The Impact of the Lightning Surge on SiC-based Medium-voltage Three-phase Four-wire Grid-connected Converters
The surge voltage induced by lightning will generate an inrush current in a grid-connected converter. It may not be large in Si-based converters because of the large grid side inductive filter. However, for SiC-based multi-level converters, the inrush current could be very large due to the small filter inductance, which is selected based on the current harmonic consideration. Most previous work focuses on system-level lightning protection while the converter-level impact, especially the internal components of the converter, is rarely discussed. This paper presents the analysis of the impact of the lightning surge on a 10 kV SiC MOSFET-based 13.8 kV three-phase four-wire grid-connected converter. The IEEE arrester model and the combined wave generator model in IEC 61000-4-5 standard are used to evaluate the inrush current, DC-link overvoltage, and component-to-ground potential of the converter. Analysis and simulation results have been provided to demonstrate the impact of lightning on the grid-connected converter. It is found that large inrush current occurs due to the small filter inductance, and the neutral-to-ground impedance impacts both the inrush current and the neutral point-to-ground potential.