Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “electromagnetic transient simulation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 163 records · Page 9

A Participation Factor-Based Approach for Defining the EMT Model Boundary for Power System Simulations with Inverter-Based Resources

The increasing penetration of inverter-based resources (IBRs) introduces new challenges to power system simulations, particularly with the emergence of fast electromagnetic transient (EMT) dynamics and sub-synchronous oscillations (SSO) that require time-consuming EMT simulations. To reduce the time cost for simulating a large-scale power grid with IBRs, this paper proposes a novel participation factor-based approach for defining a critical zone for detailed EMT modeling and simulations, which includes the IBRs, synchronous generators, and the network components participating significantly in simulated contingencies. Both model-based and response-based methods are introduced for the estimation of participation factors (PFs). The case study on the 240-bus Western Electricity Coordinating Council (WECC) system demonstrates that the EMT zone determined by the proposed approach can effectively capture power system dynamics involving IBRs.

EMT simulation↗

High-Performance Computing Based EMT Simulation of Large PV or Hybrid PV Plants

Faults in the transmission grid have led to reduced power generation from power electronics resources that are typically not connected to the faulted transmission line. In many of the cases, partial loss of power is observed within the power electronics resources like large photovoltaic (PV) power plants. This phenomena is not captured in existing simulation models and/or simulators. High-fidelity switched system electromagnetic transient (EMT) dynamic models of PV power plants can improve the fidelity of models available for accurate analysis of the impact on PV plants during simulation of faults. However, these models are extremely computationally expensive and take a long time to simulate. Long simulation times limit the ability to use these models as larger regions are studied in EMT simulations with more power electronics resources. In this paper, numerical simulation algorithms are combined with high-performance computing techniques and applied to the high-fidelity switched system EMT model of PV plants. Using these techniques, a speed-up of up to 58x is obtained, while preserving the accuracy of the simulation at greater than 98%.

Debnath, Suman↗

Using Energy Storage-Based Grid Forming Inverters for Operational Reserve in Hybrid Diesel Microgrids

In remote arctic communities, where access to a bulk electrical grid interconnection is not available, the implementation of islanded microgrids has been the most viable way to produce and distribute electricity services to their inhabitants. Historically, these islanded grids have relied primarily on diesel generators or hydropower resources to supply the baseload. However, this practice can result in increased expense due to the high costs associated with fuel transportation and the significant amounts of on-site storage necessary when fuel transportation is unavailable during winter months. In order to mitigate this problem, arctic microgrids have started to transition to a hybrid-source operational mode by incorporating renewable energy sources that are inherently variable in nature, such as wind or solar. Due to their highly stochastic behavior, these hybrid-source islanded microgrids can pose potential issues related to power quality due to introduction of rapid net load fluctuations and inability of diesel generators to respond rapidly. In addition, non-firm stochastic sources can require significant idling diesel generator resources to serve as spinning reserves, which is inefficient and wasteful. This work studies the problems that may arise in the transient dynamics of a real-world hybrid diesel microgrid when subjected to a loss of wind generation. Moreover, this work proposes a transition from a diesel spinning reserve to a battery energy-storage system (BESS) operating reserve scheme. The study of the proposed transition is important in establishing the fundamental implication of transient dynamics and the potential benefits of integrating a BESS as a spinning reserve in terms of stability, frequency nadir, and transient voltage deviation. The methods to investigate and validate the transient dynamics relied on both electromagnetic simulation models of GFMIs and a commercially available GFMI in an experimental power hardware-in-the-loop setup. The simulation results showed that the proposed operating reserve scheme improves the power quality of the system in terms of voltage deviation and frequency nadir when the microgrid is subjected to a loss of wind generation scenario. Depending on the simulation cases, adding a GFMI reduced the frequency nadir between 65.3% and 86.7%. Moreover, the reductions in the voltage deviations improved between 3.6% and 23.0%. From these results it can be concluded that the integration of a GFMI can reduce the frequency nadir in a hybrid diesel microgrid, and in turn, reduce diesel consumption, which improves system reliability while reducing fuel expenses. Furthermore, the novelty of this work relies on the fact that the offline simulation results were validated using a power hardware-in-the-loop platform that incorporated a 100 kVA commercially available GFMI as the device under test.

Hernandez-Alvidrez, Javier↗

Quantifying System Strength From Grid-Forming Resources Using Frequency Scan Approach: Preprint

Current industry practices for quantifying the system strength contribution from grid-forming (GFM) resources to ensure stability of power systems dominated by inverter-based resources (IBRs) are primarily based on iterative electromagnetic transient (EMT) time-domain simulation studies. While feasible, these approaches are resource-intensive, lack scalability and intuition, and might not evaluate the system strength contribution over the entire frequency range of interest. This paper introduces a novel, frequency-domain approach to quantify system strength support provided by a GFM resource using frequency scans. The proposed method uses transfer functions from the grid voltage magnitude (V) and phase (?), respectively, to the reactive (Q) and active power (P) output of a GFM resource for quantifying its contribution to system strength. These transfer functions provide a direct measure of the ability of a GFM resource to behave as a stiff voltage source behind a reactance over a specified frequency range, enabling robust quantification of its system strength contribution. The key innovation of this work is the development of a frequency domain system strength metric called the dynamic short-circuit ratio (dSCR) that is suitable for IBR-dominated power systems and is directly related with the familiar short circuit ratio (SCR) metric. The new metric, dSCR, enables the assessment of system strength contributions from both synchronous machines and converter-based GFM resources using a unified benchmark, which is not possible with the traditional SCR metric. The paper also demonstrates how impedance scans could identify if an unstable condition observed during weak grid conditions is a result of the lack active or reactive power support or both. By leveraging the proposed frequency-domain dSCR metric for quantifying system strength contribution from GFM IBRs, the paper demonstrates targeted mitigation strategies for weak grid instabilities without resorting to repeated, time-consuming time-domain simulations. The result is a scalable and efficient approach to remediate stability challenges in power systems with high shares of IBRs and accelerating the integration of GFM technologies for system strength support in power systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Severe Temperature Impact Study on Ferrite Electromagnetic Shielding for Wireless Electric Vehicle Charging

Wireless charging of an electric vehicle (EV) is an emerging technology that enables noncontact charging, which has advantages in terms of convenience and flexibility. However, the embedded charging pads under and on the ground expose the charging coils, ferrite shielding, and related components to a potentially severe external environment. To study the electromagnetic shielding performance under such extreme temperature conditions, ferrite shielding material's permeability characteristics are tested under temperatures as low as -50°C to as high as 240°C. Referring to the official recorded lowest and highest temperature of the United States, in this paper, it is assumed that the operation temperature ranges from -50°C to 57°C as the coldest winter and hottest summer environment for WPT application. Electromagnetic performance, shielding, and associated stray magnetic emissions are simulated by using three-dimensional (3D) transient simulations to study the impact of low and high temperature on electromagnetic shielding performance. Based on ferrite testing data, from -50°C low temperature to 57°C high temperature, the ferrite's relative permeability ranges from 2550 to 3727. The simulation study indicates that there won't be significant impact on the EM shielding performance for WPT operated under those severe environment temperature conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Positive-Sequence Modeling of Droop-Controlled Grid-Forming Inverters for Transient Stability Simulation of Transmission Systems

Here, this paper describes a positive-sequence model to represent two widely reported droop-controlled grid-forming inverters for bulk power systems simulation study. Methods of how to develop the equivalent voltage source behind impedance to represent inverters with and without inner control loops, modeling of P-f and Q-V droop controls, active and reactive power limiting modeling, and modeling of fault current limiting controls are described in detail. The model is implemented in commercially available positive-sequence simulation tools and compared with detailed electromagnetic transient models in both a single-grid-forming-inverter infinite-bus system and a modified IEEE 39-bus system. Finally, the model is tested on the full US Western Electricity Coordinating Council (WECC) system. Study results show that the model has a good level of accuracy compared to the detailed EMT models, and at the same time also achieves a high computational efficiency, which is suitable for the bulk power system simulation study.

42 ENGINEERING↗

MO-AB-BRA-08: A Modular Multi-Source X-Ray Tube for Novel Computed Tomography Applications

Purpose: To develop and build a practical implementation of an x-ray line source for the rapidly increasing number of multi-source imaging applications in CT. Methods: An innovative x-ray tube was designed using CST Particle Studio, ANSYS, and SolidWorks. A slowly varying magnetic field is synchronized with microsecond gating of multiple thermionic electron sources. Electrostatic simulations were run to optimize the geometry of the optics and prevent electrode arcing. Magnetostatic simulations were used for beam deflection studies and solenoid design. Particle beam trajectories were explored with an emphasis on focusing, acceleration, deflection, and space charge effects. Thermal constraints were analyzed for both transient and steady-state regimes. Electromagnetic simulations informed the design of a prototype unit under construction. Results: Particle tracking simulations for a benchtop system demonstrate that three 80 keV electron beams are able to be finely controlled and laterally swept a combined distance of 15 cm over a stationary target with an oscillating magnetic field in the hundreds of gauss. The beams are pulsed according to scanning sequences developed for implementation in a mock stationary CT scanner capable of a 30 ms temporal resolution. Beam spot diameters are approximately 1 mm for 30 mA beams and the stationary target stays well within thermal limits. The relevant hardware and control circuits were developed for incorporation into a physical prototype. Conclusion: A new multi-source x-ray tube was designed in a modular form factor to push the barriers of high-speed CT and spur growth in emerging imaging applications. This technology can be used as the basis for a stationary high-speed CT scanner, a system for generating a virtual fan-beam for dose reduction, or for reducing scatter radiation in cone-beam CT utilizing a tetrahedron beam CT geometry. A 2.4 kW benchtop system is currently being built to show proof of concept for the tube. Support for this research was provided by the University of Wisconsin Madison, Office of the Vice Chancellor for Research and Graduate Education with funding from the Wisconsin Alumni Research Foundation.

60 APPLIED LIFE SCIENCES↗

EMT Simulation of Large PV Plant & Power Grid for Disturbance Analysis

One of the challenges faced during the analysis of various disturbances with inverter-based resources is the ability to replicate the same disturbance in simulations. The main issue arises from lack of electromagnetic transient (EMT) models and adequate fidelity of models. To overcome this problem, in this paper, EMT simulation of power grid and one of the affected photovoltaic (PV) plants is performed to replicate the observations during the Angeles Forest disturbance in 2018. The processes to (i) develop the EMT model of the power grid from traditional transient stability (TS) data, and (ii) develop high-fidelity EMT model of PV plant from data collected on a PV plant are described in the paper. The requirements in the high-fidelity EMT model of the PV plant are also described. Finally, simulation of the Angeles Forest disturbance is performed and similar simulation results (as compared to the observed disturbances) are observed.

Debnath, Suman↗

A Power-Hardware-in-the-Loop (PHIL) Evaluation of Service Restoration With Networked Microgrids

This paper describes the power-hardware-in-the- loop (PHIL) evaluation of the feasibility of service restoration solutions determined by the PowerModelsONM.jl tool. This tool incorporates microgrids and the networking of microgrids into its determination of an optimal service restoration solution. The paper presents PHIL simulation results for a case study based on a real distribution feeder with multiple microgrids, showcas- ing the effectiveness of networked microgrids in aiding system restoration after an outage. The study leverages high-fidelity, real- time electromagnetic transient models to ensure accuracy in the simulation results. This work is the final output from the Resilient Operation of Networked Microgrids (RONM) project funded by the U.S. Department of Energy Office of Electricity Microgrid Program and led by Los Alamos National Laboratory. RONM focused on the application of PowerModelsONM.jl to enhance the resilience of distribution systems.

fault location isolation and service restoration (↗

Simulation of Fast-Rise Transients in a Large-Power Transformer Winding

A high-altitude electromagnetic pulse (HEMP) may pose a significant threat to the electrical power grid. In this context, the present study considers here the potential impact of the HEMP early-time component (E1) on the winding of a typical transmission power line transformer. A time-domain, fully electromagnetic, three-dimensional, finite-element model was used to simulate the propagation of an E1-induced voltage surge into the transformer winding. The analysis is focused on the first few turns of the winding, the ones that are impacted by the largest electric field resulting from the applied pulse. The model follows the transient dynamics, while the pulse is traveling along the conductor, and the electric field is established across the insulation gaps through capacitive coupling. The simulations also considered the effect of an electrically floating, “shield” winding conductor. This is used as a countermeasure to improve the voltage uniformity across the winding during fast-rise transients. In this case, the propagation of the E1-induced pulse is compared with that from a slower rising, lightning standard waveform. The simulation results show that the presence of the shield conductor can effectively reduce the peak electric field between winding turns, in the presence of either E1 or lightning waveforms.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Coupled Transient Finite Element Simulation of Quench in Jefferson Lab's 11 GeV Super High Momentum Spectrometer Superconducting Magnets

This paper presents coupled transient thermal and electromagnetic finite element analysis of quench in the Q2, Q3, and dipole superconducting magnets using Vector Fields Quench code. Detailed temperature distribution within coils and aluminum force collars were computed at each time step. Both normal (quench with dump resistor) and worst-case (quench without dump resistor) scenarios were simulated to investigate the maximum temperatures. Two simulation methods were utilized, and their algorithms, implementation, advantages, and disadvantages are discussed. The first method simulated the coil using nonlinear transient thermal analysis directly linked with the transient circuit analysis. It was faster because only the coil was meshed and no eddy current was modeled. The second method simulated the whole magnet including the coil, the force collar, and the iron yoke. It coupled thermal analysis with transient electromagnetic field analysis which modeled electromagnetic fields including eddy currents within the force collar. Since eddy currents and temperature in the force collars were calculated in various configurations, segmentation of the force collars was optimized under the condition of fast discharge.

75 CONDENSED MATTER PHYSICS, SUPERCONDUCTIVITY AND↗

Open Source Modeling for Power Systems Dynamics

Time-domain simulations for power systems (both phasor and electromagnetic transients) are mostly dominated by commercial tools, such as PSS/E or PSCAD. However, with the increasing penetration of inverter-based resources and changes in model paradigm, new open-source tools are looking into become a possible alternative for a range of stakeholders. In this presentation we will focus on how to improve communication with industry and other stakeholders to properly showcase the value of open source simulators. Participants will identify current barriers facing the adoption of open-source time-domain tools, and will discuss how to improve the bench-marking processes across different tools, while maintaining software modularity to include new features and models as new challenges continue to happen in energy systems.

ENERGY PLANNING, POLICY, AND ECONOMY,MATHEMATICS A↗

Model Identification of Inverter Nonlinear Control Dynamics

To comprehensively predict in silico potential disruptive dynamic performance of converter-based generation and develop solutions, the application of electromagnetic transient programs is desirable. However, these accurate simulations highly depend on inverter models of actual field implementations, which are often unavailable because they are proprietary. To address this problem, we propose a time-domain model identification method that can be used to determine the control models of inverters in continuous time from multiple experimental studies. The focus is on identifying the dynamic representation of controls because they dominate the dynamic response of renewable assets. To illustrate the applicability of the technique, we consider a subclass of inverter controllers for autonomous grid applications that rely on nonlinear oscillators.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An Asynchronous Real-time Co-simulation Platform for Modeling Interaction between Microgrids and Power Distribution Systems

This paper presents the modeling framework of an asynchronous, real-time co-simulation platform for modeling the interactions between microgrids and power distribution systems. Components of each microgrid are simulated on the OPAL-RT eMEGASIM platform so that electromagnetic transients of the inverter units are modeled at a time step of 100 microseconds. The 3-phase unbalanced distribution feeder that microgrids are connected to is simulated by using the OPAL-RT ePHASORSIM so that load transients, capacitor switching, and tap-changing events can be modeled. A MATLAB-based microgrid controller will interface controllable microgrid components through the Modbus communication. This co-simulation framework allows different microgrid controller logic to be developed and tested on a hardware-in-the-loop testbed considering both the inverter-level transient and the dynamic response of loads and utility equipment. Because the controller communicates with controllable devices via actual communication links, the impact of communication errors, delays, or denial-of-service can also be properly quantified.

Xie, Fuhong↗

FD-TD numerical simulation of an entire lightning strike on the C160 aircraft

Experimental transient electromagnetic field measurements were performed on a Transall C160 aircraft during in-flight lightning strikes. The data allow a test of the predictive capabilities of a three dimensional time domain finite difference code (ALICE) developed at ONERA in order to investigate lightning-aircraft interactions. Using a transfer function technique in the 3D code, it is shown that a bi-leader attached to an aircraft can be simulated by a linear model, and so the electromagnetic fields can be calculated anywhere on the vehicle. Comparison of experimental and numerical results were made for several lightning strikes. Skin current density and electromagnetic field distributions are discussed in detail.

Alliot, J. C.↗

Black-Starting Microgrids Using Inverter-Based Distributed Energy Resources

Recent trends in power systems show increasing deployment of inverter-based distributed energy resources (DERs) at the distribution level. Efforts have also been made to use inverter-based DERs for system restoration of critical sections of distribution feeders. In the past few years, there has been active consideration of using local grid-forming (GFM) DERs, which can form their own voltage and frequency, to black-start microgrids instead of waiting for the bulk system for supply restoration. However, using current-limited inverter-based DERs for black-start operations with high inrush currents can pose some technical challenges. This paper presents detailed electromagnetic transient studies on a digital real-time simulator to assess the operational feasibility of using local inverter-based GFM DERs for microgrid black-start operations as a bottom-up approach instead of a top-down approach where the substation is used to restore critical sections of the feeder. The paper presents key modeling details for distribution system components for studying GFM DER-based microgrid black-start operations. The paper presents simulation results comparing different black-start approaches using GFM DERs for two test systems: i) a simple test microgrid and ii) a real-world utility microgrid currently being designed and deployed by Holy Cross Energy in Colorado.

black start↗

Estimation of Participation Factors Using the Synchrosqueezed Wavelet Transform

This paper proposes a data-driven approach for estimating participation factors for a power system using only simulation results on selected disturbances. The approach is purely response-based and does not need a linearized system model for eigen-analysis, which makes it applicable to systems whose detailed, complete mathematical models are not available. Considering the unavoidable nonlinearity as exhibited in the transient period of a system response, the Synchrosqueezed Wavelet Transform is applied to simulated responses for modal analysis to obtain participation factors. Based on simulations of Kundur's two-area system using both the electromagnetic transient model and phasor model, the participation factors estimated by the proposed approach are compared with two other signal processing tools, the Prony analysis and continuous wavelet transform, and are also benchmarked with conventional model-based participation factors.

participation factor↗

High-Frequency Signature-Based Fault Detection for Future MV Distribution Grids: Preprint

Increased deployment of Distributed Energy Resources (DERs) and microgrids are significantly changing the operation of distribution grid. Increasing penetration of power electronics based DERs also raise several operational problems such as protection coordination issues, voltage raise, recloser synchronization, stability, and frequency control. Legacy systems are designed for unidirectional power flow. Bidirectional power flows, and varying short circuit levels are some of the major challenges in implementing these legacy protection schemes for future power grid with high penetration of power electronics based DERs. Inverter based DER’s can contribute to a maximum of 2 p.u. fault current. Interconnection standards might require even lower fault current contribution. If these protection related challenges are not addressed, it will result in limiting the penetration of DERs in distribution feeders. In this paper, the feasibility of high frequency signature generated by transients is evaluated to identify and locate faults in a distribution system. The paper will discuss the need for an accurate line modeling approach to accurately capture the high frequency signatures. These high frequency signatures are naturally occurring electromagnetic transients for events such as switching events in the network, faults events, etc. This is different than that implemented in transmission systems as the proposed approach utilizes advanced signal processing techniques to retrieve valuable information from the high frequency signatures generated during faults and does not just rely on time delay measurements between reflections of the high frequency signals. In the full paper, information of a modified IEEE distribution feeder test system to accurately model the high frequency signatures will be provided. The distribution lines will be modeled using universal line modeling (ULM) technique in an electromagnetic transients program (EMTP) modeling platform. Different test cases will be simulated and these test cases will include different fault types, multiple fault locations, capacitor bank switching, etc. The feeder system modeled for these simulations will also include power electronics based DERs. Additionally, experimental results demonstrating the high frequency signatures generated due to a transient event in a medium voltage (13.8 kV) distribution line will also be presented in the full paper. Furthermore, the analysis combined with simulation and experimental results in the full paper will help demonstrate the feasibility and efficacy of the proposed protection scheme. The developed protection scheme will not just help solve problems generated by bidirectional current flow, varying short-circuit current capacity, but also help in proliferation of DERs in distribution systems.

41 EE - Solar Energy Technologies Office (EE-4S)↗