Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “power system event”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 127 records · Page 7

PV Inverter Testing for Momentary Cessation and Rate-of-Change-of-Frequency Events: Preprint

To understand the power system stability and develop better electromagnetic transient (EMT) models of field deployed photovoltaic (PV) inverters, it is important to characterize inverters' response to abnormal voltage and frequency scenarios. Because EMT models are not typically available for small distribution-connected PV inverters, and because inerterconnection standards historically did not specify desired ride-through behaviors, we tested two such inverters in the lab to characterize their responses to severe undervoltage events and high rate-of-change-of-frequency (ROCOF) conditions. The inverters tested were pre-IEEE 1547-2018 residential PV inverters widely used in the Hawaiian Electric territory and many other areas. The testing results for undervoltage scenarios showed that the inverter from one vendor exhibited momentary cessation while the inverter from the other vendor did not exhibit momentary cessation behavior or tripping for most of the events below the 120 ms undervoltage trip threshold duration set by IEEE 1547-2003. The testing results for ROCOF scenarios showed that the inverter from one vendor temporarily lost synchronization during ROCOF conditions while the inverter from the other vendor did not lose synchronization or cease generation for any ROCOF conditions. Both the inverters were also tested for EMT-simulated grid events with severe changes in frequency and voltage. The observed responses of the inverters were different from the simulated response of PV inverters represented the best available assumptions from pre-existing information. The results from these experiments can be used to update the inverter models used in bulk power system studies.

IEEE 1547 2018↗

AI-Based Protective Relays for Electric Grid Resiliency

The protection systems (circuit breakers, relays, reclosers, and fuses) of the electric grid are the primary component responding to resilience events, ranging from common storms to extreme events. The protective equipment must detect and operate very quickly, generally <0.25 seconds, to remove faults in the system before the system goes unstable or additional equipment is damaged. The burden on protection systems is increasing as the complexity of the grid increases; renewable energy resources, particularly inverter-based resources (IBR) and increasing electrification all contribute to a more complex grid landscape for protection devices. In addition, there are increasing threats from natural disasters, aging infrastructure, and manmade attacks that can cause faults and disturbances in the electric grid. The challenge for the application of AI into power system protection is that events are rare and unpredictable. In order to improve the resiliency of the electric grid, AI has to be able to learn from very little data. During an extreme disaster, it may not be important that the perfect, most optimal action is taken, but AI must be guaranteed to always respond by moving the grid toward a more stable state during unseen events.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Ultra High-Temperature Magnetic Bearing System for s-CO 2 Turbines/Expanders. Phase II Final Report

The goal of this project is to design and construct of a prototype of ultra-high temperature permanent magnet (UHT–PM), which provides the force to pull the spinning shaft towards the target position in the magnetic bearing (MB) clearance circle. This project will develop a PM biased MB system, that is actively cooled to the 550°C maximum operating temperature limit of PMs. The MB test environment will include 700°C, 40krpm and 4,000 psi requirements to advance the supercritical carbon dioxide (sCO 2 ) and other types of Brayton power cycle systems. The proposed novel MBs combine PMs for supplying the bias field and electromagnets for supplying the control field, both in UHT conditions. The choice of material is the UHT Sm-Co PMs (US patent 6,451,132) due to their significantly better thermal stability. The 6-pole homopolar design permits uninterrupted force delivery via a redundant control capability (US patent 7,429,811) even if 3 poles were to fail. The Phase I efforts was to focus on development and demonstration of component technologies and detailed design of full scale components and a demonstrator test rig for use in Phase II. UHT–PMs were produced and used in the MB actuator. The operating environment of the EEC-T550 Sm-Co magnet material could be extended by implementing active cooling. Electromagnetic coils imbedded in the MB provide forces to stabilize the shaft position at the target via sensing and control stages. Shaft position sensors enable to identify the present position of the spinning shaft relative to its desired target position in the MB clearance circle (air gap). Auxiliary bearings will be installed to provide a backup support system in the event that power to the MB fails or there is a fault in a device providing current to the MB coils. For control, reliability and safety reasons the sensors and auxiliary bearings are typically located as close as possible to the MBs, which exposes them to the same environmental conditions. Development of only the actuator for the UHT environment is an inadequate approach to complete integration of the MB system in the turbine/expander. Therefore the UHT sensor and auxiliary bearing were designed and developed along with the actively cooled, UHT-PM actuator development. Although shaft position sensors are commercially available (Kaman) they may cost up to $10k per channel, and a full 5 axis magnetic suspension is best implemented with up to 20 sensors. Once successfully completed, this project will significantly extend the operating environment capability for turbomachinery applications such as nuclear power, concentrated solar thermal, fossil fuel, geothermal, and shipboard propulsion. The further advancement of UHT-PM-MB will also strengthen the US position in PM technology, which is presently heavily dominated by China. The UHT Sm-Co magnet material that will be utilized in the proposed work has been developed exclusively by the project proposer. Many actuators, motors, generators and other MB applications will greatly benefit from the proposed work.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Resilience Metrics for Building-Level Electrical Distribution Systems with Energy Storage

The energy system infrastructure that delivers power to a building's loads needs to be resilient to withstand and recover from extreme outages (e.g., grid faults that leave millions of people without power during severe weather events). Building-level electrical distribution systems (BEDSs) distribute power from a building's energy sources - including the grid, solar photovoltaic (PV) panels, and batteries - to its loads, including lighting, HVAC, and plug loads. BEDS with storage can provide resilience by distributing local electricity supply to critical loads during an outage. Quantitative metrics are needed to assess the resilience improvements associated with new BEDS and storage system technologies. In this paper, we apply an existing metric, the probability of outage survival curve (POSC), to BEDS with storage and propose novel metrics that improve upon POSC. Through a simulation-based case study, we demonstrate how these metrics are impacted by the BEDS design and how they can be used to design a resilient system.

buildings↗

Surface roughness due to residual ice in the use of low power deicing systems

Thicknesses of residual ice are presented to provide information on surface contamination and associated roughness during deicing events. Data was obtained from low power ice protection systems tests conducted in the Icing Research Tunnel at NASA Lewis Research Center (LeRC) with nine different deicing systems. Results show that roughness associated with residual ice is not characterized by uniformly distributed roughness. Results also show that deicing systems require a critical mass of ice to generate a sufficient expelling force to remove the ice.

Shin, Jaiwon↗

Surface roughness due to residual ice in the use of low power deicing systems

Thicknesses of residual ice are presented to provide information on surface contamination and associated roughness during deicing events. Data was obtained from low power ice protection systems tests conducted in the Icing Research Tunnel at NASA Lewis Research Center (LeRC) with nine different deicing systems. Results show that roughness associated with residual ice is not characterized by uniformly distributed roughness. Results also show that deicing systems require a critical mass of ice to generate a sufficient expelling force to remove the ice.

Shin, Jaiwon↗

Resilience Metrics for Building-Level Electrical Distribution Systems with Energy Storage: Preprint

The energy system infrastructure that delivers power to a building's loads needs to be resilient, such that it can withstand and recover from extreme outages (e.g., grid faults that leave millions of people without power during severe weather events). Building-level electrical distribution systems (BEDSs) distribute power from a building's energy sources - including the grid, solar photovoltaic (PV) panels, and batteries - to its loads, including lighting, HVAC, and plug loads. BEDS with storage can provide resilience by distributing local electricity supply to critical loads during an outage. Quantitative metrics are needed to assess the resilience improvements associated with new BEDS and storage system technologies. In this paper, we apply an existing metric, the probability of outage survival curve (POSC), to BEDS with storage and propose a set of novel metrics that improve upon POSC. Through a simulation-based case study, we demonstrate how these metrics are impacted by the BEDS design and how they can be used to design a resilient system.

buildings↗

Is a Generator the Only Solution When the Grid Fails? Optimizing Systems for Resiliency and Carbon Reduction: Preprint

Traditionally, buildings are dependent on utility infrastructure, and when a grid failure happens, end users rely on the closest source of energy storage to sustain operation until power is restored. For buildings, that typically means using an electric generator. This electric generator either uses on-site energy storage such as fossil fuels in a tank or a gas connection which is, in turn, tied to gas wells—also a form of energy storage. Generators are popular for their ease of implementation and low capital costs; however, they have limited value outside of disruptions, and they are a source of scope 1 emissions, or direct greenhouse gas emissions from sources controlled by the building owner. In contrast, some power generation and storage systems, such as photovoltaic (PV) panels and battery energy storage systems (BESS), can serve the same purpose during grid disruptions while presenting advantages outside of power failure. This paper explores methods for storing and converting energy on-site to increase building resiliency, focusing on solutions that minimize scope 1 emissions. We analyze the cost and carbon impacts of energy efficiency measures, PV arrays, and BESS, with and without generators, in a simulation test case. We find significant benefits can be achieved both during and outside of power failure events when designing systems that integrate the on-demand capability of generators, the low carbon energy supplied by PV, and the storage capabilities of BESS. Specifically, adding even minimal BESS and PV can result in downsizing the generator, increasing generator efficiency and requiring less fuel.

ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION↗

Assessment of the Electrical Substation-Grid Testbed with Inside/Outside Devices and Distributed Ledger Technology

The electrical substation-grid testbed was created to integrate the GOOSE and/or DNP (Distributed Network Protocol) messages with time synchronized sources and Distributed Ledger Technology (DLT). The objective was to study the impact of faults and cyber-events at an electrical substation with inside (protective relays) and outside (power meters) substation devices. The electrical substation-grid testbed was based on the design of a 34.5/ 12.47 kV electrical substation (sectionalized bus configuration) with two power transformers, connected to radial power lines and load feeders. The electrical substation-grid testbed was installed at 252 lab space (Advanced Power System Protection), Grid Research Integration and Deployment Center (GRID-C), Oak Ridge National Laboratory. This testbed was created for Task 5, DarkNet project. The electrical substation-grid testbed was created to simulate fault and/or cyber events that could potentially result in damage to the electrical infrastructure. In addition, tests were run that are usually not allowed to be performed in an operational electrical power grid, because these test scenarios could trip breakers and/or generate fault situations that could potentially damage equipment. The number of tests performed in the electrical substation-grid testbed were executed in a better way than in a real electrical substation and/or power grid, because multiple tests could be run in a short period of time, and complex permits, and safety/ schedule restrictions like in a real electrical substation environment were not needed. The electrical substation-grid testbed was created using real measurement, communication, and protection devices that are used by electrical utilities, to have same conditions that we could observe in a real power grid or electrical substation. The electrical substation-grid testbed was based on using a real time simulator and expansion box with amplifiers that were wired to electrical substation-grid devices. This hardware-in-the-loop (HIL) was provided by protective relays, power meters, ethernet switches, remote terminal units, synchronized timing network clock, DLT devices, workstations, and servers. This report includes the design, installation, and assessment of the electrical substation-grid testbed that was similar to an operational electrical substation, integrating the power system protection, communication, and control systems. The results for the electrical substation-grid testbed were based on:• verifying the analog signals for protective relays and power meters, • observing the synchronized time source frame at devices, • authenticating the GOOSE (IEC 61850) and DNP messages from power meters and protective relays, and • verifying the trip conditions of protective relays at fault tests with the power system fault event detection, using DLT devices. For future work, the electrical substation-grid testbed with protective relays and power meters, using DLT and synchronized time source from DarkNet, will be used to study the impact of cyber-events at inside and outside substation devices. Advanced algorithms for detecting cyber-events produced by non-desired protective relay settings will be studied, to improve the detection and reliability of protection, control, and communication systems at power grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Visualizing Fault Induced Traveling Waves In Medium Voltage Systems

Traveling waves are induced in power systems during most transient events in the grid. These waves travel close to the speed of light in overhead lines and 50% to 60% the speed of light in underground cables. Even though traveling wave-based protection schemes for transmission systems are available commercially, traveling waves in medium voltage distribution networks are still in research space. Compared to transmission system, medium voltage distribution systems contain more reflections and refractions. Thus, visualization is challenging and is critical in locating faults in distribution network. To address this visualization challenge, this paper presents an open-source tool to visualize the traveling waves using Bewley lattice approach. The developed visualization tool will be useful for the protection engineers to detect and triangulate fault locations in the medium voltage systems and isolate the faults.

Bewley Lattice↗

Designing resilient decentralized energy systems: The importance of modeling extreme events and long-duration power outages

Mitigating and adapting to climate change requires decarbonizing electricity while ensuring resilience of supply, since a warming planet will lead to greater extremes in weather and, plausibly, in power outages. Although it is well known that long-duration outages severely impact economies, such outages are usually not well characterized or modeled in grid infrastructure planning tools. Here, we bring together data and modeling techniques and show how they can be used to characterize and model long-duration outages. We illustrate how to integrate outages in planning tools for one promising mode of resilient energy supply—microgrids. Failing to treat these extremes in models can lead to microgrid designs (1) that do not realize their full value of resilience, since models do not see the benefits of protecting against extremes, and (2) that appear reliable on paper yet do not actually protect against extremes. Although utilities record power interruptions, lack of access to that data is hindering research on resilience; making datasets available publicly would substantially aid efforts to improve grid planning tools.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Current Practices in Distribution Utility Resilience Planning for Winter Storms

This report is part of a series of hazard-focused case studies examining common practices in electric utility resilience planning. We use standard terminology defining resilience as the ability to anticipate, withstand, absorb, and recover from hazards that cause long duration outages. We distinguish between reliability and resilience using Institute of Electrical and Electronics Engineers (IEEE) 1366-2022, which defines major events as an event that exceeds reasonable design and/or operational limits of the electric power system. Resilience planning is focused on major event days and reliability planning is focused on nonmajor event days. Utility resilience plans are assessed according to common resilience components identified in existing resilience frameworks. The focus of this report is on winter storms in which the primary hazards are heavy snowfall, freezing rain, ice, extreme cold, severe wind, and flooding. These hazards can also contribute to generation shortages, resulting in bulk power system impacts that have consequences for the distribution system, such as load shedding. Stand-alone reports focusing on wildfires and nonwinter storms have been published in parallel with this report. This report can be used as a starting point for understanding potential investment prioritization processes and investment options. This report is intended to improve utility resilience planning by supporting constructive dialogue among utilities, regulators, and other stakeholders.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Optimal Network Reconfiguration and Scheduling With Hardware-in-the-Loop Validation for Improved Microgrid Resilience

With the increased occurrence of various major extreme weather events, power outages and prompt power system restorations have recently drawn more attention to the resilience and recovery of power systems. From the perspective of a more resilient power delivery at the distribution grid, system restoration using network topology reconfiguration together with optimal scheduling of distributed energy resources are adopted in this paper. The proposed optimization model aims at minimizing the total load shedding cost and other operational costs, in which linearized topological constraints borrowed from graph theory and linearized DistFlow models are respectively used to maintain the radial network topology and power flow balance after system contingencies. To demonstrate the applicability of the proposed strategy, a real-world case study of a networked three-microgrid system in Adjuntas, Puerto Rico, is used with the consideration of different independent/interconnected microgrid scenarios, contingencies, and fairness settings. Furthermore, hardware-in-the-loop testing is conducted for the same three-microgrid network, where the closely matched results with the simulated ones have validated the effectiveness of the proposed restoration strategy, which is now ready to move one step forward towards field deployment. Finally, to test the proposed restoration strategy in a larger networked system, the modified IEEE-33 bus test distribution system is considered, and the results show a more resilient power delivery for critical loads under three and four line outages.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Universal Utility Data Exchange (UUDEX) - Workflow Design - Rev 1

This workflow design document describes the process of establishing a Universal Utility Data Exchange (UUDEX) Connection between two or more UUDEX Endpoints. The existing processes required to establish a data link using Inter Control Center Communications Protocol (ICCP) are very time consuming, from both the perspectives of effort and calendar time. The intent of UUDEX is to provide a more streamlined alternative. The UUDEX Workflow is also used to establish UUDEX Connections to exchange data other than that found in traditional ICCP data exchanges such as exchanges of power system model files, security events and mitigations, disturbance reports, and market data.

97 MATHEMATICS AND COMPUTING↗

Start Up Application Concerns with Field Programmable Gate Arrays (FPGAs)

This note is being published to improve the visibility of this subject, as we continue to see problems surface in designs, as well as to add additional information to the previously published note for design engineers. The original application note focused on designing systems with no single point failures using Actel Field Programmable Gate Arrays (FPGAs) for critical applications. Included in that note were the basic principles of operation of the Actel FPGA and a discussion of potential single-point failures. The note also discussed the issue of startup transients for that class of device. It is unfortunate that we continue to see some design problems using these devices. This note will focus on the startup properties of certain electronic components, in general, and current Actel FPGAs, in particular. Devices that are "power-on friendly" are currently being developed by Actel, as a variant of the new SX series of FPGAs. In the ideal world, electronic components would behave much differently than they do in the real world, The chain, of course, starts with the power supply. Ideally, the voltage will immediately rise to a stable V(sub cc) level, of course, it does not. Aside from practical design considerations, inrush current limits of certain capacitors must be observed and the power supply's output may be intentionally slew rate limited to prevent a large current spike on the system power bus. In any event, power supply rise time may range from less than I msec to 100 msec or more.

Katz, Richard B.↗

Visualizing Fault Induced Traveling Waves in Medium Voltage Systems: Preprint

Traveling waves are induced in power systems during most transient events in the grid. These waves travel close to the speed of light in overhead lines and 50% to 60% the speed of light in underground cables. Even though traveling wave-based protection schemes for transmission systems are available commercially, traveling waves in medium voltage distribution networks are still in research space. Compared to transmission system, medium voltage distribution systems contain more reflections and refractions. Thus, visualization is challenging and is critical in locating faults in distribution network. To address this visualization challenge, this paper presents an open-source tool to visualize the traveling waves using Bewley lattice approach. The developed visualization tool will be useful for the protection and safety engineers to detect and triangulate fault locations in the medium voltage systems and isolate the faults.

Bewley Lattice↗

Impact of Wildfires on Solar Resource Availability in California in a Changing Climate

Wildfires can emit large amounts of atmospheric particulate matters and influence not only air quality but also availability of photovoltaic (PV) generation due to scattering and absorption of solar radiation. Under anthropogenic changing climate, wildfire activity is projected to increase over western North America due to drier and warmer climate, implying increasing impact on solar resource and larger uncertainty in solar generation especially in regions with faster PV penetration. This study focuses on quantifying the impact of wildfires on aerosol optical depth (AOD) and thus solar resource over California using National Solar Radiation Database (NSRDB), developed by the National Renewable Energy Laboratory (NREL). This assessment includes historical analysis and estimation of solar resource under wildfire scenarios (2020 wildfire and an enhanced wildfire scenario based on 2020 wildfires). Historical analysis for the period of July-October 2019/2020 (low/high fire activity period) shows that the averaged global horizontal irradiance (GHI) and direct normal irradiance (DNI) are reduced by about 30 and 90 W m-2 (5.6 and 15.3%), respectively, during high fire activity period. To create AOD dataset for enhanced fire scenario, 165% increase in burn area (in around 2050) is selected based on comprehensive literature review, which is further applied to the Fire INventory from NCAR (FINN) fire emission. WRF-Chem model with the enhanced FINN emissions is used to simulate and represent a preserving spatial distribution of burned areas and wildfire-emitted aerosols. Our initial analysis suggests that the"enhanced 2020 wildfire" AOD can increase by a factor of 1.3 - 2, which can significantly reduce solar irradiance and increase uncertainty in generation and reliability of power system in extreme wildfire events under a high solar penetration scenario. Overall, this study provides an estimate of the impacts of wildfires on solar resource to make informed decisions on reserve planning, generation scheduling, and reliability investments.

aerosol optical depth↗