Science Uses Deployment Operations-Advanced Wireless: Exploring Open Radio Access Network Technologies for Energy Science

Open Radio Access Network is emerging as a solution to the increasing demand for more flexible, cost-effective, and advanced mobile network infrastructures. This evolution is driven by advancements in wireless technologies and the growing complexity of deploying and managing these networks. O-RAN represents a significant shift in wireless technology, building upon the 3rd Generation Partnership Project framework to foster openness, flexibility, and interoperability. By decoupling hardware and software components, Open Radio Access Network enables a multi-vendor ecosystem that encourages innovation and diverse solutions. Open Radio Access Network's potential extends beyond traditional wireless applications, with growing interest in its role in advancing energy systems, particularly in the context of smart grids, microgrids, and the integration of renewable energy sources. While the role of open-wireless technologies in driving energy transformation is increasingly recognized, further exploration is needed. Vendors and utilities are investigating how Open Radio Access Network technologies can optimize energy use cases and improve the performance of 5G and beyond applications. This report outlines efforts under the Science Uses Deployment Operations Advance Wireless project, a collaboration between the National Laboratory of the Rockies' Cybersecurity Research Center, Argonne National Laboratory, Lawrence Berkeley National Laboratory, and the Department of Energy's Energy Science Network research and operations staff. The focus of this project is on due diligence, through testing and evaluation, preparing for the deployment of advanced wireless infrastructure for scientific use cases, with an emphasis on Open Radio Access Network technology, its components, integrations, and its ability to support vertical stack application across the energy sector. Additionally, the report highlights the value cases for utilities, underscoring how adopting open wireless standards can accelerate the evolution of energy systems, foster innovation, and improve the integration of critical energy technologies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Influence of Inverter-Based Resources on Microgrid Protection: Part 1: Microgrids in Radial Distribution Systems

Microgrids are being deployed at a rising rate, primarily as a means of increasing power system resilience. Commonly, a microgrid today includes at least some inverter-based resources (IBRs), and many microgrids have modes or conditions under which they are entirely energized by IBRs. Also, most microgrids today are deployed on radial distribution circuits, but it is conceivable that they could also be considered for deployment on secondary network systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

ReNCAT: The Resilient Node Cluster Analysis Tool

ReNCAT is a software application that suggests microgrid portfolios that reduce the impact of large-scale disruptions to power, as measured by the Social Burden Metric. ReNCAT examines a power distribution network to identify regions that can be isolated into microgrids that enable critical services to be provided even if the remainder of the study area is left without power. ReNCAT operates on a simplified representation of the power grid, one that aggregates and approximates loads and conductors. Microgrids are formed within the power network by setting switch states to split or join portions of the grid. ReNCAT identifies candidate microgrid portfolios with varying tradeoffs between cost and service availability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Mixed Integer Linear Programming-basedDistributed Energy Management for Three-phaseUnbalanced Active Distribution Network

A mixed integer linear programming (MILP)–baseddistributed energy management for three-phase unbalancedactive distribution network is proposed. Modern distributionnetworks have becoming more and more active with increasingdeployment of microgrids, distributed energy resources (DERs)as well as controllable loads. Considering various ownership andcontrol models of microgrids, DERs and controllable loads, adistributed energy management was formulated using the alternatingdirection method of multipliers (ADMM) algorithm. ByADMM, the distribution management system (DMS) and theseactive components are coordinated through price signals, whichare adjusted according to the generation-load mismatch per nodeper phase. To enable resolution of the ADMM-based distributedoptimization using more accessible and popular MILP solver,different linearization techniques were proposed to linearize theaugmented Lagrangian terms and other nonlinear terms. Resultsof case studies on a three-phase active distribution network withthree microgrids and several DERs and controllable loads validatedthe effectiveness of proposed MILP-based distributed energymanagement. In addition, the capability of proposed method inmitigating phase power unbalance has been demonstrated.

Liu, Guodong↗

Day-Ahead Forecasting with Federated LSTM to Plan Energy Sharing in a Community Microgrid

Energy balancing in microgrids is a key enabler of resilience. Community microgrids located close to each other have the added benefit of networking and sharing surplus energy, if available. Such complex decision-making runs on optimization that requires reliable short-term (up to very-short-term) forecasts of energy generation and consumption for scheduling or trading. Each microgrid may also opt to not expose their sensitive data such as consumption patterns of individual businesses or residences. This paper investigates a federated approach to dayahead forecasting that trains naive long short-term memory (LSTM) at each business in a microgrid and aggregates weights at the microgrid controller using proximal regularization. This approach ensures that the controller has access only to energy surplus/deficit and not the actual generation or consumption values, avoiding unwanted exposure of sensitive data. A community microgrid in Adjuntas, Puerto Rico with 3 businesses is selected as a case study with a laboratory-scale computing setup. A central LSTM forecaster, where sensitive data from businesses are aggregated at the controller, is implemented as a baseline for qualifying the results. This work serves as a proof-of-concept for scaling the approach to networked and nested microgrids with more complex control options.

Sundararajan, Aditya [ORNL] (ORCID:000000033577854↗

AI-enabled traveling wave protection for microgrids

Grid forming inverters provide voltage and frequency regulations for microgrids; in the meantime, new challenges are introduced for microgrid protections. For instance, inverters’ control strategies can affect protection behaviors, and low short-circuit ratios and bi-directional power flows also make protection operations complex. Protection schemes based on conventional principles such as overcurrent and distance relays do not always provide reliable, sensitive, or selective operations. Here, we devise a traveling wave protection approach for microgrids using a wavelet-driven deep neural network named WaveletKernelNet (WKN). Compared with conventional methods, the presented approach provides enhanced sensitivity, higher selectivity, and better identification of various faults in microgrids. Extensive case studies validate the efficacy and excellent performance of the devised approach.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Real-Time Model-Adaptive Relaying Applied to Microgrid Protection

In microgrids, the short-circuit current magnitude is significantly limited by more than an order of magnitude due to the relatively small inverter-based resources. Commercially available protective devices for distribution cannot reliably protect a microgrid due to their dependence on the magnitude of the fault current. Moreover, overcurrent relays typically cannot function properly for a microgrid because they are incapable of detecting faults and/or performing the coordination between the relays in inverter-based microgrids operated in the islanded mode. This paper proposes a model-adaptive relay designed to adjust the relay curves based on the available generation and the network topology. The proposed method runs a real-time model of the microgrid, which gathers information from the network to calculate the available short-circuit current in the specified node. The fault current from the model is then used for the adaptive algorithm to calculate the relay settings, considering coordination with the downstream fuses and upstream reclosers. This work presents the validation of the proposed method in Hardware-in-the-Loop, in a hardware testbed as well as field deployed in a real microgrid in East-Tennessee.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Spatial-Temporal Recurrent Graph Neural Networks for Fault Diagnostics in Power Distribution Systems

Fault diagnostics are extremely important to decide proper actions toward fault isolation and system restoration. The growing integration of inverter-based distributed energy resources imposes strong influences on fault detection using traditional overcurrent relays. This paper utilizes emerging graph learning techniques to build new temporal recurrent graph neural network models for fault diagnostics. The temporal recurrent graph neural network structures can extract the spatial-temporal features from data of voltage measurement units installed at the critical buses. From these features, fault event detection, fault type/phase classification, and fault location are performed. Compared with previous works, the proposed temporal recurrent graph neural networks provide a better generalization for fault diagnostics. Moreover, the proposed scheme retrieves the voltage signals instead of current signals so that there is no need to install relays at all lines of the distribution system. Therefore, the proposed scheme is generalizable and not limited by the number of relays installed. The effectiveness of the proposed method is comprehensively evaluated on the Potsdam microgrid and IEEE 123-node system in comparison with other neural network structures.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Low Voltage Network Protection Utility Workshop (Summary and Next Steps)

Increased penetration of Distributed Energy Resources and microgrids have fundamentally changed the operation al characteristics of Low Voltage (LV) network systems. Current LV network protection philosophy and practice are due for a significant re vamp to keep up with changing operating conditions. This workshop invites four of the major LV network users in the US to discuss the challenges they face today and the new technologies they have been experimenting with in light of this workshop discussion, use cases for further hardware-in-the-loop testing efforts are proposed to evaluate new LV network protection solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Bilevel Voltage Regulation Operation for Distribution Systems With Self-Operated Microgrids

The emerging of microgrids in distribution systems has significantly enhanced the resilience of power grids. However, the operators of a distribution system and microgrids therein can be different and have accessibility to different devices. To model the operation of such a grid, this work proposes a bilevel formulation and probes into the voltage regulation operation, considering the interaction between different systems. The proposed bilevel formulation considers the cooperation of active energy resources (AER), transformer tap-changers, and capacitor banks that are controlled by different operators. To facilitate the solution time of the target bilevel optimization, the lower-level problems with different objectives are modeled using deep neural networks (DNNs) which are then converted into a set of constraints. Hence, the bilevel problem can be reformed to a single-level problem. Lastly, the proposed solution procedures are validated using a customized joint system constructed by the IEEE 123-bus system and a real distribution system in Iowa. According to the numerical validation results, the solution time of the proposed nonlinear activation function based DNN model is 69 times faster than other methods in solving voltage regulation with a bilevel structure.

24 POWER TRANSMISSION AND DISTRIBUTION↗

DC Microgrids Under Denial of Service Attacks: Feasibility and Stability Issues

Distributed control has been extensively studied for a DC microgrid to coordinate multiple grid assets where each asset can generate its own control decisions based on communications within its neighborhood. Nevertheless, such a control strategy usually has a strong dependence on active information exchange and needs to always maintain a pre-determined communication graph. This makes it vulnerable to cyber attacks, especially denial of service (DoS) attacks that block communication channels that effectively change the communication graph. In this paper, we study two potential impacts of DoS attacks: the inability to maintain steady-state and dynamical generation-demand balance, i.e. the feasibility and stability issues. We develop a mathematical model to describe the cyber-induced system steady-state and dynamical performance. The model reveals the impacts of DoS attacks and enables formal analysis. Case studies are shown to verify the proposed work.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Study of microgrid resilience through co-simulation of power system dynamics and communication systems

The interdependence of power and communication systems in smart grid technologies is acknowledged, but difficult to quantify. Communication systems can be essential to maintaining stability in microgrids that are islanded due to extreme events. Though many power system studies assume the presence of communication networks, detailed modeling of power and communication systems for dynamic studies of microgrids is rare. The work presented in this paper develops a framework for power and communication system co-simulation to study the impact of communications system on microgrid stability. An operational use case is examined where a battery energy storage system operates to offset the loss of generation in an islanded microgrid. The framework is evaluated for different communication technologies, network structures, and communication media.

Thekkumparambath Mana, Priya↗

Resilient Node Cluster Analysis Tool (ReNCAT) v. 2.1

SAND2021-6533 O The Resilient Node Cluster Analysis Tool (ReNCAT) identifies portions of a power distribution network that can be isolated into microgrids in order to supply services to a community during disruptive events. Candidate microgrid configurations are evaluated using a burden metric, a measure of the relative effort community members must expend to acquire services required for their well-being. Results present multiple candidate configurations, each with a different balance of cost and burden. Sandia National Laboratories is a multimission laboratory managed and operated by National Technology & Engineering Solutions of Sandia, LLC, a wholly owned subsidiary of Honeywell International Inc., for the U.S. Department of Energy’s National Nuclear Security Administration under contract DE-NA0003525.

Melander, Darryl↗

Resilient, Rural, and Revolutionary: Salisbury Square's Direct-Current Affordable Microgrid Community: Preprint

The technology to interconnect buildings with a dedicated direct-current (DC) power distribution network is in place today; what is missing is a turnkey approach to designing a DC microgrid - and the business models allowing such systems to be deployed, owned, and operated at scale. To close this gap, the Salisbury Square Development Team, comprising clean-energy experts, has engineered a resilient community DC microgrid for an affordable housing community in Randolph, Vermont. Ten single-family, occupant-owned residences and 12 multifamily rental units will share locally generated and stored solar energy via a DC power distribution bus capable of operating during extended grid outages. With a DC power distribution network in place, each home will be equipped with high-efficiency DC lighting and appliances, operating alongside alternating current (AC) appliances, even during an islanded mode of operation. To obtain a comprehensive understanding of what is possible and achievable, the Team collaborated with the local utility, regulatory agencies, a national laboratory, energy-as-service providers, and vendors. The collaborators evaluated microgrid typologies, business models, and energy modeling, and analyzed electrification and resilience. Further, the Team applied the URBANoptTM (Urban Renewable Building and Neighborhood optimization, NREL 2022) software development kit (SDK) to Salisbury Square's single-family and multifamily buildings to validate workflows and identify needs for advanced capability. This paper addresses the barriers to entry, scalability, and impact on residents and system ownership. It also examines the analysis that informed the design and engineering of the DC microgrid and the opportunities to streamline the process.

DER↗

Dynamic Shaping of Grid Response of Multi-Machine Multi-Inverter Systems Through Grid-Forming IBRs: Preprint

We consider the problem of controlling the frequency response of weakly-coupled multi-machine multi-inverter low-inertia power systems via grid-forming inverter-based resources (IBRs). In contrast to existing methods, our approach relies on dividing the larger system into multiple strongly-coupled subsystems, without ignoring either the underlying network or approximating the subsystem response as an aggregate harmonic mean model. Rather, through a structured clustering and recursive dynamic shaping approach, the frequency response of the overall system to load perturbations is shaped appropriately. We demonstrate the proposed approach for a three-node triangular configuration and a small-scale radial network. Furthermore, for small-scale radial microgrids, we demonstrate the ability of IBRs to tune the effective transfer functions of synchronous machines. This enables us to relax the uniform turbine time-constant assumptions and widen the scope of existing synchronization results for proportionally heterogeneous machines.

frequency-shaping control↗

A Novel Protection Scheme for Unbalanced Faults in Inverter Dominated Networks: A Computationally Efficient Algorithm for Entry-Level Relays

Microgrids are now a common practice in distribution systems to increase resilience and reliability. However, microgrid protection remains a critical challenge, considering its requirement to operate in both grid connected and islanded, and the variability in fault characteristics under each mode of operation. This paper presents unbalanced power (S unb ) based fault detection algorithm, which considers local voltage and current unbalances to determine faults in the system. S unb is a computationally efficient fault detection algorithm that is suitable for implementation in the programmable logic of entry level protective relays. In addition, the difference in current and voltage unbalance (D n ) is used to determine the fault type. The proposed method demonstrates high sensitivity and selectivity for line-to-ground (LG), line-to-line (LL), and double line-to-ground (LLG) faults, representing the most common faults in distribution systems. It also allows relay coordination with upstream and downstream protection devices in both island and grid connected operation, while preserving grading margins. The same pickup and time multiplier settings of a particular relay for both modes of operation eliminates the need for adaptive settings, which rely on communication networks. Validation was performed with a hardware-in-the-loop (HIL) setup using Typhoon HIL real time simulator interfaced with three entry-level, SEL 751 relays. Results confirmed the algorithm’s ability to discriminate fault conditions, and determine the fault type under both operating modes, maintain fast detection times, and ensure proper protection coordination.

fault classification↗

A Flexible Operation of Distributed Generation in Distribution Networks With Dynamic Boundaries

Distributed generators performing black start to form isolated microgrids offer a flexible and resilient solution to service restoration in distribution systems. Employing the dynamic microgrid concept, distributed generators can form isolated microgrids by changing their physical boundaries through smart switches and conventional circuit breakers. However, the flexibility of distributed generators has not been thoroughly investigated and utilised in existing works. To address this issue, this letter presents a new model to the reconfiguration formulation in active distribution networks considering different operation modes of distributed generators. Compared with the existing models, this study provides a new formulation supporting different DGs' operation modes and fully making use of their flexibility. Illustrative results on IEEE 34-test systems verify the effectiveness of the proposed model.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Hardware Platform for Studying Naval Power Electronic Power Distribution Systems

Abstract – Future intelligent ship system designs will likely include electric propulsion, numerous highpower sensors, and directed energy weapons. Supply and control of these large nonlinear loads will require a networked, multi-converter power electronic power distribution system. This work presents a hardware platform to emulate a microgrid power system with multiple power converters and a power data communication network. The platform is reconfigurable and can include both AC and DC power distribution zones, representative of shipboard power systems. It also allows for the study of both power control actuation and power data communication delays. Since the platform is based on electric power hardware, spatial and temporal uncertainties are inherently embedded in the system. Specifically, this work examines the control actuation of multiple pulsed power loads in a single microgrid. Several pulse load levels and operating scenarios have been implemented and measured. A framework for control parameter quantification is presented, and various metrics are explored to capture pulse signal characteristics. The sensitivity of pulse load metric parameters is analyzed. Dynamic shipboard, mission-specific load profiles coupled with pulse loads can also be emulated in the hardware platform.