Enhanced pool boiling heat transfer with metal foam tubes in inline tube bundle configuration
Flooded evaporators, commonly known as shell-and-tube heat exchangers, are widely used in large-scale industrial refrigeration and air-conditioning systems due to their high pool boiling heat transfer efficiency. However, their bulky configuration requires a large refrigerant inventory, which poses safety challenges—particularly when employing next-generation A2L refrigerants that are mildly flammable. Here, to address this issue, the development of compact heat exchangers with enhanced heat transfer performance is essential. In this study, a novel metal foam tube design is proposed to augment pool boiling heat transfer. Experiments were conducted at a saturation temperature of 20 °C and across a heat flux range of 7–60 kW m −2 . The tests were conducted for both smooth and metal foam tubes with an inline tube bundle configuration and for a pitch–to–diameter (P/D) ratios of 1.3 and 1.5. Pool boiling performance was evaluated for next-generation hydrofluoroolefin (HFO) refrigerants, R1234yf and R1234ze(E), with R134a serving as the baseline fluid. The results indicate that the heat transfer coefficient (HTC) of R1234yf is comparable to R134a, while R1234ze(E) shows slightly lower performance. Importantly, the metal foam tubes achieved up to a 217% enhancement in HTC compared to smooth tubes.