Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “MVDC”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

A study on dc fault handling of dc-dc converter based on series and parallel connected DABs in MVdc applications

With the increase of direct current (dc) based power generating stations and loads, multi-terminal medium voltage dc (MT-MVdc) systems are gaining popularity. The dc sources and loads are interfaced with the MT-MVdc systems using series and parallel connected dual-active-bridge (SP-DAB). In this paper, the dc fault ride through procedure of SP-DAB meant for MT-MVdc application is analyzed. The need for dc breaker (DCB) under the requirements of MT-MVdc is established through EMT simulation studies. It is shown that an additional dc filter capacitor is essential at the output terminals of the SP-DAB to ride through the dc faults.

Jaldanki, Sreenivasa [ORNL] (ORCID:000000028122322↗

Control Oriented Models for Co-Design: Technical Overview of MT HVDC, MVDC, and Solid State Transformer Building Blocks

The electric power system is shifting toward a power electronics–enabled grid, where converter based “building blocks” (e.g., high voltage direct current (HVDC) links, multi terminal HVDC (MT HVDC) networks, medium voltage DC (MVDC) links, and solid state transformers (SSTs)) provide fast, precise control of power flows, voltage, and frequency. This report develops and applies publicly shareable electromagnetic transient (EMT) and phasor models to examine how such building blocks can be composed and coordinated to support offshore wind integration, inter area transfers, feeder support, and resilience. Section 2 documents a modular multilevel converter (MMC)–based MT HVDC modeling framework and two use cases: a compact WSCC/IEEE 9 bus test system and a 240 bus “mini WECC” case with five offshore wind plants (OWFs). Phasor to EMT transfer, initialization, and sanity checks are summarized, and neutral demonstrations of normal and contingency operation are reported. Section 3 frames the problem of wind plant inertial frequency response (IFR): shaping energy release and recovery to improve nadir while avoiding aerodynamic stall; representative simulations illustrate the issues without disclosing proprietary control. Section 4 develops MVDC concepts through an IEEE 16 bus loop and an Olympic Peninsula case study that compares AC vs. MVDC corridors and shows how feeder headroom can be pooled via DC couplers. Section 5 surveys SST architectures and identifies a gap: scalable, communication free coordination of multiple SSTs for islanded feeder networks. Across the report, novel methods and configurations under separate publication and IP review are not disclosed; only topic oriented, replicable setups and non proprietary results are shown. These models and use cases are intended as foundations for future publications and co design studies on architecture, control, and coordination of PE enabled grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An analysis of parameters affecting ampacity in aircraft bipolar MVDC power cables via coupled electrical, thermal, and computational fluid dynamic modelling

Abstract The next generation of aircraft, including more electric aircraft and all‐electric aircraft (AEA), requires electric power systems with high power density and low system mass specifications. Increasing the voltage of the system to the range of a few kV, medium voltage (MV), is a reasonable approach to achieving high‐power‐density and low‐system‐mass EPSs for aircraft applications. Higher voltages, however, pose many challenges for aviation MV power cables such as arcs and arc tracking, partial discharges (PDs), and thermal management. In this regard, thermal management is more challenging since heat transfer by convection is greatly reduced at wide‐body aircraft's cruising altitudes due to the reduced air pressure. In this paper, a finite element method (FEM) model is developed in COMSOL Multiphysics for an aircraft bipolar MVDC (±5 kV) power cable. Using the model, the maximum permissible cable current at a low pressure of 18.8 kPa (at an altitude of 12.2 km from sea level, the usual cruising altitude for wide‐body aircraft) is calculated. Also, an analytical model is developed based on analytical and proven empirical correlations governing conductive, radiative, and convective heat transfers at the steady state to estimate the ampacity of the bipolar cable system at reduced pressure. It was shown that the proposed analytical model can be used for atmospheric pressure and systems with a larger number of poles, expanding its range of applications. The results of the FEM and analytical models correlate at wide ranges of parameters such as ambient temperature, duct size, distance between the positive and negative pole cables, and the overall diameter of the cables. The influence of horizontal and vertical arrangement of poles is included in the analytical model. The results of this study can be used to design bipolar MVDC power cable systems for the envisaged wide‐body AEA.

Azizi, Arian↗

Considerations for a Medium-Voltage DC Electrolysis Testbed

Here we present the results of a study focused on the feasibility of using Medium Voltage DC (MVDC) power distribution from wind power generation to electrolyzers for hydrogen production. This approach, using hybrid energy generation in a MVDC microgrid, offers many advantages. These include possible improvements in efficiency, reliability and installation cost compared to a more typical state-of-the-art AC distribution configuration. It also eliminates the need for transformers, which have recently been subject to price volatility and availability concerns. This study highlights the practical feasibility of MVDC distribution networks for integrating various energy sources, offering improved efficiency and reduced system complexity compared to conventional AC-based solutions. Future work will focus on enhancing fault protection strategies, scaling the system to larger renewable installations, and conducting hardware implementation at the National Renewable Energy Laboratory's (NREL) Flatirons Campus (FC). In the sections that follow we show that a DC Collection and Distribution System (DC CDS) reduces the losses associated with the electrical conversion / distribution process relative to a state-of-the-art AC approach, improving overall efficiency by 5%. On the qualitative side, reducing the number of conversion stages is likely to improve reliability, reduce capital investment cost, and enable simpler control algorithms to be used, and reduced risk of instabilities and malfunctions.

08 HYDROGEN↗

ARC-SAFE: Accelerated Response semiconducting Contactors and Surge Attenuation For DC Electrical systems (Final Scientific/Technical Report)

The landscape of power transmission and distribution is quickly evolving as more power conversion is done through power electronics and transmitted or distributed at medium voltage direct current (MVDC). As power electronics tend to store less energy and be less resilient to faults than conventional power transformers, a reliable and fast protection against faults is critical to protect power electronics (PE) based infrastructure, especially for medium- and high-voltage applications. This motivates the development of PE based protection circuits to replace slower contemporary electromechanical breakers. In this project a novel PE based MVDC circuit breaker is developed; the new design is comprised of 1) a normally-on leg made of commercially-available, cascaded SiC junction field effect transistors (JFETs) with a passive balancing network, and 2) a normally-off leg based on an optically-triggered gallium nitride (GaN) photoconductive semiconductor switch (PCSS). The normally-off leg was designed to be quickly turned on, to divert current to an auxiliary dissipative circuit, as the normally-on leg is turned off. This approach, using solid-state devices, was selected for a high-performance, fast-switching operation for the DC circuit breaker as compared to approaches that use slower mechanical switches. To be practical, the circuit breaker must have low conduction loss (low Ron) in the normally-on leg and fast coordinated triggering of the normally-off leg to avoid damage from inductive flyback, which could be considerable for long lengths of cable.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Negative Medium-Voltage Direct Current Discharges in Air under Simulated Sub-Atmospheric Pressures for All-Electric Aircraft

The increase in the global temperature due to greenhouse gas emissions is a major concern to the world. To achieve the goal of zero emissions by 2050 in the USA the practical realization of all-electric vehicles, particularly all-electric aircraft (AEA), is important. For the design of electrical power systems (EPSs) in all-electric aircraft, a bipolar medium-voltage direct current (MVDC) system of ±5 kV is being investigated. However, several challenges manifest when using such voltages in a low-pressure environment. One of the main challenges is the partial discharge (PD) behavior of the insulation. It is important to study the PD behavior of the insulation by simulating the aviation environment in the lab. This work aimed to study the partial discharge behavior of air under a negative DC voltage in a needle-to-plane electrode geometry by simulating the aviation pressures in the lab. The partial discharge inception voltage (PDIV) and the breakdown voltage (BDV) show an obvious pressure-dependent variation. Regression analysis was performed to better understand the relationship between the PDIV and pressures. Plots were drawn for the average discharge current at each voltage step until breakdown. This paper’s findings can provide valuable insight into the design of EPS for an AEA. To the best of our knowledge, such a study has not been carried out to date.

air discharge↗

Return on Investment and Sustainability of HVDC Links: Role of Diagnostics, Condition Monitoring, and Material Innovations

HVDC cable systems are becoming an upscaled technical option, compared to AC, because of various factors, including easier interconnections, lower losses, and longer transmission distances. In addition, renewables providing direct DC energy, electrified transportation, and aerospace where DC can be favored because of higher carried specific power all point in the direction of broad future usage of HV and MV DC links. However, contrary to AC, there is little return from on-field installation as regards long-term cable reliability and aging processes. This gap must be covered by intensive research, and contributing to this research is the purpose of this paper. The focus is on key points for HVDC (and MVDC) cable reliability and sustainability, from design modeling able to account for voltage transients and extrinsic aging (such as that caused by partial discharges) to the impact of aging on insulation conductivity (which rules the electric field distribution, thus aging rate). Also, recyclable and nanostructured materials, as well as health conditions, are considered. It is shown how cable design can account for accelerated aging due to voltage transients, as well as for aging-time dependence of conductivity, and how design can be free of extrinsic aging caused by PDs. Algorithms for health condition evaluations, which have additional value in a relatively new technology such as HVDC polymeric cables, are applied to insulation system aging under partial discharges, showing how they can provide an indication of insulation degradation globally or locally (weak spots) and of possible maintenance times. All of this can effectively contribute to reducing the risk of major cable breakdown and damage under operation, which would significantly affect the return on investment (ROI).

Montanari, Gian Carlo (ORCID:0000000320258693)↗

Integrating Data Centers and Grid Technologies at Scale

This presentation focuses on the challenge of integrating AI-driven data centers with the power grid at scale. It examines the AI data center capacity challenge and the role of new Medium Voltage Direct Current (MVDC) and other grid-enhancing technologies in enabling efficient and reliable power delivery. The session will highlight the National Laboratory of the Rockies' ARIES capabilities and planning tools, along with collaborative examples involving Verrus, Compass, and Schneider through the Agora test bed for grid-friendly data center evaluations, and ON. Energy for UPS evaluation. It will showcase the NLR Stable Grid Platform for studying oscillations caused by large-scale data centers, along with planning tools to assess grid security and reliability. Additionally, the presentation covers reconductoring strategies to increase grid capacity and explores innovative data center architectures, including the Advanced DC Architectures with Power-electronic Transformers (ADAPT) platform, which enables testing of complete DC architectures for data centers.

24 POWER TRANSMISSION AND DISTRIBUTION↗