At least 1,567 records · Page 87

Dynamic Line Rating: Research and Policy Evaluation

Dynamic Line Rating (DLR) is a smart grid technology that allows the rating of electrical conductors to be increased based on local weather conditions. Overhead lines are conventionally given a conservative rating based on worst case scenarios. We demonstrate that observing the conditions in real time leads to additional capacity and safer operation. This paper provides a report of a pioneering scheme in the United States of America in which DLR has been applied. Thereby, we demonstrate that observing the local weather conditions in real time leads to additional capacity and safer operation. Secondly, we discuss limitations involved. In doing so, we arrive at novel insights which will inform and improve future DLR projects. Third, we provide a policy background and discussion to clarify the technology’s potential and identifies barriers to the imminent adoption of dynamic line rating systems. We provide suggestions for regulatory bodies about possible improvements in policy to encourage adoption of this beneficial technology.

17 WIND ENERGY↗

Voltage Regulation Using a Permanent Magnet Synchronous Generator with a Series Compensator: Preprint

A wind power plant (WPP) is often operated at unity power factor, and the utility host where the WPP connects prefers to regulate the voltage. Although this may not be an issue in a stiff grid, the connection to a weak grid can be a problematic. This paper explores the advantages of having voltage regulation capability via reactive power control. Another issue in wind power generation is that not all turbines are able to control their reactive power due to technical reasons or contractual obligations. A synchronous condenser (SC) using a permanent magnet synchronous generator (PMSG) is proposed to provide necessary reactive power for regulating voltage at a weak grid connection. A PMSG has the advantage of higher efficiency and reliability. Because of its lack of a field winding, a PMSG is typically controlled by a full-power converter, which can be costly. In the proposed system, the reactive power of the SC is controlled by a serially connected compensator operating in a closed-loop configuration. The compensator also damps the PMSG’s tendency to oscillate. The compensator’s VA rating is only a fraction of the rating of the SC and the PMSG. In this initial investigation, the proposed scheme is shown to be effective by computer simulations.

17 WIND ENERGY↗

Energy Extraction from a Slider-Crank Wave Energy under Irregular Wave Conditions: Preprint

A slider-crank wave energy converter (WEC) is a novel energy conversion device. It converts wave energy into electricity at a relatively high efficiency, and it features a simple structure. Past analysis on this particular WEC has been done under regular sinusoidal wave conditions, and suboptimal energy could be achieved. This paper presents the analysis of the system under irregular wave conditions; a time-domain hydrodynamics model is adopted and a rule-based control methodology is introduced to better serve the irregular wave conditions. Results from the simulations show that the performance of the system under irregular wave conditions is different from that under regular sinusoidal wave conditions, but a reasonable amount of energy can still be extracted.

17 WIND ENERGY↗

Systematic Approach to Better Understanding Integration Costs: Preprint

When someone mentions integration costs, thoughts of the costs of integrating renewable generation into an existing system come to mind. We think about how variability and uncertainty can increase power system cycling costs as increasing amounts of wind or solar generation are incorporated into the generation mix. However, seldom do we think about what happens to system costs when new baseload generation is added to an existing system or when generation self-schedules. What happens when a highly flexible combined-cycle plant is added? Do system costs go up, or do they go down? Are other, non-cycling, maintenance costs impacted? In this paper we investigate six technologies and operating practices--including VG, baseload generation, generation mix, gas prices, self-scheduling, and fast-start generation--and how changes in these areas can impact a system's operating costs. This paper provides a working definition of integration costs and four components of variable costs. It describes the study approach and how a production cost modeling-based method was used to determine the cost effects, and, as a part of the study approach section, it describes the test system and data used for the comparisons. Finally, it presents the research findings, and, in closing, suggests three areas for future work.

17 WIND ENERGY↗

Energy Extraction from a Slider-Crank Wave Energy Converter under Irregular Wave Conditions

A slider-crank wave energy converter (WEC) is a novel energy conversion device. It converts wave energy into electricity at a relatively high efficiency, and it features a simple structure. Past analysis on this particular WEC has been done under regular sinusoidal wave conditions, and suboptimal energy could be achieved. This paper presents the analysis of the system under irregular wave conditions; a time-domain hydrodynamics model is adopted and a rule-based control methodology is introduced to better serve the irregular wave conditions. Results from the simulations show that the performance of the system under irregular wave conditions is different from that under regular sinusoidal wave conditions, but a reasonable amount of energy can still be extracted.

17 WIND ENERGY↗

Wind Generation Participation in Power System Frequency Response: Preprint

The electrical frequency of an interconnected power system must be maintained close its nominal level at all times. Excessive under- and overfrequency excursions can lead to load shedding, instability, machine damage, and even blackouts. There is a rising concern in the electric power industry in recent years about the declining amount of inertia and primary frequency response (PFR) in many interconnections. This decline may continue due to increasing penetrations of inverter-coupled generation and the planned retirements of conventional thermal plants. Inverter-coupled variable wind generation is capable of contributing to PFR and inertia with a response that is different from that of conventional generation. It is not yet entirely understood how such a response will affect the system at different wind power penetration levels. The modeling work presented in this paper evaluates the impact of wind generation's provision of these active power control strategies on a large, synchronous interconnection. All simulations were conducted on the U.S. Western Interconnection with different levels of instantaneous wind power penetrations (up to 80%). The ability of wind power plants to provide PFR - and a combination of synthetic inertial response and PFR - significantly improved the frequency response performance of the system.

17 WIND ENERGY↗

Investigating Power System Primary and Secondary Reserve Interaction under High Wind Penetration Using Frequency Response Model

Power system frequency needs to be maintained close to its nominal value at all times to avoid machine damage, under-frequency load-shedding and even blackouts. Adequate primary frequency response and secondary frequency response are the primary forces to correct an energy imbalance at the second to minute level. As wind energy becomes a larger portion of the world's energy portfolio, there are greater oppotunities for wind to provide frequency response services. This paper addresses one area of frequency control that has been missing in previous work - the reliabilty impacts and interactions between primary and secondary frequency control. The lack of a commercially available tools to simulate the interaction of these two responses has limited the energy industry's understanding of when the depletion of primary control reserve will impact the performance of secondary conrol response or vice versa. To investigate this issue, in this paper we develop a multi-area frequency response integration model with combined primary and secondary frequency control capabilities.

17 WIND ENERGY↗

Hardware-in-the-loop grid simulator system and method

A hardware-in-the-loop (HIL) electrical grid simulation system and method that combines a reactive divider with a variable frequency converter to better mimic and control expected and unexpected parameters in an electrical grid. The invention provides grid simulation in a manner to allow improved testing of variable power generators, such as wind turbines, and their operation once interconnected with an electrical grid in multiple countries. The system further comprises an improved variable fault reactance (reactive divider) capable of providing a variable fault reactance power output to control a voltage profile, therein creating an arbitrary recovery voltage. The system further comprises an improved isolation transformer designed to isolate zero-sequence current from either a primary or secondary winding in a transformer or pass the zero-sequence current from a primary to a secondary winding.

17 WIND ENERGY↗

Structural Mass Saving Potential of a 5-MW Direct-Drive Generator Designed for Additive Manufacturing

As wind turbine blade diameters and tower height increase to capture more energy in the wind, higher structural loads results in more structural support material increasing the cost of scaling. Weight reductions in the generator transfer to overall cost savings of the system. Additive manufacturing facilitates a design-for-functionality approach, thereby removing traditional manufacturing constraints and labor costs. The most feasible additive manufacturing technology identified for large, direct-drive generators in this study is powder-binder jetting of a sand cast mold. A parametric finite element analysis optimization study is performed, optimizing for mass and deformation. Also, topology optimization is employed for each parameter-optimized design.The optimized U-beam spoked web design results in a 24 percent reduction in structural mass of the rotor and 60 percent reduction in radial deflection.

17 WIND ENERGY↗

Structural Design Optimization of Doubly-Fed Induction Generators Using GeneratorSE

A wind turbine with a larger rotor swept area can generate more electricity, however, this increases costs disproportionately for manufacturing, transportation, and installation. This poster presents analytical models for optimizing doubly-fed induction generators (DFIGs), with the objective of reducing the costs and mass of wind turbine drivetrains. The structural design for the induction machine includes models for the casing, stator, rotor, and high-speed shaft developed within the DFIG module in the National Renewable Energy Laboratory's wind turbine sizing tool, GeneratorSE. The mechanical integrity of the machine is verified by examining stresses, structural deflections, and modal properties. The optimization results are then validated using finite element analysis (FEA). The results suggest that our analytical model correlates with the FEA in some areas, such as radial deflection, differing by less than 20 percent. But the analytical model requires further development for axial deflections, torsional deflections, and stress calculations.

17 WIND ENERGY↗

High voltage DC power conversion system and method of operating the same

A fraction rated conversion system for coupling a plurality of high voltage direct current (HVDC) power strings in parallel to an HVDC transmission system includes at least one fraction rated power converter coupled to the plurality of HVDC power strings and at least one capacitive device coupled to the at least one fraction rated power converter. The at least one fraction rated power converter and the at least one capacitive device regulate a differential voltage across each HVDC power string of the plurality of HVDC power strings to be substantially similar to each other.

17 WIND ENERGY↗

Impedance Measurement of Wind Turbines using a Multimegawatt Grid Simulator: Preprint

This paper presents the impedance measurements of a 4 MW wind turbine conducted using a multimegawatt grid simulator at the National Renewable Energy Laboratory in Colorado, United States. This paper describes different systems, including a 7 MVA grid simulator, a 5 MW dynamometer, a medium-voltage measurement system, and a real-time control system used for the automated impedance measurement of a utility-scale wind turbine. Different aspects of impedance measurement are discussed, including the selection of the magnitude of injected perturbation, measurement of frequency cross-coupling between the sequence impedance responses, and the alignment of the reference frame for sequence impedance measurement. The paper also demonstrates high-fidelity validation of an EMT simulation model of the wind turbine using impedance measurements.

24 POWER TRANSMISSION AND DISTRIBUTION↗