At least 1,405 records · Page 78

Measurement Adequacy for Monitoring Data Center Oscillations

Artificial intelligence (AI) training data centers with periodic load profiles can induce sustained grid oscillations across a wide frequency range, making accurate monitoring essential for reliable power system operation. This report evaluates the adequacy of existing measurement systems for monitoring such oscillations, focusing on phasor measurement units (PMUs) and point-on-wave (POW) measurement systems. The analysis shows that while PMUs are highly effective for monitoring low-frequency electromechanical oscillations, they have inherent limitations in accurately representing higher-frequency oscillations due to constraints imposed by reporting rates and the bandwidth of phasor estimation filters. Even when configured with higher reporting rates, the filtering inherent in the phasor estimation process can significantly attenuate oscillation magnitudes, potentially leading to underestimation of oscillatory behavior. This has important implications for compliance and performance monitoring of large loads. To address the limitations associated with PMU-based monitoring, the report examines the use of high-resolution POW measurements, which can capture oscillations across a broader frequency range. However, continuous POW monitoring introduces practical challenges related to large data volumes, communication bandwidth, and real-time data processing. For this reason, the report also discusses emerging approaches that use POW measurements as a complementary capability alongside PMUs to improve observability of oscillations from large data center loads.

47 OTHER INSTRUMENTATION↗

A Green Prison: The Santa Rita Jail Campus Microgrid

A large microgrid project is nearing completion at Alameda County’s twenty-two-year-old 45 ha 4,000-inmate Santa Rita Jail, about 70 km east of San Francisco. Often described as a green prison, it has a considerable installed base of distributed energy resources (DER) including an eight-year old 1.2 MW PV array, a five-year old 1 MW fuel cell with heat recovery, and considerable efficiency investments. A current US$14 M expansion adds a 2 MW-4 MWh Li-ion battery, a static disconnect switch, and various controls upgrades. During grid blackouts, or when conditions favor it, the Jail can now disconnect from the grid and operate as an island, using the on-site resources described together with its back-up diesel generators. In other words, the Santa Rita Jail is a true microgrid, or μgrid, because it fills both requirements, i.e. it is a locally controlled system, and it can operate both grid connected and islanded. The battery’s electronics includes Consortium for Electric Reliability Technology (CERTS) Microgrid technology. This enables the battery to maintain energy balance using droops without need for a fast control system.

25 ENERGY STORAGE↗

Thermal Energy Storage for Electricity Peak-demand Mitigation: A Solution in Developing and Developed World Alike

In much of the developed world, air-conditioning in buildings is the dominant driver of summer peak electricity demand. In the developing world a steadily increasing utilization of air-conditioning places additional strain on already-congested grids. This common thread represents a large and growing threat to the reliable delivery of electricity around the world, requiring capital-intensive expansion of capacity and draining available investment resources. Thermal energy storage (TES), in the form of ice or chilled water, may be one of the few technologies currently capable of mitigating this problem cost effectively and at scale. The installation of TES capacity allows a building to meet its on-peak air conditioning load without interruption using electricity purchased off-peak and operating with improved thermodynamic efficiency. In this way, TES has the potential to fundamentally alter consumption dynamics and reduce impacts of air conditioning. This investigation presents a simulation study of a large office building in four distinct geographical contexts: Miami, Lisbon, Shanghai, and Mumbai. The optimization tool DER-CAM (Distributed Energy Resources Customer Adoption Model) is applied to optimally size TES systems for each location. Summer load profiles are investigated to assess the effectiveness and consistency in reducing peak electricity demand. Additionally, annual energy requirements are used to determine system cost feasibility, payback periods and customer savings under local utility tariffs.

25 ENERGY STORAGE↗

On Distribution Grid Optimal Power Flow Development and Integration

Due to changes in electric distribution grid operation, new operation regimes have been recommended. Distribution grid optimal power flow (DOPF) has received tremendous attention in the research community, yet it has not been fully adopted across the utility industry. Our paper recognizes this problem and suggests a development and integration procedure for DOPF. We propose development of DOPF as a three step procedure of 1) processing the grid, 2) obtaining a tractable solution, and 3) implementing multiple solution algorithms and benchmarking them to improve application reliability. For the integration of DOPF, we demonstrate how a DOPF federate may be developed that can be integrated in a co-simulation environment to mimic the real-world conditions and hence improve its practicality to be deployed in the field. To demonstrate the efficacy of the proposed methods, tests on IEEE 123 bus system are performed where the usage of tractable formulation in DOPF algorithm development and its comparison to the benchmark solution are demonstrated.

Hanif, Sarmad↗

Grid Integration Studies: Data Requirements, Greening the Grid

A grid integration study is an analytical framework used to evaluate a power system with high penetration levels of variable renewable energy (VRE). A grid integration study simulates the operation of the power system under different VRE scenarios, identifying reliability constraints and evaluating the cost of actions to alleviate those constraints. These VRE scenarios establish where, how much, and over what timeframe to build generation and transmission capacity, ideally capturing the spatial diversity benefits of wind and solar resources. The results help build confidence among policymakers, system operators, and investors to move forward with plans to increase the amount of VRE on the grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Marine Hydrokinetic Turbine Power-Take-Off Design for Optimal Performance and Low Impact on Cost-of-Energy: Preprint

Marine hydrokinetic devices are becoming a popular method for generating marine renewable energy worldwide. These devices generate electricity by converting the kinetic energy of moving water, wave motion or currents, into electrical energy through the use of a power-take-off (PTO) system. Most PTO systems incorporate a mechanical or hydraulic drivetrain, power generator, and electric control/conditioning system to deliver the generated electric power to the grid at the required state. Like wind turbine applications, the PTO system must be designed for high reliability, good efficiency, and long service life with reasonable maintenance requirements, low cost, and an appropriate mechanical design for anticipated applied steady and unsteady loads. The ultimate goal of a PTO design is high efficiency and low maintenance and cost, with a low impact on the device cost-of-energy (CoE).

16 TIDAL AND WAVE POWER↗

Advanced Transmission Technologies – GETs and HPCs Session 1: ATT Foundations and Dynamic Line Ratings (DLRs)

The INL TADA GETs Cohort Session 1, held on November 4, 2025, convened experts to address the integration of advanced transmission technologies, including Grid-Enhancing Technologies (GETs) and High Performance Conductors (HPCs), with a focus on digital assurance challenges. The session highlighted the growing importance of cybersecurity, supply chain transparency, reliability, and business risk management in deploying GETs, especially Dynamic Line Ratings (DLRs). Participants examined how expanded attack surfaces, limited vendor pools, and new regulatory requirements—such as FERC Orders 881, 2023, and 1920—are influencing utilities and technology providers. The workshop underscored the need for cyber-informed engineering, secure-by-design principles, and practical risk management strategies, while fostering collaboration and knowledge sharing among industry peers. Technical discussions covered the evolution from static to dynamic line ratings, complexities of cloud-based architectures, and NERC CIP compliance challenges. The session concluded with a collaborative risk exercise and a preview of future workshops on advanced power flow control and transmission topology optimization, reinforcing the cohort’s commitment to advancing digital assurance in the energy sector.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Cyber-physical cascading failure and resilience of power grid: A comprehensive review

Smart grid technologies are based on the integration of the cyber network and the power grid into a cyber-physical power system (CPPS). The increasing cyber-physical interdependencies bring about tremendous opportunities for the modeling, monitoring, control, and protection of power grids, but also create new types of vulnerabilities and failure mechanisms threatening the reliability and resiliency of system operation. A major concern regarding the interdependent networks is the cascading failure (CF), where a small initial disturbance/failure in the network results in a seemingly unexpected large-scale failure. Although there has been a significant volume of recent work in the CF research of CPPS, a comprehensive review remains unavailable. This article aims to fill the gap by providing a systematic literature survey regarding the modeling, analysis, and mitigation of CF in CPPS. The open research questions for further research are also discussed. This article allows researchers to easily understand the state of the art of CF research in CPPS and fosters future work required towards full resolutions to the remaining questions and challenges.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Community-Based Approach to Leading the Nation in Smart Energy Use

Project Objectives The AEP Ohio gridSMART® Demonstration Project (Project) achieved the following objectives: • Built a secure, interoperable, and integrated smart grid infrastructure in northeast central Ohio that demonstrated the ability to maximize distribution system efficiency and reliability and consumer use of demand response programs that reduced energy consumption, peak demand, and fossil fuel emissions. • Actively attracted, educated, enlisted, and retained consumers in innovative business models that provided tools and information reducing consumption and peak demand. • Provided the U.S. Department of Energy (DOE) information to evaluate technologies and preferred smart grid business models to be extended nationally. Project Description Ohio Power Company (the surviving company of a merger with Columbus Southern Power Company), doing business as AEP Ohio (AEP Ohio), took a community-based approach and incorporated a full suite of advanced smart grid technologies for 110,000 consumers in an area selected for its concentration and diversity of distribution infrastructure and consumers. It was organized and aligned around: • Technology, implementation, and operations • Consumer and stakeholder acceptance • Data management and benefit assessment Combined, these functional areas served as the foundation of the Project to integrate commercially available products, innovative technologies, and new consumer products and services within a secure two-way communication network between the utility and consumers. The Project included Advanced Metering Infrastructure (AMI), Distribution Management System (DMS), Distribution Automation Circuit Reconfiguration (DACR), Volt VAR Optimization (VVO), and Consumer Programs (CP). These technologies were combined with two-way consumer communication and information sharing, demand response, dynamic pricing, and consumer products, such as plug-in electric vehicles and smart appliances. In addition, the Project incorporated comprehensive cyber security capabilities, interoperability, and a data assessment that, with grid simulation capabilities, made the demonstration results an adaptable, integrated solution for AEP Ohio and the nation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Reduced-Order Models of Static Power Grids based on Spectral Clustering

For large-scale interconnected power systems that cover large geographical areas, certain electrical studies are required so that appropriate decisions ensure system reliability and low cost. For such studies, it is often neither practical nor necessary to model in detail the entire power system, which is increasingly complex due to a more diverse range of grid assets to choose from in both short and long-term planning. The goal of this paper is to present a methodology to reduce the order of large-scale power networks based on spectral graph theory given that current methods for static network reduction are not scalable. A brief analysis of some spectral clustering properties to determine which graph Laplacian matrix should be used and why is included. The analysis shows that the utilization of the normalized graph Laplacian is more advantageous for clustering purposes. Techniques are proposed to approximate cost functions for the aggregated generators. This is done via linear regression. The reduced-order model obtained with the proposed methodology has an accuracy above 94% and solves the scalability issue commonly present in other reduction methods. If the utilization of the reduced-order model is either constrained to load levels above mid-peak demand, or cost functions of aggregated units are approximated via a piecewise quadratic approach, then the error distribution is in the order of 10^-3. .

Baquedano-Aguilar, Mario D.↗

Cyber-Physical Event Emulation-Based Transmission-and-Distribution Co-Simulation for Situational Awareness of Grid Anomalies (SAGA)

Energy management of transmission and distribution networks (T&D) is becoming more challenging with the accelerated adoption of distributed energy resources (DERs)-such as distributed photovoltaic generation and battery energy storage systems (BESS)-on the electric grid. To better analyze the impacts of DERs on both transmission and distribution systems, a comprehensive T&D co-simulation platform is developed. Further, with DERs more actively participating in system operation-e.g., by providing real-time grid services-their cyber vulnerability needs to be better understood to maintain system reliability. This paper discusses a cyber-physical events emulation-based T&D co-simulation platform to perform comprehensive cyber events emulations, physical simulation, and analysis of interdependent impacts. Results from the case studies-which show how cyber events on a synthetic distribution network can impact operations on the transmission and distribution network-validate that the proposed T&D cosimulation platform can perform cyber-physical events emulation and produce response in near realtime; therefore, with extensive simulation using the proposed co-simulation platform, the system operators can accumulate adequate training data for system situational awareness of grid anomalies.

anomalies detection↗

Numerical homogenization of concrete microstructures without explicit meshes

Life management of electric hydro or nuclear power plants requires to estimate long-term concrete properties on facilities, for obvious safety and serviceability reasons. Decades-old structures are foreseen to be operational for several more decades. As a large number of different concrete formulations are found in EDF facilities, empirical models based on many experiments cannot be an option for a large fleet of power plant buildings. To build predictive models, homogenization techniques offer an appealing alternative. To properly upscale creep, especially at long term, a rather precise description of the microstructure is required. However, the complexity of the morphology of concrete poses several challenges. In particular, concrete is formulated to maximize the packing density of the granular skeleton, leading to aggregates spanning several length scales with small inter particle spacings. Thus, explicit meshing of realistic concrete microstructures is either out of reach of current meshing algorithms or would produce a number of degrees of freedom far higher than the current generic FEM codes capabilities. This paper proposes a method to deal with complex matrix-inclusions microstructures such as the ones encountered at the mortar or concrete scales, without explicitly meshing them. The microstructure is superimposed to an independent mesh, which is a regular Cartesian grid. This inevitably yields so called 'gray elements', spanning across multiple phases. As the reliability of the estimate of the effective properties highly depends on the behavior affected to these gray elements, special attention is paid to them. As far as the question of the solvers is concerned, generic FEM codes are found to lack efficiency: they cannot reach high enough levels of discretization with classical free meshes, and they do not take advantage of the regular structure of the mesh. Thus, a specific finite differences/finite volumes solver has been developed. At first, generic off-the-shelf linear system solvers were used. To further improve the efficiency in terms of memory requirements, specific variants of the preconditioned conjugate gradient were implemented. This allowed to homogenize the conductivity of a concrete-like microstructure using more than 10{sup 9} degrees of freedom on a rather common hardware for 2010 (a PC embedding 48 GB of RAM). Taking benefit of the properties of the regular Cartesian grid we have also investigated a multi-level method to improve the CPU efficiency of the code.

36 MATERIALS SCIENCE↗

Robust, multidimensional mesh motion based on Monge-Kantorovich equidistribution

Mesh-motion (r-refinement) grid adaptivity schemes are attractive due to their potential to minimize the numerical error for a prescribed number of degrees of freedom. However, a key roadblock to a widespread deployment of the technique has been the formulation of robust, reliable mesh motion governing principles, which (1) guarantee a solution in multiple dimensions (2D and 3D), (2) avoid grid tangling (or folding of the mesh, whereby edges of a grid cell cross somewhere in the domain), and (3) can be solved effectively and efficiently. In this study, we formulate such a mesh-motion governing principle, based on volume equidistribution via Monge-Kantorovich optimization (MK). In earlier publications [1, 2], the advantages of this approach in regards to these points have been demonstrated for the time-independent case. In this study, demonstrate that Monge-Kantorovich equidistribution can in fact be used effectively in a time stepping context, and delivers an elegant solution to the otherwise pervasive problem of grid tangling in mesh motion approaches, without resorting to ad-hoc time-dependent terms (as in moving-mesh PDEs, or MMPDEs [3, 4]). We explore two distinct r-refinement implementations of MK: direct, where the current mesh relates to an initial, unchanging mesh, and sequential, where the current mesh is related to the previous one in time. We demonstrate that the direct approach is superior in regards to mesh distortion and robustness. The properties of the approach are illustrated with a paradigmatic hyperbolic PDE, the advection of a passive scalar. Imposed velocity flow fields or varying vorticity levels and flow shears are considered.

99 GENERAL AND MISCELLANEOUS↗

Power System Resilience Metrics Augmentation for Critical Load Prioritization

One of the major goals of new grid operation regimes, such as transactive energy systems (TESs), is to make the power grid more resilient to withstand natural or man-made disasters and potential reliability events, and to continue to serve the maximum number of its customers. But it is a well-known fact to system operators that not all customers are the same. This implies that any discussion of TESs’ impacts on the resilience of the power system should consider the needs of its critical customers (such as the power system operation centers, fire and police stations, and hospitals) over those of other customers. When evaluating the resilience of the system, bonus points must be awarded to any system that could maintain its power supply to critical customers during a disturbance that may cause an outage. This report discusses critical infrastructure (CI) as found in the literature and then categorizes it based on the field to which the operations belong (such as human life/safety-related, operations management, necessary city operation, industrial customers, etc.). Each of these CI categories is further divided into types of critical customers (e.g., the human life/safety-related category has different types of customers like hospitals, fire and police stations, etc.). The entire demand of each of the critical customer types is not categorized as critical load (CL); instead, only a portion of the total load of these critical customers is characterized as critical load. This is done based on the categories of equipment, the function of which is crucial in the operation of the overall facility. CL categorization is performed to provide the ratio of the critical load portion to the overall load , so that it can serve as a parameter in the resilience evaluation of the grid through a metrics-based approach. Such categorization is important as it helps to augment the existing quantifiable resilience metrics with CL categorization. The metrics for a power system need to not only consider how well a system performed during a disturbance event, but also how it reduced strain and supplied power to its CLs. The first step in this process is characterize CLs in the system. After CL characterization, the next step is the inclusion of these loads in the resilience metrics. To that end, in this report weight-based augmentation of resilience metrics is proposed, where certain customers (the ones that are categorized as critical) are assigned higher weights than others. Though an overview of assigning weights to customers is discussed, there is no one-size-fits-all approach for every power system. The decisions made about assigning such weights to customers vary greatly from one operator to another, based on their unique systems and the current and predicted states of critical customers. This decision-making can include the type of disturbance event, which might only affect certain parts of the system. In general, analyzing critical customers before an event helps understand system vulnerabilities. It also helps in planning and conducting operations during the event, evaluating system performance after the event, and supporting better planning for future events. An alternative to the current practices of managing the grid for outages is an innovative TES, which has the potential to provide a platform for including distributed energy resources for managing CLs. This report also describes how TES qualities can help (1) to maintain power supply to critical customers for uninterrupted operations and (2) to restore lost power supply to the critical customers rapidly.

24 POWER TRANSMISSION AND DISTRIBUTION↗

The Future Role of Hydropower in the Northeastern United States: May 2020-May 2022

This paper explores the future role of hydropower in the Northeastern US and beyond. The intent is to provide experience-based insights into how hydropower can best support the reliable and economic evolution of the New England power system and, more broadly, all US grids. Many of the challenges facing New England are driven by the potential integration of 10s of GWs of variable energy resources. Hydro can assist in remediating several issues, and the paper explores how Hydro might hit above its weight in a future low carbon New England system. Hydro can assist in handling periods of over generation, reduce the risk of curtailment of zero carbon resources, improve market efficiency, and provide valuable essential reliability services.

13 HYDRO ENERGY↗

Trial Implementation of a Multihazard Risk Assessment Framework for High-Impact Low-Frequency Power Grid Events

The Pacific Northwest National Laboratory developed a risk framework for modeling high-impact, low-frequency power grid events to support risk-informed decisions. In this research article, we briefly recap the framework and demonstrate its implementation for seismic and geomagnetic hazards using a benchmark reliability test system. We describe integration of a collection of models implemented to perform hazard analysis, fragility evaluation, consequence estimation and post-event restoration. We demonstrate the value of the framework as a multi-hazard power grid risk assessment and management tool. The research will benefit transmission planners and emergency planners by improving their ability to maintain a resilient grid infrastructure against impacts from major events.

power grid, risk assessment, seismic hazard, dynam↗