Low-GWP Refrigerant Evaluation in AC Systems for High Ambient Temperature Applications - Design and Simulation Practice to Identify Charge Reduction Opportunities for Residential AC/HP Units
Based on three 5-ton, single-speed heat pumps (HPs), using R-410A, which use the same compressor, indoor blower and outdoor fan, the DOE/ORNL Heat Pump Design Model was used to conduct comparative modelling study. Regarding charge reduction opportunities, in general, we recommend: 1. Downsizing the outdoor condenser will reduce the required system charge, i.e. using smaller tube diameters or fewer tubes; reducing the evaporator inner volume is less important; to offset the reduced condenser tube side surface area, one can increase the air side surface area (fin density) or condenser air flow rate via using a more efficient fan. 2. microchannel heat exchangers are most effective in reducing the required charge, by up to 60% in the condenser and evaporator. To develop low charge systems, one should at least use a microchannel heat exchanger as the outdoor condenser. 3. TXV systems are less sensitive to charge reduction. For the drop-in application, one can decrease the charge to minimize the liquid section in the condenser, at the expense of minor performance degradation; for example, when reducing the system charge by 15% (decrease the subcooling degree to 2R), the simulation results prove that the decrease is less than 3% in the EER and less than 6% in the capacity.