Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “grid-forming”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 163 records · Page 9

SVM-Based Synchronized Fault Detection for 100% Renewable Microgrids

Traditional protection schemes face significant challenges when applied to microgrids with high penetrations of renewables with inverter-based resources (IBRs). The proliferation of advanced sensing and communication technologies has generated copious data, offering an opportunity to overcome these limitations using data-driven machine learning approaches. This work proposes a novel approach based on a support vector machine (SVM) for detecting faults within a 100% renewable microgrid. The approach encompasses a systematic offline training stage for the development of a linear SVM-based fault detection algorithm. This process covers offline data collection from the microgrid under study, the extraction of features such as positive- and negative-sequence components and the total harmonic distortion of the voltage and current measurements of the relays, and the design of the linear SVM-based classifier. During the online implementation, however, different classifiers can exhibit asynchronicity in detecting the fault inception at different subcycle-to-cycle period-level delays. To circumvent this asynchronicity issue, a separate algorithm is developed for each relay to estimate the fault inception time as close to the real fault time. The performance of the proposed SVM-based synchronized fault detection method is evaluated using online time-domain simulation studies on a microgrid test system. The results corroborate the reliability of the fault detection scheme when tested under various fault cases (fault types, locations, and impedances) and non-fault cases during both grid-tied and islanded operation modes.

100% microgrid↗

A Power-Hardware-in-the-Loop (PHIL) Evaluation of Service Restoration With Networked Microgrids

This paper describes the power-hardware-in-the- loop (PHIL) evaluation of the feasibility of service restoration solutions determined by the PowerModelsONM.jl tool. This tool incorporates microgrids and the networking of microgrids into its determination of an optimal service restoration solution. The paper presents PHIL simulation results for a case study based on a real distribution feeder with multiple microgrids, showcas- ing the effectiveness of networked microgrids in aiding system restoration after an outage. The study leverages high-fidelity, real- time electromagnetic transient models to ensure accuracy in the simulation results. This work is the final output from the Resilient Operation of Networked Microgrids (RONM) project funded by the U.S. Department of Energy Office of Electricity Microgrid Program and led by Los Alamos National Laboratory. RONM focused on the application of PowerModelsONM.jl to enhance the resilience of distribution systems.

fault location isolation and service restoration (↗

Design of Zone-Based Hierarchical Protection System for 100% Renewable Microgrids

Design of a reliable and secure protection system for a 100% renewable microgrid with only inverter-based resources (IBRs), is quite challenging. Most of the existing protection schemes in the state-of-the-art are suitable for microgrids with mixed-type of distributed energy resources (DERs) that covers both rotating machine-based DERs as well as IBR-based DERs, where the fault current level is moderately high. Due to drastic reduction in fault current level based on mode of operation and the variation of the low fault current level based on the operating level of the IBRs, the existing protection schemes face critical challenges, in case of a 100% renewable microgrid. This article proposes a zone-based hierarchical protection scheme that partitions a microgrid into various zones-of-protection and assigns speed-based hierarchical protection schemes in order to address the fundamental challenges of such microgrids. The performance of the proposed scheme is evaluated using time-domain simulation study on a microgrid test system. The results corroborates that the proposed hierarchical zone-based protection scheme exhibits enhanced reliability, security and dependability while tested with various fault cases (fault types, locations, and impedances), and non-fault cases during both grid-tied and islanded mode.

grid-forming inverter↗

Distribution System Blackstart and Restoration Using DERs and Dynamically Formed Microgrids

Extreme weather events have led to long-duration outages in the distribution system (DS), necessitating novel approaches to blackstart and restore the system. Existing blackstart solutions utilize blackstart units to establish multiple microgrids (MGs), sequentially energize non-blackstart units, and restore loads. However, these approaches often result in isolated MGs. In DERs-aided blackstart, the continuous operation of these MGs is limited by the finite energy capacity of commonly used blackstart units like battery energy storage (BES)-based gridforming inverters (GFMIs). To address this issue, this article proposes a holistic blackstart and restoration framework that incorporates synchronization between dynamic MGs and the entire DS with the transmission grid (TG). To support synchronization, we leveraged virtual synchronous generator-based control for GFMIs to estimate their frequency response to load pick-up events using only initial/final quasi-steady-state points. Subsequently, a synchronization switching condition is developed to model synchronizing switches, aligning them seamlessly with a linearized branch flow problem. Finally, we designed a bottomup blackstart and restoration framework that considers the switching structure of the DS, energizing/synchronizing switches, DERs with grid-following inverters, and BES-based GFMIs with frequency security constraints. In conclusion, the proposed framework is validated in IEEE-123-bus system, considering cases with two and four GFMIs under various TG recovery instants.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Orchestrating the Restoration of Wind-Dominant Grids from Blackouts (Final Report of Award No. DE-SC0021410)

This is the final report of Award No. DE-SC0021410: “Orchestrating the Restoration of Wind-Dominant Grids from Blackouts.” It: (1) summarizes the technical/scientific accomplishments, (2) lists the publications containing scientific details of the accomplishments, (3) reports several dissemination activities, (4) names new research grants as consequence of this project, (5) lists the project team funded by the project, and (6) concludes the project.

17 WIND ENERGY↗

Optimal Operation and Impact Assessment of Distributed Wind for Improving Efficiency and Resilience of Rural Electricity Systems

This project aims to empower rural utilities by developing advanced optimization models and algorithms for effectively integrating distributed wind energy alongside battery storage and other distributed energy resources (DERs). The primary objectives are to reduce peak demand, ensure reliable emergency power supply, and regulate voltage and frequency. To address operational challenges, the project introduces innovative mitigation strategies and ultrafast assessment frameworks to evaluate the impacts of distributed wind and DERs on rural grids, offering actionable solutions to potential issues. Economic viability is assessed through cost-benefit analysis using real rural utility data, ensuring the practical application of the project outcomes.

17 WIND ENERGY↗

Introduction to Microgrids

A microgrid is simply a typical power system that has distributed energy resources (DERs), like small diesel generators, with loads in the network. The resiliency offered by microgrids to retain service during system events makes them a suitable support for the electric grid during natural disasters. One key factor that differentiates microgrids from a typical distribution grid is its ability to disconnect itself in the event of a blackout and sustain its loads through DERs. Microgrid systems will reconnect to the main grid when the grid comes back up. The resiliency offered by microgrids to retain service during system events makes them a suitable support for the electric grid during natural disasters. This presentation discusses the typical key steps involved in microgrid planning, installation, operation in a interoperable and interconnectable fashion.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Hardware-in-the-Loop Using Electromagnetic Transient Simulation

Digital real time simulators have the capability to run electromagnetic transient simulations in real time. This capability allows users to leverage the hardware-software combination to evaluate controller performance, protection device performance, and power device performance. This has helped many field deployment projects to be successful and be cost-effective. In this talk, we will present current state-of-art, and future of real time electromagnetic transient simulation and its impacts on field deployment.

08 HYDROGEN↗

Study of the Protection Improvements for a Weak Grid Area With High Inverter-Based Resources (IBRs)

This project designs enhanced protection scheme for the real-world weak grid area with a high penetration of IBRs. As the existing protection schemes are originally designed for traditional synchronous machines, we first evaluate if the protection scheme will continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with IBR original equipment manufacturer black-box models is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. Enhanced protection is designed to address the challenge of lack of negative sequence current from IBRs, including increased restraining factors a2 and k2 to block 32Q or using V instead QV ORDER for ground faults, enhanced mho distance element with voltage and phase angle supervision for L-L faults. The efficacy of enhanced protection logic is validated and proven to work reliably. Additionally, IEEE Std. 2800-2022 negative sequence current compliant GFL and GFM IBRs from another vendor are tested and proven to work reliably without need for enhanced logic. Therefore, this work provides valuable decision-making for utilities facing protection system challenges due to IBRs, either designing enhanced protection scheme or requesting their IBRs being IEEE Std. 2800-2022 compliant to produce regulated negative sequence current for protection relay to make correct decision.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Shunt-Connected FACTS and Synchronous Condensers

In recent years, the electric-transmission system has undergone a significant transformation marked by a greater integration of renewable-energy sources like wind and solar, the phasing out of thermal generation plants, and a concerted effort towards electrifying energy consumption. To keep pace with the integration of renewable-energy sources and the escalating demands of industries and households, it is imperative to expand and modernize the existing power infrastructure. These upgrades are essential to maintain grid stability, enhance power delivery, and boost overall efficiency of the system. However, challenges have emerged with the growing complexity of power grids, particularly in the realms of voltage control, transient stability, and power-quality management.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Solar Energy CommUnity Resiliency (Final Technical Report)

Final Technical Report for DE-EE0009336 Solar Energy CommUnity Resiliency (SECURE) The Solar Energy CommUnity Resiliency (SECURE) project aimed to support development of resilient community microgrids to improve grid reliability and maintain power during times of crisis. The SECURE project approached this objective by addressing key technical and business challenges impeding implementation of resilient community microgrids. To achieve the goals of this project, we pursued several specific objectives through comprehensive design and requirements development.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Systematic Framework for Tuning Open-Source Multifunctional IBR Models To Emulate OEM Black-Box Fault Dynamics

This paper presents a systematic framework to tune a generic IBR EMT model to match with an OEM provided balckbox inverter model based on the fault current responses. The key learnings and findings are summarized as follows: The tunable key parameters include inner control loops and current limiters to align the fault current magnitude, sequence content, and phase trajectories with the OEM models across diverse fault type and locations. The tuned model's fidelity is validated through comparative analysis with an OEM blackbox model, assessing both the fault current response and the responses of multiple relay elements. The results demonstrate the tuned generic model can trigger relay decision logic that is identical or near identical to that of the OEM model, thus generating very good match model for fault studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Fuel Cell Inverter Dataset

This data set contains the three phase AC voltage, three phase AC current, DC voltage and DC current. These data sets were captured during fuel cell inverter operation in grid-connected dispatch, islanded load changes, transition from grid-connected mode to islanded mode and vice-versa.

25 ENERGY STORAGE↗