At least 19 records

Electromagnetic compatibility qualification of power electronics for I and C power applications - 152

Electromagnetic Compatibility (EMC) is a growing field in nuclear equipment qualification. Previously confined to I and C equipment residing in control and cable spreading rooms, EMC qualification has expanded to include the inverters and battery chargers which often power safety-related I and C equipment, as well as adjustable speed drives and material handling equipment which could potentially affect sensitive safety-related I and C systems. Because much of the data collected to form the current EMC limits and guidance was collected from low-power equipment in relatively low EMI environments, the same guidance, applied to power electronic equipment, produces overly conservative estimations of the performance needed for EMC. Excessive modification in an attempt to bring the equipment into compliance with EMC limits may not be necessary. This paper provides a brief summary of current applicable EMC guidance and demonstrates a road map for the qualification of larger, more powerful devices which takes into account the entire EMC process, including design, testing, mapping of the installed location, and justification of EMC failures with the end goal being successful, timely, and cost-effective implementation of upgrades and compatibility with existing plant infrastructure (in the intended installation environment), even if equipment exceeds traditional operating envelopes. (authors)

42 ENGINEERING↗

Ensuring electromagnetic compatibility in grid-connected power converters: Challenges, standards, and compliance strategies

In today's rapidly advancing world, electronic devices and systems are fundamental to a wide range of industries, including renewable energy and global telecommunications infrastructure. However, as these devices become more complex and widespread, the risk of electromagnetic interference (EMI) also increases, underscoring the importance of stringent Electromagnetic Compatibility (EMC) requirements for maintaining system integrity. This paper addresses the specific challenges associated with grid-connected power converters (GCPCs), which are critical in integrating renewable energy into existing power grids. It explores the complexities of EMI in the context of GCPCs, particularly given the recent emergence of tailored EMC standards for these systems. The paper also highlights the shortcomings of applying generic or unrelated standards to GCPCs, often leading to inadequate compliance and testing protocols. Through a detailed analysis of existing standards and recent advancements in product-specific EMC requirements, this paper provides a comprehensive overview of the current landscape, offering guidance to stakeholders on navigating the intricate EMC compliance landscape, with a focus on methodologies, testing procedures, and the evolving regulatory environment for GCPCs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Technical Basis for Electromagnetic Compatibility Regulatory Guidance Update

The objective of this report is to serve as the technical basis document for the next, planned revision of this RG that highlights and provides the rationale for the recommended changes. The structure of this document follows and summarizes the several assessment activities undertaken during the course of this project to evaluate new and updated electromagnetic compatibility (EMC) standards, testing methods and limits, and relevant technology developments being incorporated into plant activities that may have EMI/RFI implications, as well as other specific issues, including impacts of electrostatic discharge (ESD) on safety equipment and impacts on increased usage of wireless devices in nuclear power plants.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Task 4 - EMI/RFI Issues Potentially Impacting Electromagnetic Compatibility of I&C Systems (NRCHQ6014D0015)

The U.S. Nuclear Regulatory Commission’s (NRC’s) regulations in Part 50, “Domestic Licensing of Production and Utilization Facilities,” of Title 10 of the Code of Federal Regulations (10 CFR Part 50) state that structures, systems, and components important to safety in a nuclear power plant are to be designed to accommodate the effects of environmental conditions (i.e., remain functional under all postulated service conditions) and that design control measures such as testing are to be used to check the adequacy of design. Regulatory Guide (RG) 1.180 was developed to provide guidance to licensees and applicants on methods acceptable to the NRC staff for complying with the NRC’s regulations on design, installation, and testing practices for addressing the effects of electromagnetic and radio-frequency interference (EMI/RFI) and power surges on safety-related instrumentation and control (I&C) systems. The first revision of RG 1.180 was issued in January 2000 and a second revision was issued in October 2003*. The second revision differed from the first revision in endorsing Military Standard (MIL-STD)-461E and the International Electrotechnical Commission (IEC) Standard (Std) 61000 series of EMI/RFI test methods, extending the guidance to cover signal line testing, incorporating frequency ranges where portable communications devices are experiencing increasing use, and relaxing the operating envelopes (test levels) when experience and confirmatory research warranted. It also offered exemptions from specific test criteria based on technical considerations such as plant conditions and the intended location of the safety-related I&C equipment. Since the last revision, new requirements have been identified, associated RGs have been created and updated, and additional industry guidance has been developed. Additionally, the operational environment has changed with the increase in wireless communication technology for both personal (smartphone) and industrial (remote I&C) purposes. Also, specific concerns and issues with testing methods and methodologies have been identified that must be addressed. Further, most of the standards that serve as the basis for the RG have been revised. Therefore, the NRC’s Office of Regulatory Research has contracted with Oak Ridge National Laboratory (ORNL) to incorporate new information and resolve the identified issues under NRC-HQ-60-14-D-0015, “Update to RG 1.180, Revision 2, Guidelines for Evaluating Electromagnetic and Radio-Frequency Interference in Safety-Related Instrumentation and Control Systems.” The ultimate goal of this project is to provide NRC the technical basis for developing and publishing a new revision of the RG. The focus of Task 4 was for ORNL to identify and address any new or additional EMI/RFI issues that could potentially impact the EMC of I&C systems. More specifically, ORNL was to evaluate the impact of any new issue on safety equipment in their local environments and then determine whether the issues should be included and discussed in the revision to RG 1.180 that is currently under way.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

High-Density Signal Interface Electromagnetic Radiation Prediction for Electromagnetic Compatibility Evaluation

Radiated power calculation approaches for practical scenarios of incomplete high- density interface characterization information and incomplete incident power information are presented. The suggested approaches build upon a method that characterizes power losses through the definition of power loss constant matrices. Potential radiated power estimates include using total power loss information, partial radiated power loss information, worst case analysis, and statistical bounding analysis. A method is also proposed to calculate radiated power when incident power information is not fully known for non-periodic signals at the interface. Incident data signals are modeled from a two-state Markov chain where bit state probabilities are derived. The total spectrum for windowed signals is postulated as the superposition of spectra from individual pulses in a data sequence. Statistical bounding methods are proposed as a basis for the radiated power calculation due to the statistical calculation complexity to find a radiated power probability density function.

42 ENGINEERING↗

A Compact, Single Stage, >1 kV Medium-Voltage Line Impedance Stabilization Network

This paper presents the design of a single-phase, single-stage line impedance stabilization network (LISN) for medium-voltage (MV) applications. More than 1 kV rated widebandgap (WBG) power semiconductor switches are increasingly utilized in new, emerging power electronics energy systems to improve power density and efficiency. However, due to inherently fast-switching speeds, WBG switch modules emit considerable electromagnetic interference (EMI) (e.g., common mode (CM) or differential mode (DM)). State-of-the-art offers standardized LISN solutions to validate and certify the new energy system for electromagnetic compatibility (EMC). However, most are for low voltage applications (i.e., < 1 kV). MV LISNs (i.e., > 1 kV) are rare until recently and literature does not provide sufficient guidelines for designing and characterizing such devices. It has been a critical challenge for many scientists and engineers to reliably certify the emerging MV energy systems (e.g., electric ships and aircraft). This paper addresses such a technology gap. Specifically, a CISPR 16-1-2 compliant 50Ω/50μH LISN with 1.5kV, 75A and 30MHz measurement capability has been proposed. Detailed performance study versus non-linear parasitic parameters variations in MV inductors and capacitors have been done. Based on new understandings, novel techniques to intuitively mitigate unwanted parasitic have been proposed to develop the proposed LISN successfully. Thorough characterization of important LISN parameters are presented and factors influencing them are analyzed. A rigorous analysis, experimental tests, and in-depth comparisons over state-of-the-art have been made to validate the effectiveness. This is done through the state-of-the-art 300kVA MV EMI testbed.

42 ENGINEERING↗

Modeling and analyzing parasitic parameters in high frequency converters

This research focuses on electromagnetic interference (EMI) / electromagnetic compatibility (EMC) design and analysis in power electronics systems. To limit the EMI under the standards, different methods and strategies are investigated. Parasitic parameters of high frequency (HF) transformer are analyzed using a novel analytical method, finite element method (FEM), and experimental measurements for different structures and windings arrangements. Also, the magnetic field, electric field, electric displacement, and electric potential distribution are simulated and analyzed. Moreover, a high voltage system is considered and analyzed to improve the EMC. The EMI propagation paths are analyzed. The EMI noise level of the system is obtained and compared to the IEC61800-3 standard. To improve the EMC, the parasitic parameters of the transformer, as the main path of EMI circulation, are analyzed and optimized to block the propagation. Furthermore, the geometry structure of the HF transformer is optimized to lower the parasitics in the system. Three pareto-optimal techniques are investigated for the optimization. The models and results are verified by 3D-FEM and experimental results for several given scenarios. Furthermore, the EMC modeling and conducted EMI analysis are developed for a system including an AC-DC-DC power supply (rectifier and dual active bridge (DAB) converter). Moreover, the common mode (CM) EMI noise propagation through the system is discussed and the noise sources and effect of components on the noise are analyzed. Additionally, the CM impedance of different parts of the system and the noise levels are discussed. Finally, EMI attenuation techniques were applied to the system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Criteria for Determining the Safety of Wireless Technologies at Nuclear Power Plants

This report provides an initial discussion of the potential impact to safety-related/important-to-safety (SR/ITS) systems by the possible expanded use of wireless technologies. One aspect of this discussion is focused on a review of Regulatory Guide (RG) 1.180 Rev. 2 to determine whether any revisions are necessary to reflect the current state of practice in evaluating and protecting instrumentation and control (I&C) systems and components from electromagnetic interference (EMI) or radiofrequency interference (RFI) on safety and nonsafety I&C. Electromagnetic compatibility (EMC) is the ability of a device or system to function satisfactorily in its electromagnetic (EM) environment, which is achieved by limiting the unintentional generation, propagation, and reception of EM energy that may cause unwanted effects such as EMI. The goal of EMC is to ensure the correct operation of different types of equipment in a common EM environment.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Electromagnetic and thermal properties of three-dimensional printed multilayered nano-carbon/poly(lactic) acid structures

A new type of light-weight material produced by 3D printing consisting of nano-carbon doped polymer layer followed by a dielectric polymer layer is proposed. We performed temperature dependent characterization and measured the electromagnetic (EM) response of the samples in the GHz and THz range. The temperature dependent structural characteristics, crystallization, and melting were observed to be strongly affected by the presence and the number of nano-carbon doped layers in the sandwich structure. The electromagnetic measurements show a great potential of such a type of periodic material for electromagnetic compatibility applications in microwave frequency range. Sandwich structures containing only two nano-carbon layers already become not transparent to the microwaves, giving an electromagnetic interference shielding efficiency at the level of 8–15 dB. A sandwich consisting of one nano-carbon doped and one polymer layer is opaque for THz radiation, because of 80% of absorption. These studies serve as a basis for design and realization of specific optimal geometries of meta-surface type with the 3D printing technique, in order to reach a high level of electromagnetic interference shielding performance for real world EM cloaking and EM ecology applications.

71 CLASSICAL AND QUANTUM MECHANICS, GENERAL PHYSIC↗

Implementation of wireless technologies in nuclear power plants' electromagnetic environment using cognitive radio system - 153

Wireless technologies have increased efficiency in many industrial settings across the world by enabling a mobile workforce and improving communications. Unfortunately, the nuclear power industry has been slow to adopt wireless technology as a result of safety, security, and reliability concerns expressed by regulators and others. A Research and Development (R and D) effort is currently being conducted to address two significant technical concerns for the introduction of wireless technology in nuclear power plants, which are electromagnetic compatibility (EMC) and wireless coexistence. Most equipment in nuclear power plants has never been tested for vulnerability to wireless transmission. As such, the impact of modern wireless devices on nuclear safety and plant reliability is not understood. Existing guidance from the Nuclear Regulatory Commission (NRC) and Electric Power Research Institute (EPRI) rely on the use of exclusion zones to protect plant equipment, which can result in exclusion zones of up to eight feet for some tablet devices rendering them ineffective for the mobile workforce. Another unknown is how different wireless devices will operate in close proximity to one another in the harsh electromagnetic environment of a nuclear power plant. These issues are being addressed through development of a cognitive radio system that has the ability to generate and output multiple wireless signals such as Wi-Fi, Bluetooth, and cellular communications at varying power levels and frequencies. The cognitive radio system is a modular system that can test nuclear plant equipment located in training areas, simulators, and the actual plant environment. In addition to using the system for testing plant equipment to wireless signals and EMC standards, the system can also monitor the radio spectrum for usage in other plant focuses such as cyber security. The R and D work will provide the objective guidance for the nuclear industry in the two areas mentioned and will develop a cognitive radio system for in-plant EMC and coexistence testing. The system will assist in the seamless use of wireless technology in nuclear power plants while greatly reducing the risks wireless signals may introduce. (authors)

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Multipole-Based Cable Braid Electromagnetic Penetration Model: Electric Penetration Case

In this paper, we investigate the electric penetration case of the first principles multipole-based cable braid electromagnetic penetration model reported in the Progress in Electromagnetics Research B 66, 63–89 (2016). We first analyze the case of a 1-D array of wires: this is a problem which is interesting on its own, and we report its modeling based on a multipole-conformal mapping expansion and extension by means of Laplace solutions in bipolar coordinates. We then compare the elastance (inverse of capacitance) results from our first principles cable braid electromagnetic penetration model to that obtained using the multipole-conformal mapping bipolar solution. These results are found in a good agreement up to a radius to half spacing ratio of 0.6, demonstrating a robustness needed for many commercial cables. We then analyze realistic cable implementations without dielectrics and compare the results from our first principles braid electromagnetic penetration model to the semiempirical results reported by Kley in the IEEE Transactions on Electromagnetic Compatibility 35, 1–9 (1993). Finally, although we find results on the same order of magnitude of Kley's results, the full dependence on the actual cable geometry is accounted for only in our proposed multipole model which, in addition, enables us to treat perturbations from those commercial cables measured.

42 ENGINEERING↗

High-performance photonic transformers for DC voltage conversion

Abstract Direct current (DC) converters play an essential role in electronic circuits. Conventional high-efficiency DC voltage converters, especially step-up type, rely on switching operation, where energy is periodically stored within and released from inductors and/or capacitors connected in a variety of circuit topologies. Since these energy storage components, especially inductors, are fundamentally difficult to scale down, miniaturization of switching converters proves challenging. Furthermore, the resulting switching currents produce significant electromagnetic noise. To overcome the limitations of switching converters, photonic transformers, where voltage conversion is achieved through light emission and detection processes, have been demonstrated. However, the demonstrated efficiency is significantly below that of the switching converter. Here we perform a detailed balance analysis and show that with a monolithically integrated design that enables efficient photon transport, the photonic transformer can operate with a near-unity conversion efficiency and high voltage conversion ratio. We validate the theory with a transformer constructed with off-the-shelf discrete components. Our experiment showcases near noiseless operation and a voltage conversion ratio that is significantly higher than obtained in previous photonic transformers. Our findings point to the possibility of a high-performance optical solution to miniaturizing DC power converters and improving the electromagnetic compatibility and quality of electrical power.

42 ENGINEERING↗

Nonlinear interaction of meta-atoms through optical coupling

We propose and experimentally demonstrate a multi-frequency nonlinear coupling mechanism between split-ring resonators. We engineer the coupling between two microwave resonators through optical interaction, whilst suppressing the direct electromagnetic coupling. This allows for a power-dependent interaction between the otherwise independent resonators, opening interesting opportunities to address applications in signal processing, filtering, directional coupling, and electromagnetic compatibility.

71 CLASSICAL AND QUANTUM MECHANICS, GENERAL PHYSIC↗

A source of high-power pulses of elliptically polarized ultrawideband radiation

Here, we describe a source of high-power ultrawideband radiation with elliptical polarization. The source consisting of a monopolar pulse generator, a bipolar pulse former, and a helical antenna placed into a radioparent container may be used in tests for electromagnetic compatibility. In the source, the helical antenna with the number of turns N = 4 is excited with a high-voltage bipolar pulse. Preliminary, we examined helical antennas at a low-voltage source aiming to select an optimal N and to estimate a radiation center position and boundary of a far-field zone. Finally, characteristics of the source in the operating mode at a pulse repetition rate of 100 Hz are presented in the paper as well. Energy efficiency of the antenna is 0.75 at the axial ratio equal to 1.3. The effective potential of radiation of the source at the voltage amplitudes of the bipolar pulse generator equal to -175/+200 kV reaches 280 kV.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Level monitoring system with pulsating sensor—Application to online level monitoring of dashpots in a fast breeder reactor

An innovative continuous type liquid level monitoring system constructed by using a new class of sensor, viz., pulsating sensor, is presented. This device is of industrial grade and it is exclusively used for level monitoring of any non conducting liquid. This instrument of unique design is suitable for high resolution online monitoring of oil level in dashpots of a sodium-cooled fast breeder reactor. The sensing probe is of capacitance type robust probe consisting of a number of rectangular mirror polished stainless steel (SS-304) plates separated with uniform gaps. The performance of this novel instrument has been thoroughly investigated. The precision, sensitivity, response time, and the lowest detection limit in measurement using this device are <0.01 mm, ∼100 Hz/mm, ∼1 s, and ∼0.03 mm, respectively. The influence of temperature on liquid level is studied and the temperature compensation is provided in the instrument. The instrument qualified all recommended tests, such as environmental, electromagnetic interference and electromagnetic compatibility, and seismic tests prior to its deployment in nuclear reactor. With the evolution of this level measurement approach, it is possible to provide dashpot oil level sensors in fast breeder reactor for the first time for continuous measurement of oil level in dashpots of Control and Safety Rod Drive Mechanism during reactor operation.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗