Multi-Segment Decentralized Control Strategies for Renewables-Rich Microgrids in Extreme Conditions

Microgrids provide a promising approach to accommodating various distributed energy resources (DERs), while requiring significant communication infrastructures that may be affected by extreme conditions such as natural disasters and cyber-attacks. In this paper, a fully decentralized control strategy without the need for communication is proposed for islanded microgrids with high renewables penetration. First, special multi-segment power/frequency characteristic curves are designed, so that different DERs can be automatically coordinated in a prioritized manner such as renewables first to maintain power balance while DER frequencies are regulated at their reference values. Second, piecewise linear served load versus frequency models are designed to prioritize loads according to their significance, so that only noncritical loads will be curtailed as needed while critical loads are supplied without any interruptions during power deficiency. The proposed strategy can effectively deal with various normal and extreme system conditions including 100% renewables penetration, loads and renewables variations, power deficiencies requiring load curtailments, disconnection of existing DERs, connection of new DERs as well as network sectionalization and reconfiguration. As a result, the proposed control strategy is validated in the real-time digital simulator (RTDS) model of the IIT Campus Microgrid to demonstrate its effectiveness in enhancing the resiliency of renewables-rich microgrids in extreme conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Planning Roadmap for DER Integration in India: Industry Best Practices and Resource Guide

Ensuring safe, reliable, cost-effective DER integration at scale requires holistic planning, broad stakeholder engagement, and should address key development areas such as standards adoption, equipment testing and certification, interoperability and cybersecurity, interconnection procedures, and advanced forecasting and DER management. Each of these areas currently represent significant challenges for utilities, regulators, OEMs, developers, and even consumers worldwide. India has already seen significant growth of DERs and has announced targets for substantial growth yet to come, with the potential for DERs to make up a non-negligible portion of the country's overall generation capacity. As such, it is of critical importance that Indian stakeholders consider the potential impacts of wide-spread adoption of DERs and take preemptive action related to the five development areas listed here, among others. India should consider strategies including the adoption of key DER standards related to interconnection, testing, and cybersecurity; enabling effective and secure communication channels for DER interoperability; testing and certifying DER equipment in accredited testing laboratories; building robust, streamlined interconnection procedures; and revamping legacy system planning structures to incorporate DERs in a holistic planning framework.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Formally Verified ZTA Requirements for OT/ICS Environments with Isabelle/HOL

The clean energy transformation includes the integration of distributed energy resources with the power grid, which has led to a substantial increase in the complexity of power grids infrastructure and the underlying operational technology environment. Power grids infrastructure represents an operational technology environment that has become a system of systems, integrating heterogeneous devices which are both software-and hardware-intensive; as a result, there are increasing demands to exploit advances in the commodity of software-hardware infrastructures to improve energy systems requirements such as cybersecurity and resilience. In such a setting, system requirements at different levels mix, which leads to vulnerabilities and undesirable outcomes. The use of formal methods to characterize and prove system requirements removes ambiguity, increases automation, and provides high levels of assurance and reliability. In this paper, we contribute a methodology and a framework for the system-level verification of zero trust architecture requirements in operational technology environments. We define a formal specification for the core functionalities of operational technology environments, the corresponding invariants, and security proofs. Of particular note is our modular approach for the formal verification of asynchronous interactions in operational technology environments. The formal specification and the proofs have been mechanized using the interactive theorem proving environment Isabelle/HOL.

formal methods↗

Deep-Learning-Based Multi-Timescale Load Forecasting in Buildings: Opportunities and Challenges from Research to Deployment

Electricity load forecasting for buildings and campuses is becoming increasingly important as the penetration of distributed energy resources (DERs) grows. Efficient operation and dispatch of DERs require reasonably accurate predictions of future energy consumption in order to conduct near-real-time optimized dispatch of on-site generation and storage assets. Electric utilities have traditionally performed load forecasting for load pockets spanning large geographic areas, and therefore, forecasting has not been a common practice by buildings and campus operators. Given the growing trends of research and prototyping in the grid-interactive efficient buildings domain, characteristics beyond simple algorithm forecast accuracy are important in determining the algorithm's true utility for smart buildings. Other characteristics include the overall design of the deployed architecture and the operational efficiency of the forecasting system. In this work, we present a deep-learning-based load forecasting system that predicts the building load at 1-hour intervals for 18 hours in the future. We also discuss challenges associated with the real-time deployment of such systems as well as the research opportunities presented by a fully functional forecasting system that has been developed within the National Renewable Energy Laboratory's Intelligent Campus program.

building load forecasting↗

Hardware-in-the-Loop Testbed for Cyber-Physical Security of Photovoltaic Farms

In the last decades, modem grids with distributed energy resources, such as photovoltaic (PV) farms, are increasingly vulnerable to cyber-attacks that seriously affect the stability and performance of the power system. While cyber-physical security of smart grids is extensively studied, most of the existing work focuses on the grid level and neglects the modeling and features of device-level power electronics converters (PECs). Furthermore, establishing a high-fidelity simulation testbed that can simulate harmonic frequencies of the PV farm is in urgent need. In this paper, a high-fidelity and real-time hardware-in- the-loop testbed is built to simulate the harmonics of power electronics converters for cyber-physical security of PEC-enabled PV farms. Based on this testbed, the impact of typical cyber-attacks and physical faults on the PV converter can be analyzed, thus providing a foundation for cyber-attack detection, root cause diagnosis, and resilient control to mitigate the adverse effects of cyber-attacks.

14 SOLAR ENERGY↗

Behavioral and Population Data-Driven Distribution System Load Modeling

Distribution system residential load modeling and analysis for different geographic areas within a utility or an independent system operator territory are critical for enabling small-scale, aggregated distributed energy resources to participate in grid services under Federal Energy Regulatory Commission Order No. 2222 [1]. In this study, we develop a methodology of modeling residential load profiles in different geographic areas with a focus on human behavior impact. First, we construct a behavior-based load profile model leveraging state-of-the-art appliance models. We simulate human activity and occupancy using Markov chain Monte Carlo methods calibrated with the American Time Use Survey data set. Second, we link our model with cleaned Current Population Survey data from the U.S. Census Bureau. Finally, we populate two sets of 500 households using California and Texas census data, respectively, to perform an initial analysis of the load in different geographic areas with various group features (e.g., different income levels). To distinguish the effect of population behavior differences on aggregated load, we simulate load profiles for both sets assuming fixed physical household parameters and weather data. Analysis shows that average daily load profiles vary significantly by income and income dependency varies by locality.

American Time Use Survey↗

Remote Off-grid Microgrid Design Support Tool (ROMDST) - An Optimal Design Support Tool for Remote, Resilient, and Reliable Microgrids Phase II - Final Report

The objective of the project is to develop an advanced optimization-based design support tool for AC or DC microgrids in remote locations, where utility grids may not be accessible. The mathematical model and the interface are being developed such that multiple design objectives and criteria/constraints can be easily enabled or disabled, to deliver a flexible tool relevant to a large, diverse user base, and to facilitate future feature developments. The new tool delivered by this project leverages the team’s extensive expertise in the development, testing, deployment, and commercialization of the state-of-the-art Distributed Energy Resources Customer Adoption Model (DER-CAM) – which is the foundation for the new tool. Phase I of the project leverages the microgrid design and decision support tool DER-CAM. Key Phase I developments include the following adaption to the DER-CAM model: a) AC or DC microgrid architectures, b) multiple economic objectives (e.g. single customer vs community vs utility perspective), c) constraints on fuel availability (e.g. total fuel available during outage periods), d) active and reactive power flow constraints for normal and N-1 contingency cases, e) component part load efficiencies (e.g. power electronic devices), and f) interactive data visualization capabilities (e.g. design topology elements). A component library including components’ default technical and economical characteristics was also developed. In Phase II, the project is focused on tool testing and validation, use for real-world microgrid designs, and outreach. Fully developing this tool will have the following impacts: 1) optimal off-grid microgrid designs that replace existing back of the envelope or non-optimal calculations, reducing capital costs and risk of microgrid deployment; 2) removing barriers to microgrid assessments by lowering microgrid soft costs, as the tool is freely usable; 3) reliable and resilient designs that reduce the cost of critical load shedding due to component outages.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Chapter 7: Predictive Analytics in Future Power Systems: A Panorama and State-of-the-Art of Deep Learning Applications

The challenges surrounding the optimal operation of power systems are growing in various dimensions, due in part to increasingly distributed energy resources and a progression towards large-scale transportation electrification. Currently, the increasing uncertainties associated with both renewable energy generation and demand are largely being managed by increasing operational reserves - potentially at the cost of suboptimal economic conditions - in order to maintain the reliability of the system. This chapter looks at the big picture role of forecasting in power systems from generation to consumption and provides a comprehensive review of traditional approaches for forecasting generation and load in various contexts. This chapter then takes a deep dive into the state-of-the-art machine learning and deep learning approaches for power systems forecasting. Furthermore, a case study of multi-time-horizon solar irradiance forecasting using deep learning is discussed in detail. Smart grids form the backbone of the future interdependent networks. For addressing the challenges associated with the operations of smart grid, development and wide adoption of machine learning and deep learning algorithms capable of producing better forecasting accuracies is urgently needed. Along with exploring the implementation and benefits of these approaches, this chapter also considers the strengths and limitations of deep learning algorithms for power systems forecasting applications. This chapter, thus, provides a panoramic view of state-of-the-art of predictive analytics in power systems in the context of future smart grid operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Stochastic Optimization with Risk Aversion for Virtual Power Plant Operations: A Rolling Horizon Control

While the concept of aggregating and controlling renewable distributed energy resources (DERs) to provide grid services is not new, increasing policy support of DER market participation has driven research and development in algorithms to pool DERs for economically viable market participation. Sandia National Laboratories recently undertook a three-year research program to create the components of a real-world virtual power plant (VPP) that can simultaneously participate in multiple markets. Our research extends current state-of-the-art rolling horizon control through the application of stochastic programming with risk aversion at various time resolutions. Our rolling horizon control consists of (1) day-ahead optimization to produce an hourly aggregate schedule for the VPP operator and (2) sub-hourly optimization for real-time dispatch of each VPP subresource. Both optimization routines leverage a two-stage stochastic program (SP) with risk aversion, and integrate the most up-to-date forecasts to generate probabilistic scenarios in real operating time. Our results demonstrate the benefits to the VPP operator of constructing a stochastic solution regardless of the weather. In more extreme weather, applying risk optimization strategies can dramatically increase the financial viability of the VPP. As a result, the methodologies presented here can be further tailored for optimal control of any VPP asset fleet and its operational requirements.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impacts of Inverter-Based Advanced Grid Support Functions on Islanding Detection

A long-standing requirement for inverters paired with distributed energy resources is that they are required to disconnect from the electrical power system (EPS) when an electrical island is formed. In recent years, advanced grid support controls have been developed for inverters to provide voltage and frequency support by integrating functions such as voltage and frequency ride-through, volt-VAr control, and frequency-Watt control. With these new capabilities integrated into the inverter, additional examination is needed to determine how voltage and frequency support will impact pre-existing inverter functions like island detection. This paper inspects how advanced inverter functions will impact its ability to detect the formation of an electrical island. Results are presented for the unintentional islanding laboratory tests of three common residential-scale photovoltaic inverters performing various combinations of grid support functions. For the inverters tested, grid support functions prolonged island disconnection times slightly; however, it was found that in all scenarios the inverters disconnected well within two seconds, the limit imposed by IEEE Std 1547-2003.

14 SOLAR ENERGY↗

A Decision Support Tool for Distributed Solar and Storage Investments: A Case Study in Austin, TX

This study builds a decision support tool to evaluate when it is a good economic decision (least cost with minimum discomfort) for the residential customer to invest in distributed energy resources (DERs) based on different electricity rate structures, DER ownership frameworks, and DER rebates offered by electric utilities. Here, the tool is demonstrated using empirical electricity consumption data from Pecan Street Inc. (a non-profit entity based on Austin, Texas), residential rates from Austin Energy (the municipal electric utility in Austin, Texas), DER ownership costs from various nationwide pilot programs, and incentives offered by electric utilities in the United States. Results show that for constant electricity rates, the overall expenditure is least when the customer owns solar panels without storage, while for time-varying pricing structures, the least expensive scenario is one where the customer does not own any DERs. As the capital costs for DERs decline, utilities incentivize customer ownership of DERs, and more residential customers face the decision of whether to invest in DERs, this study aims to be a key tool in aiding that decision-making process.

14 SOLAR ENERGY↗

An Advanced Synchronized Time Digital Grid Twin Testbed for Relay Misoperation Analysis of Electrical Fault Type Detection Algorithms

Distributed energy resources and the number of relays are expected to rise in modern electrical grids; consequently, relay misoperations are also expected to grow. Relays can detect electrical fault types using an internal algorithm and can display the result using light indicators on the front of the relay. However, some relays’ internal algorithms for predicting types of electrical faults could be improved. This study assesses a relay’s external and internal algorithms with an Advanced Synchronized Time Digital Grid Twin (ASTDGT) testbed with paired relays. A misoperation relay analysis focused on measuring the accuracy of using the boundary admittance (the external algorithm) versus the set-default (the internal algorithm) relay method to determine the electrical fault types was performed. In this study, the internal and external relay algorithms were assessed with a synchronized time digital grid twin testbed using a real-time simulator. This testbed evaluated two sets of logic at the same time with the digital grid twin and paired relays in the loop. Different types of electrical faults were simulated, and the relays’ recorded events and electrical fault light indicator states were collected from the human–machine interfaces. This ASTDGT testbed with paired relays successfully evaluated the relay algorithm misoperations. The boundary admittance method had an accuracy of 100% for line-to-line, line-to-ground, and line-to-line ground faults.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Determining Utility System Value of Demand Flexibility From Grid-interactive Efficient Buildings

This report focuses on ways current methods and practices that establish the value to electric utility systems of distributed energy resource (DER) investments can be enhanced to determine the value of demand flexibility in grid-interactive efficient buildings that can provide grid services. The report introduces key valuation concepts that are applicable to demand flexibility that these buildings can provide and links to other documents that describe these concepts and their implementation in more detail.The scope of this report is limited to the valuation of economic benefits to the utility system. These are the foundational values on which other benefits (and costs) can be built. Establishing the economic value to the grid of demand flexibility provides the information needed to design programs, market rules, and rates that align the economic interest of utility customers with building owners and occupants. By nature, DERs directly impact customers and provide societal benefits external to the utility system. Jurisdictions can use utility system benefits and costs as the foundation of their economic analysis but align their primary cost-effectiveness metric with all applicable policy objectives, which may include customer and societal (non-utility system) impacts.This report suggests enhancements to current methods and practices that state and local policymakers, public utility commissions, state energy offices, utilities, state utility consumer representatives, and other stakeholders might support. These enhancements can improve the consistency and robustness of economic valuation of demand flexibility for grid services. The report concludes with a discussion of considerations for prioritizing implementation of these improvements.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Solar +: Clean Energy Strategies for the Sunshine State (Final Technical Report (FTR) of the Florida Alliance for Accelerating Solar and Storage Technology Readiness (FAASSTeR))

This reports on a four-year effort to provide foundational research, analysis, strategies and assistance to help Florida, and other states that might learn from this work, to grow solar energy in conjunction with other distributed energy resources by addressing and overcoming existing barriers, and in way that delivers increased value. The start of this effort coincided with an inflection point of sorts into a new dawn for solar energy in Florida, where the Sunshine state’s national ranking in total installed solar, according to the Solar Energy Industries Association (SEIA), has rose from 13th to 4th. Florida has now become the national leader in annual utility-scale solar growth as dozens of large plants have come online. Also, during this time, Florida utilities have expressed a strong and growing interest in understanding the role of energy storage and how to best plan for and deploy this unique resource as part of strategies to grow solar. The utility-scale solar growth experienced has been fueled by the economics of solar cost-parity with natural gas combined cycle plants and Florida Public Service Commission’s (PSC) approval of cost-recovery for the Investor-Owned Utilities (IOU’s), primarily through the Solar Base Rate Adjustment (SoBRA) mechanism. This has led to gigawatts (GW’s) of rate-based solar capacity additions over several years, along with fairly significant amounts of energy storage. Meanwhile, municipal electric utilities, which, collectively, are the third largest source of power in the state, have been increasing solar considerably through power purchase agreements (PPA’s) and are on track to have close to 1 GW of grid-connected solar by 2024. Florida’s municipal utilities and the Florida Municipal Electric Association (FMEA) have been key partners in the Florida Alliance for Accelerating Solar and Storage Technology Readiness (FAASSTeR), formed to carry out this effort. The six largest of these have been Core Team utilities, engaging throughout the project in weekly calls, discussions, and project direction, participating in and hosting workshops and benefiting from technical assistance in several areas.

14 SOLAR ENERGY↗

Stochastic Microgrid Scheduling With Chance‐Constrained Resilience Consideration

Traditionally, it is assumed that microgrids transition seamlessly from grid‐connected operation to islanded mode in the event of sudden main grid outages. In reality, the islanding process, especially unintentional islanding, is rarely seamless. Instead, it is subject to voltage and frequency fluctuations caused by the instantaneous disconnection of the point of common coupling (PCC) switch, variations in loads and renewable generation output and even the protection tripping of distributed energy resources (DERs). To mitigate these fluctuations and facilitate a smooth islanding process, we propose a stochastic microgrid scheduling model that incorporates chance‐constrained resilience measures. Specifically, the resilience measure is defined as the probability of successful islanding (PSI), that is, the probability that a microgrid can mitigate the generation‐demand imbalance caused by the disconnection of the PCC switch, variations in load and renewable generation and DER tripping. This measure is modelled using chance constraints. Unlike existing reliability and resilience indices, which typically neglect the possibility of microgrid/DER failure under extreme events and assume their survival while primarily focussing on reducing impact duration or magnitude, the proposed PSI‐based framework explicitly addresses microgrid and DER survival during the islanding transition. The formulated nonlinear chance constraints are approximated using a multiinterval approach and equivalently represented as a mixed‐integer linear programming (MILP) formulation. Case study results validate the proposed method, showing that the PSI estimation error is reduced to less than 8%, compared to approximately 28% with existing methods. Various sensitivity analyses on the DER tripping rate and PSI settings were performed to validate the robustness of the proposed method. In particular, the necessity of accounting for DER tripping in the PSI calculation was demonstrated.

chance constrained optimization↗

DER Inverter Control Fault Ride Through Model in Accordance with IEEE 1547-2018 Std

Distributed Energy Resources (DER) with smart inverters are becoming more prevalent as the need for renewable energy and grid stability increases. An important challenge arises when considering that inverterbased generation methods contribute less current during faults, rendering traditional overcurrent protection unsatisfactory. DERs have fault ride-through requirements when operating in high or low voltage, outlined by IEEE Std. 1547-2018. Faults cause the voltage to reach abnormal steady state magnitudes, depending on the fault resistance and fault type. There are several high voltage and low voltage ride-through zones defined by IEEE Std. 1547-2018. Each zone’s ride through duration decreases as the applicable voltage measurement, i.e., the phase RMS voltage, deviates from its nominal value. This presentation demonstrates the implementation of IEEE Std. 1547-2018 high and low voltage ridethrough grid support functions using a preexisting RSCAD model, discussing the challenges presented during this process. The implemented controls monitor the filtered phase voltages to have a more accurate reading of the applicable voltages. The controls sense the duration that the applicable voltage remains in a specific zone. The breaker trips and ceases energization to the grid when the duration is exceeded. The standard allows the operator to adjust the ride-through times and voltage zones from the default settings. These ranges are implemented into the runtime, which acts as the operator’s SCADA. The results show the accuracy of the voltage measurements, which remain within the IEEE Std. 1547-2018 for all cases.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Plug-in Electric Vehicle Charging Response Characterization for Grid Integration: Implications for Smart Charge Management

The rapid expansion of plug-in electric vehicles (PEVs) has created a unique challenge for electrical grids due to their significant power demand. At the same time, PEVs also create a unique opportunity to ease their own burden on the power grid, as they create a growing fleet of distributed energy resources capable of providing grid services such as demand response, frequency regulation, and renewable balancing. For aggregators and grid operators to effectively integrate PEVs into grid management, it is essential to first understand and characterize how they would respond in such situations. This study examines 25 models of PEVs across 25 makes, spanning model years from 2013 to 2025, to characterize their responses to the basic controls used in vehicle-grid integration (VGI): stopping, starting, and modulating the charge rate. Each vehicle was tested in a controlled laboratory setting to evaluate its performance in response to varying the maximum allowable current via the SAE J1772 control pilot signal, as well as its response to wake-up commands outlined in SAE J1772. Results show measurable differences across vehicle makes in the accuracy, latency, and precision with which PEVs respond to changes in ampacity, as well as varying sleep and wake-up behavior. The test results show that all vehicles respond to changes in ampacity, though with varying accuracy, precision, latency, and resolution. Wake-up behavior also differs across makes and models. These findings indicate that effective grid integration strategies must account for these differences. The results provide a foundation for understanding current vehicle behavior and advancing smart-charging methods while also highlighting the need for further testing, broader standardization, and manufacturer collaboration to ensure the successful integration of PEVs into the electrical grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Methods for Microgrid Protection (Literature Review)

This work reviews existing conventional and non-conventional protection schemes for grid- and islanded-connected mode operations in North American microgrid projects. The protection schemes applied for the microgrid projects had different types of distributed energy resources (DERs), and integrated the hydropower/diesel generators, gas/steam/wind turbines and photovoltaic (PV) systems with energy storages. In this work, conventional protection schemes were those defined within the IEEE Standard C37.2-2008, while non-conventional schemes were those not defined within this Standard. The pros and cons of conventional and non-conventional protection schemes applied in microgrid projects were discussed in detail. The overvoltage, undervoltage and frequency elements were the most common conventional protection schemes applied in microgrid projects in North America. These protection elements were used to detect the islanded conditions and faults that could not be sensed by overcurrent relays because the small fault currents contributed by the low-inertia DERs and power-electronic sources. The directional overcurrent elements allowed to distinguish between external (grid) and internal (microgrid) faults. The adaptive protection was the most popular non-conventional protection scheme applied in microgrid projects. The adaptive protection detected if the microgrid was set in grid- or islanding-connected modes and selected the relay settings for the actual microgrid conditions to avoid relays’ misoperations. In conclusion, each microgrid project can confront different types of DERs and operation modes that require individual studies to solve their protection and control challenges, to obtain the best technical and economical solution. The protection scheme results and discussions for North American microgrid projects collected in this report provides an important information to guide protection and control engineers, designers and researchers in defining the protection methods for microgrids based on the types of DERs and grid- or islanded-connected operational modes

24 POWER TRANSMISSION AND DISTRIBUTION↗