramento Municipal Utility District (SMUD) 1-MW photovoltaic power plant is presented. DOE, the California Energy Commission, and SMUD will fund the project cooperatively. Emphasis is placed on the details of the government contract/cooperation agreement.

Powell, R. V.↗

PV large systems project

Near term photovoltaic central-station markets are analyzed. Cost effectiveness of photovoltaic plants is determined in terms of reduction of oil consumption. The breakeven photovoltaic system cost vs oil-steam power generation is given. The value of photovoltaic power plants in Southern California and in Los Angelos is given in terms of fuel savings and capacity value. The potential value of third party financing, facilitated by Federal and state tax incentives is analyzed.

Leonard, S. L.↗

Silicon solar photovoltaic power stations

Modular design of components and arrays, cost estimates for modules and support structures, and cost/performance analysis of a central solar photovoltaic power plant are discussed. Costs of collector/reflector arrays are judged the dominant element in the total capital investment. High-concentration solar tracking arrays are recommended as the most economic means for producing solar photovoltaic energy when solar cells costs are high ($500 per kW generated). Capital costs for power conditioning subsystem components are itemized and system busbar energy costs are discussed at length.

Chowaniec, C. R.↗

Lifetime Cost and Performance model for photovoltaic power systems

This paper describes the approach and procedures of the Lifetime Cost and Performance (LCP) model for photovoltaic power systems. The LCP model is designed to evaluate the impact of alternative initial design and recurrent policy decisions on both cost and power output over the lifetime of a photovoltaic power plant. LCP is, therefore, useful to system designers and operators for addressing questions relating to optimal system configuration, installation activities, level of effort and timing of operations/maintenance actions, allowable degradation and replacement options.

Borden, C. S.↗

Automated construction of lightweight, simple, field-erected structures

The feasibility of automation of construction processes which could result in mobile construction robots is examined. The construction of a large photovoltaic power plant with a peak power output of 100 MW is demonstrated. The reasons to automate the construction process, a conventional construction scenario as the reference for evaluation, and a list of potential cost benefits using robots are presented. The technical feasibility of using robots to construct SPS ground stations is addressed.

Leonard, R. S.↗

Power conditioning subsystems for photovoltaic central-station power plants - Technology and performance

Central-Station (CS) Photovoltaic (PV) systems have the potential of economically displacing significant amounts of centrally generated electricity. However, the technical viability and, to some extent, the economic viability of central-station PV generation technology will depend upon the availability of large power conditioners that are efficient, safe, reliable, and economical. This paper is an overview of the technical and cost requirements that must be met to develop economically viable power conditioning subsystems (PCS) for central-station power plants. The paper also examines various already commercially available PCS hardware that may be suitable for use in today's central PV power stations.

Krauthamer, S.↗

Power conditioning subsystems for photovoltaic central-station power plants - State-of-the-art and advanced technology

An overview is given of the technical and near-term cost requirements that must be met to develop economically viable power conditioning subsystems (PCS) for large-scale, central photovoltaic power stations. Various commercially available PCS hardware suitable for use in today's central photovoltaic power stations are also surveyed. Federal and industrial activities in the research and development of advanced PCSs that will contribute to the attainment of fully competitive, large-scale photovoltaic power stations are reviewed. The status of the DOE central station PCS program is discussed.

Bulawka, A.↗

Grounding and fault protection of the SMUD PVI array

If large terrestrial photovoltaic (PV) power plants are to provide an economic source of generation, low-cost, reliable and easily maintainable systems must be developed. In addition, if the system is to be a central station powerplant owned and operated by an electric utility, the design must also be consistent with utility specifications and design standards. The particular solutions developed to address these issues, with regard to grounding and fault protection, for the first phase of the Sacramento Municipal Utility District's (SMUD) 100 mw(ac) PV powerplant are presented. This plant, known as PV1, is nominally rated at 1 mw(ac) and is scheduled to be in operation by the spring of 1984.

Rosen, D.↗

Effects of design on cost of flat-plate solar photovoltaic arrays for terrestrial central station power applications

The paper examines the impact of module and array designs on the balance-of-plant costs for flat-plate terrestrial central station power applications. Consideration is given to the following types of arrays: horizontal, tandem, augmented, tilt adjusted, and E-W tracking. The life-cycle cost of a 20-year plant life serves as the costing criteria for making design and cost tradeoffs. A tailored code of accounts is developed for determining consistent photovoltaic power plant costs and providing credible photovoltaic system cost baselines for flat-plate module and array designs by costing several varying array design approaches.

Tsou, P.↗

Evolution of integrated panel structural design and interfaces for PV power plants

The evolution of integrated photovoltaic (PV) panel design at ARCO Solar is discussed. Historically, framed PV modules of about 1 x 4-ft size were individually mounted in the field on fixed support structures and interconnected electrically with cables to build higher-power arrays. When ARCO Solar saw the opportunity in 1982 to marry its PV modules with state-of-the-art heliostat trackers developed by ARCO Power Systems, it became obvious that mounting individual modules was impractical. For this project, the framed modules were factory-assembled into panels and interconnected with cables before being mounted on the trackers. Since then, ARCO Solar made considerable progress and gained substantial experience in the design and fabrication of large PV panels. Constraints and criteria considered in these design activities included static and dynamic loads; assembly and transportation equipment and logistics, structural and electrical interfaces, and safety and grounding concerns.

Arnett, J. C.↗

Central station applications planning activities and supporting studies

The application of photovoltaic technology in central station (utility) power generation plants is considered. A program of data collection and analysis designed to provide additional information about the subset of the utility market that was identified as the initial target for photovoltaic penetration, the oil-dependent utilities (especially muncipals) of the U.S. Sunbelt, is described along with a series of interviews designed to ascertain utility industry opinions about the National Photovoltaic Program as it relates to central station applications.

Leonard, S. L.↗

Assessment of a satellite power system and six alternative technologies

The satellite power system is assessed in comparison to six alternative technologies. The alternatives are: central-station terrestrial photovoltaic systems, conventional coal-fired power plants, coal-gasification/combined-cycle power plants, light water reactor power plants, liquid-metal fast-breeder reactors, and fusion. The comparison is made regarding issues of cost and performance, health and safety, environmental effects, resources, socio-economic factors, and institutional issues. The criteria for selecting the issues and the alternative technologies are given, and the methodology of the comparison is discussed. Brief descriptions of each of the technologies considered are included.

Wolsko, T.↗

Urban air pollution and solar energy

The design and performance of solar energy systems for many potential applications (industrial/residential heat, electricity generation by solar concentration and photovoltaics) will be critically affected by local insolation conditions. The effects of urban air pollution are considered and reviewed. A study of insolation data for Alhambra, California (9 km south of Pasadena) shows that, during a recent second-stage photochemical smog alert (greater than or equal to 0.35 ppm ozone), the direct-beam insolation at solar noon was reduced by 40%, and the total global by 15%, from clean air values. Similar effects have been observed in Pasadena, and are attributable primarily to air pollution. Effects due to advecting smog have been detected 200 km away, in the Mojave Desert. Preliminary performance and economic simulations of solar thermal and photovoltaic power systems indicate increasing nonlinear sensitivity of life cycle plant cost to reductions in insolation levels due to pollution.

Gammon, R. B.↗

Fuel cell energy storage for Space Station enhancement

Viewgraphs on fuel cell energy storage for space station enhancement are presented. Topics covered include: power profile; solar dynamic power system; photovoltaic battery; space station energy demands; orbiter fuel cell power plant; space station energy storage; fuel cell system modularity; energy storage system development; and survival power supply.

Stedman, J. K.↗

Solar Power System Evaluated for the Human Exploration of Mars

The electric power system is a crucial element of any mission for the human exploration of the Martian surface. The bulk of the power generated will be delivered to crew life support systems, extravehicular activity suits, robotic vehicles, and predeployed in situ resource utilization (ISRU) equipment. In one mission scenario, before the crew departs for Mars, the ISRU plant operates for 435 days producing liquefied methane and oxygen for ascent-stage propellants and water for crew life support. About 200 days after ISRU production is completed, the crew arrives for a 500-day surface stay. In this scenario, the power system must operate for a total of 1130 days (equivalent to 1100 Martian "sols"), providing 400 MW-hr of energy to the ISRU plant and up to 18 kW of daytime user power. A photovoltaic power-generation system with regenerative fuel cell (RFC) energy storage has been under study at the NASA Glenn Research Center at Lewis Field. The conceptual power system is dominated by the 4000- m2 class photovoltaic array that is deployed orthogonally as four tent structures, each approximately 5 m on a side and 100-m long. The structures are composed of composite members deployed by an articulating mast, an inflatable boom, or rover vehicles, and are subsequently anchored to the ground. Array panels consist of thin polymer membranes with thin-film solar cells. The array is divided into eight independent electrical sections with solar cell strings operating at 600 V. Energy storage is provided by regenerative fuel cells based on hydrogen-oxygen proton exchange membrane technology. Hydrogen and oxygen reactants are stored in gaseous form at 3000 psi, and the water produced is stored at 14.7 psi. The fuel cell operating temperature is maintained by a 40-m2 deployable pumped-fluid loop radiator that uses water as the working fluid. The power management and distribution (PMAD) architecture features eight independent, regulated 600-Vdc channels. Power management and distribution power cables use various gauges of copper conductors with ethylene tetrafluoroethylene insulation. To assess power system design options and sizing, we developed a dedicated Fortran code to predict detailed power system performance and estimate system mass. This code also modeled the requisite Mars surface environments: solar insolation, Sun angles, dust storms, dust deposition, and thermal and ultraviolet radiation. Using this code, trade studies were performed to assess performance and mass sensitivities to power system design parameters (photovoltaic array geometry and orientation) and mission parameters (landing date and landing site latitude, terrain slope, and dust storm activity). Mission analysis cases were also run. Power results are shown in this graph for an analysis case with a September 1, 2012, landing date; 18.95 North latitude landing site; two seasonal dusts storms; and tent arrays. To meet user load requirements and the ISRU energy requirement, an 8-metric ton (MT) power system and 4000-m2 photovoltaic array area were required for the assumed advanced CuInS2 thin-film solar cell technology. In this figure, the top curve is the average daytime photovoltaic array power, the middle curve is average daytime user load power, and the bottom curve is nighttime power. At mission day 1, daytime user power exceeds 120 kW before falling off to 80 kW at the end of the mission. Throughout the mission, nighttime user power is set to the nighttime power requirement. In this analysis, "nighttime" is defined as the 13- to 15-hr period when array power output is below the daytime power requirement. During dust storms, power system capability falls off dramatically so that by mission day 900, a daily energy balance cannot be maintained. Under these conditions, the ISRU plant is placed in standby mode, and the regenerative fuel cell energy storage is gradually discharged to meet user loads.

Kerslake, Thomas W.↗

NASA objectives for improved solar power plants

The present work describes the principal goals for the main effort of NASA's research and development of solar photovoltaic cells and arrays. These are (1) to reduce array costs from $270/watt to $90/watt (no change in volume) or to $41/watt (high volume production), (2) raise power density from 66 watts/kg to 110 watts/kg, and (3) minimize dynamic interaction problems. The first two goals can be accomplished by increased cell efficiency, reduced cell thickness, the development of a multiple ribbon growth process, and automation of cell production. To minimize dynamic interaction between array and spacecraft, module flexibility will be increased.

Cohn, E. M.↗