At least 127 records · Page 7

Integration of renewable energy generation and storage systems for emissions reduction in an islanded campus microgrid

Microgrid connected building communities are projected to play an integral part in the clean energy transition. These types of systems, when integrated with distributed energy resources (DERs) such as combined heat and power (CHP), district heating and cooling, renewable generation, and energy storage, can provide clean, reliable power to critical facilities and vulnerable communities. The intermittent nature of renewable generation is a challenge when integrating renewables into any grid system, but particularly in islanded microgrids. The University of Texas at Austin (UT) operates an islanded microgrid powered by a CHP plant, while also utilizing district heating and cooling systems and thermal energy storage (TES). High fidelity operating data was used to develop a validated reduced order model of UT’s integrated campus energy systems to serve as a testbed for use in a case study. Hypothetical renewable energy installations on land owned by UT in west Texas were modeled and integrated into the validated campus models along with battery energy storage (BES). Simulations showed that a combination of renewable energy from wind, and optimally controlled 24-hour thermal and battery storage systems could reduce carbon dioxide emissions on campus by 45.4%. The additional retrofit of burner systems to utilize hydrogen natural gas blends resulted in an overall annual emissions reduction of 54.7%. Carbon capture and storage eliminated the majority of the remaining emissions with increased plant energy expenditure. The presented simulations display the practical limitations of a CHP system complemented by renewable generation and short-term storage in eliminating emissions. Furthermore, results highlight the need for further research and development in long duration storage technologies and hydrogen fueled turbines to increase penetration of renewable energy and reduce emissions.

CHP↗

Impact of Geothermal District Heating System on Flexibility of Microgrid in Tuttle, Oklahoma

Flexibility is the capability of the power grid to maintain a balance between electricity generation and variable demand. This study presents preliminary results evaluating the impact of geothermal district heating systems on the flexibility of microgrid in Tuttle, Oklahoma. Heating demand profiles were modeled using EnergyPlus for the district that includes two schools and 250 single-family houses. Then, geothermal energy production was modeled using GEOPHIRES to estimate how much heating demand in the district can be supplied by five different geothermal system scenarios. The results indicated that geothermal energy production varied depending on the resource temperature at different depths, system configurations, and flow rates. For the grid flexibility analysis, electricity consumptions in the five geothermal systems were estimated for pump operations to circulate water from the wells to radiators, while electricity consumption by air-source heat pump in the base case was estimated to supply the same heating load. Electricity consumption in the geothermal systems was significantly lower than those in base cases. The electricity saved by the geothermal system was then incorporated into the microgrid electrical load profiles where variable renewable electricity generation is significantly high. The results visually showed that geothermal district heating system can improve grid flexibility as a baseload during the winter season. The results also highlighted potential opportunities to save energy costs that will be further analyzed in future study.

Cambium↗

Impact of Geothermal District Heating System on Flexibility of Microgrid in Tuttle, Oklahoma: Preprint

Flexibility is the capability of the power grid to maintain a balance between electricity generation and variable demand. This study presents preliminary results evaluating the impact of geothermal district heating systems on the flexibility of a conceptual microgrid in Tuttle, Oklahoma. Heating demand profiles were modeled using EnergyPlus for the district that includes two schools and 250 single-family houses. Then, geothermal energy production was modeled using GEOPHIRES to estimate how much heating demand in the district can be supplied by five different geothermal system scenarios. The results indicated that geothermal energy production varied depending on the resource temperature at different depths, system configurations, and flow rates. For the grid flexibility analysis, electricity consumptions in the five geothermal systems were estimated for pump operations to circulate water from the wells to radiators, while electricity consumption by air-source heat pump in the base case was estimated to supply the same heating load. Electricity consumption in the geothermal systems was significantly lower than those in base cases. The electricity saved by the geothermal system was then incorporated into the microgrid electrical load profiles where variable renewable electricity generation is significantly high. The results visually showed that geothermal district heating system can improve grid flexibility as a baseload during the winter season. The results also highlighted potential opportunities to save energy costs that will be further analyzed in future study.

Cambium↗

Chapter 11: Renewable Microgrids as a Foundation of the Future Sustainable Electrical Energy System

Renewable microgrids are an integral part of the future sustainable energy system. This chapter focuses on the role of renewable energy-based microgrids in the electricity system transformation. It is seen as a foundation that complements large-scale generation plants and high-voltage transmission lines by providing additional flexibility and resilience. This flexibility and resilience are crucial for balancing the energy system and ensuring its long-term sustainability, given the changing supply and demand patterns due to rooftop solar photovoltaics (PV), battery storage, electric mobility, and heat pumps. It is also an opportunity for residential and commercial consumers to become active participants in the energy market. Innovation, new technologies and business models will act as the key enabler for this transformation. The regulatory restructuring of the energy market will be crucial for successful integration of prosumers and aggregated energy communities. The chapter presents the vision of a sustainable, decentralized, and digitized energy future including market potential, most innovative case study projects and start-up companies, and the shifts needed in the regulatory landscape.

battery storage↗

A Fast Dynamic Internal Predictive Power Scheduling Approach for Power Management in Microgrids: Preprint

This paper presents a Dynamic Internal Predictive Power Scheduling (DIPPS) approach for optimizing power management in microgrids, particularly focusing on external power exchanges among diverse prosumers. DIPPS utilizes a dynamic objective function with a time-varying binary parameter to control the timing of power transfers to the external grid, facilitated by efficient usage of energy storage for surplus renewable power. The microgrid power scheduling problem is modeled as a mixed-integer nonlinear programming (MINLP-PS) and subsequently transformed into a mixed-integer linear programming (MILPPS) optimization through McCormick's relaxation to reduce computational complexity. A predictive window window with 6 data points is solved at an average of 0.92s, a 97.6% improvement over the 38.27s required for the MINLP-PS formulation, implying the numerical feasibility of the DIPPS approach for real-time implementation. Finally, the approach is validated against a static objective using real-world load data across three case studies with different time-varying parameters, demonstrating the ability of DIPPS to optimize power exchanges and efficiently utilize distributed resources while shifting the external power transfers to specified time durations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Bi-Level Adaptive Storage Expansion Strategy for Microgrids Using Deep Reinforcement Learning

Battery energy storage (BES) is a versatile resource for the secure and economic operation of microgrids (MGs). Prevailing stochastic optimization-based approaches for BES expansion planning for MGs are computationally complicated. This work proposes a data-driven bi-level multi-period BES expansion planning framework to determine the siting, sizing, and timing of BES installations. The proposed planning framework unifies deep reinforcement learning (DRL) and linear programming, thereby decoupling the determinations for the integer and continuous decision variables in two time scales, respectively. In the upper level, a rainbow DRL agent with quantile regression is trained to provide dynamic planning policies to accommodate stochastic renewable energy resources (RESs), load, and battery price changes efficiently. Further, the lower level computes the optimal operation of MGs with frequency constraints to hedge the islanding contingency. The two levels communicate with one another by exchanging storage configuration and operating expenses in order to accomplish the shared goal of minimizing investment and operation costs. Comparative case studies on an MG are carried out to demonstrate the superiority of the proposed DRL-based solution to the mixed-integer linear programming counterpart on efficiency, scalability, and adaptability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Decentralized Approach for Modeling Organized Convection Based on Thermal Populations on Microgrids

Abstract In this study, a spectral model for convective transport is coupled to a thermal population model on a two‐dimensional horizontal “microgrid,” covering the typical gridbox size of general circulation models. The goal is to explore new ways of representing impacts of spatial organization in cumulus cloud fields. The thermals are considered the smallest building block of convection, with thermal life cycle and movement represented through binomial functions. Thermals interact through two simple rules, reflecting pulsating growth and environmental deformation. Long‐lived thermal clusters thus form on the microgrid, exhibiting scale growth and spacing that represent simple forms of spatial organization and memory. Size distributions of cluster number are diagnosed from the microgrid through an online clustering algorithm, and provided as input to a spectral multiplume eddy‐diffusivity mass flux scheme. This yields a decentralized transport system, in that the thermal clusters acting as independent but interacting nodes that carry information about spatial structure. The main objectives of this study are (a) to seek proof of concept of this approach, and (b) to gain insight into impacts of spatial organization on convective transport. Single‐column model experiments demonstrate satisfactory skill in reproducing two observed cases of continental shallow convection. Metrics expressing self‐organization and spatial organization match well with large‐eddy simulation results. We find that in this coupled system, spatial organization impacts convective transport primarily through the scale break in the size distribution of cluster number. The rooting of saturated plumes in the subcloud mixed layer plays a key role in this process.

54 ENVIRONMENTAL SCIENCES↗

Network reconfiguration and distributed energy resource scheduling for improved distribution system resilience

Electric utility companies work to restore as much load as possible after power outages caused by extreme weather events. In this paper, an outage management strategy is proposed to enhance distribution system resilience through network reconfiguration and distributed energy resources (DERs) scheduling. After a line fault, the proposed algorithm can identify radial network topology based on the rank of the incidence matrix. The reconfiguration is implemented by switching tie lines and sectionalizing lines. With the new network topology, an optimal DER scheduling problem is solved to minimize the accumulative cost for dispatchable DER operation and load reduction. Finally, the optimal topology that minimizes the accumulative cost is selected from all radial topologies. The computational workload is relatively low because only linear programming needs to be solved. Using the case studies of the IEEE 69-bus and IEEE 123-bus systems, we consider the worst-case scenarios in which faults occur in the upstream feeder. The simulation results demonstrate that the proposed strategy allows for a relatively high percentage of the load to remain in service after line faults. Furthermore, compared with microgrid-formation approaches, the proposed strategy has advantages when applied to the distribution systems with several normally-open tie lines and low DER penetration.

42 ENGINEERING↗

Irrigation Modernization Task 4: Accelerating Energy Solutions (FY2022 Final Report)

This report offers insights on energy solutions for irrigation modernization that serve the needs of farmers as well as residents and industry in the local community. Solutions are found in the irrigation districts where local generation from renewable energy sources – solar, hydro, and wind – can be combined with energy storage and customer loads. These combined resources configured in microgrids can lower costs during peak loads and provide resiliency by maintaining electricity supply during outages. The goal of this project, as stated in the FY2022 AOP, is to promote realization of energy solutions that are tailored to physical location, community, infrastructure, and energy value streams. Further, it is to develop examples of how to increase value of, and overcome barriers to, energy solutions in the context of irrigation modernization. In pursuit of that goal, the project looked at options for: 1) Reducing the cost of energy consumed in irrigation systems, 2) Increasing the revenue from surplus power generation, and 3) Deploying new power generation configured as part of a local microgrid. Potential solutions to reducing energy costs and increasing surplus power revenue revolve around addressing regulatory and legal constraints tied to how power is purchased by and sold to the irrigator or irrigation district. Some headway was made in identifying barriers and ways to push utilities to be more accommodating to distributed energy sources; however, for the most part, real progress hinges on changes at the regulatory and legislative level. Deployment of local, renewable generation systems can be implemented provided the economics of the project and the location are favorable. In concert with Famers Conservation Alliance and Energy Trust of Oregon, a number of approaches were studied in the past year, including off-grid solar powered pumps, grid-tied community solar projects, and in-conduit canal hydropower systems. Ultimately three viable projects were identified: 1) North Unit Irrigation District/City of Redmond, Oregon Critical Facility Microgrid – offers combined in-conduit hydro and solar power generation. 2) Wallowa County/Joseph, Oregon Irrigation System Upgrades – centered on upgrades to a non-powered dam that will add a turbine as well as in-conduit power in canal feeders downstream. 3) Medford, Oregon Wastewater Treatment Plant Biogas Cogeneration System – centered on building out biogas storage and grid upgrades to power the plant, sell excess power, and provide emergency backup power (supplanting a diesel generator). Each of these projects has characteristics that broaden the understanding of the value of microgrids employing renewable energy to achieve resiliency and net-zero carbon goals. The first two projects are centered on new hydropower systems. Although the Medford project is only tangentially tied to an irrigation district, it was selected for study analysis as it was the only one mature enough (with sufficient data) to complete an analysis within this project year. Thus, we chose to move forward developing a case study, in concert with the Community Water-Power Resilience project, to demonstrate a method for evaluating such projects. Essentially, this case study serves as a template for studies to be carried out next year that more directly involve irrigation system hydropower, e.g., the project at the Wallowa County/Joseph, Oregon Irrigation System. Lastly, it is recognized that the locations and case studies in this report are all located in Oregon. We recognize this as a limitation. While the intent is not to ignore other states or regions, this result is driven by the fact that we have cultivated a collaboration with non-profit entities in Oregon that focus on these topics – Farmers Conservation Alliance and Energy Trust of Oregon. These partners were central to identifying projects that may be good fits for this program. A goal in the coming year is to establish collaboration with entities in other states/regions that, similarly, can connect us to potential projects in their geographic area. The potential benefits from the WPTO’s support for demonstration projects as energy solutions in irrigation districts include: (1) Alternative power supplies for communities and farms using renewable, carbon-free energy resources, (2) Cost savings for electricity for communities and farms, (3) Resiliency of power supplies for critical loads when electricity from the grid is not available, (4) Resiliency of power supplies for critical infrastructure in the event of catastrophic events, and (5) Demonstration of irrigation modernization projects that provide resilience and a reduced carbon footprint to irrigation districts and nearby communities. These deployments can serve as vanguards/archetypes spurring similar projects in other districts and states.

13 HYDRO ENERGY↗

Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition

Power systems are transforming with increasing levels of inverter-based resources (IBRs). This transformation requires critical roles of grid-forming (GFM) inverters replacing synchronous generators for bulk power system stabilization and ancillary services, also allowing flexible power system operation, such as microgrid that is operated by multiple GFM IBRs to achieve system resilience against contingencies. To realize the resilient power systems allowing flexible in-and-out operation of GFM IBRs potentially programmed with different primary controls, a synchronization method universally applicable, i.e., independent of control types, would be beneficial to ease the integration process, but it has not been actively studied. To fill the gap, this paper proposes a universal synchronization method that achieves a passive synchronization to enable a smooth transition in a grid with off-nominal system parameters, i.e., voltage and frequency. The logic proposed requires no modification on the primary control, thus applicable to any type of GFMs with a voltage reference input. To validate the concept, a simulation of an IEEE 13-bus benchmark system modified with 3 GFM inverters is presented. It simulates an inverter-driven black start scenario in which GFM inverters autonomously turn on and connect to the grid under heavy loading, using the synchronization logic. The case study demonstrates that GFM inverters can tune their voltage reference to smoothly synchronize without severe transients, and contribute to a seamless black start of the grid under unbalanced load conditions. Two GFM methods - Droop and dispatchable virtual oscillator control - are used for the demo to validate feasibility and interoperability of the passive synchronization.

black start↗

Case Study: Applying the INL Resilience Framework to Iowa Lakes Electric Cooperative Distributed Wind Systems

Traditional metrics and evaluation methods for resiliency are not sufficient to evaluate the effect that distributed wind systems will have, particularly in light of the challenges described above. While the concept of resiliency is not new, its application to the electric grid is neither standardized nor well-defined, and there is little to no guidance on how to evaluate resilience specifically for distributed wind systems. To fill this gap, the Idaho National Laboratory (INL), as part of the multi-laboratory Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL) project, has developed a resilience framework for electric energy delivery systems (EEDS). The framework provides detailed steps for evaluating resiliency in the planning, operational, and future stages, and encompasses five core functions of resilience. It allows users to evaluate the resilience of distributed wind, taking into consideration the resilience of the wind systems themselves, as well as the effect they have on the resiliency of any systems they are connected to. In this study, we evaluate the resilience of the distributed wind systems at Iowa Lakes Electric Cooperative to cybersecurity hazards. We show that the wind resource can benefit the overall system resilience during some hazards. We show that the practices in place make the wind subsystems resilient against some cybersecurity hazards but that there are still significant risks associated with other cybersecurity hazards

17 WIND ENERGY↗

IRES Microgrid Energy Integration Report Version 1.0

This report presents technical information and guidance for the planned Integrated Renewable Energy System (IRES) microgrid project. This deployment of the microgrid and its associated assets was initiated in the beginning of 2022 at the Marine and Coastal Research Laboratory (MCRL) facility of Pacific Northwest National Laboratory (PNNL)-Sequim, Washington. The information in the report is organized under two main focus areas: electrical power interface, or interconnection, information of planned IRES assets; and communication and control interface, or interoperability, information of the planned IRES assets. The information will provide technical input for the development of the IRES microgrid controller technical specification, and also provide input for PNNL’s evaluation of adequacy of the electrical service infrastructure at MCRL to support the IRES project and help identify any gaps that will require facility-based upgrades. From an R&D aspect, this study and report will build on PNNL’s research and development work relating to energy storage (ES) codes and standards (C&Ss), including hybrid systems, performed on behalf of the Department of Energy (DOE) Office of Electricity (OE) ES. The current state of C&Ss for advanced technologies and their application, including microgrid-based technology is limited. For cases where formal standards issued by recognized Standards Developing Organizations do not yet exist, guidance is provided based on emerging best practices, including industry-group references that can be leveraged for microgrid technology which is in its early stages of development and use.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Prefeasibility Analysis of Behind-the-Meter Distributed Energy Resources in Highland Park, MI: Highland Park Pathways to Power [Slides]

Through the Communities LEAP (Local Energy Action Program) Pilot, the National Renewable Energy Laboratory (NREL) engaged the Highland Park Stakeholder Coalition to scope four technical assistance work areas to address their energy needs and goals. This slide deck addresses the highlighted tasks under work area "B" related to policy analysis, due diligence, and case studies for removing barriers and providing best practices for local clean energy development. NREL used the REopt platform to evaluate the techno-economic potential of adding solar PV, electric storage, and/or diesel generators at several locations in Highland Park, Michigan: a typical residential and commercial building in Highland Park, the Earnest T. Ford Recreation Center, and the Parker Village Microgrid. The analysis goals focused on the ability of solar PV, electric storage, and/or diesel generators to reduce electricity costs and improve site resilience.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluating Utility Costs Savings and Resilience: A Case Study in Port Arthur, Texas

This study evaluates the techno-economic feasibility of integrating solar photovoltaics (PV), battery energy storage systems (BESS), and generators to enhance both cost savings and resilience in critical community facilities in Port Arthur, Texas. Using NREL's REopt model, we analyze four facilities: the Golden Triangle Empowerment Center (GTEC), Lamar State College (LSC), Port Arthur Independent School District (PAISD), and Port Arthur Transit (PAT). A key aspect of the analysis is the incorporation of the Value of Lost Load (VoLL) and microgrid upgrade costs to assess the hidden value of resilience during grid outages. While standalone PV scenarios show moderate cost reductions and a 10-15% decrease in CO2 emissions, the inclusion of resilience measures with BESS and generators significantly increases system costs. However, the hidden value of resilience - quantified through avoided outage costs - leads to a substantial improvement in financial outcomes, resulting in positive Net Present Value (NPV) at many sites. The study demonstrates that resilient solar and storage systems offer both economic and resilience benefits, particularly for underserved communities, by balancing energy savings and enhanced operational continuity during outages.

14 SOLAR ENERGY↗

A Resilient Integrated Resource Planning Framework for Transmission Systems: Analysis and Optimization

This article presents a resilient Integrated Resource Planning (IRP) framework designed for transmission systems, with a specific focus on analyzing and optimizing responses to High-Impact Low-Probability (HILP) events. The framework aims to improve the resilience of transmission networks in the face of extreme events by prioritizing the assessment of events with significant consequences. Unlike traditional reliability-based planning methods that average the impact of various outage durations, this work adopts a metric based on the proximity of outage lines to generators to select HILP events. The system’s baseline resilience is evaluated by calculating load curtailment in different parts of the network resulting from HILP outage events. The transmission network is represented as an undirected graph. Graph-theoretic techniques are used to identify islands with or without generators, potentially forming segmented grids or microgrids. This article introduces Expected Load Curtailment (ELC) as a metric to quantify the system’s resilience. The framework allows for the re-evaluation of system resilience by integrating additional generating resources to achieve desired resilience levels. Optimization is performed in the re-evaluation stage to determine the optimal placement of distributed energy resources (DERs) for enhancing resilience, i.e., minimizing ELC. Case studies on the IEEE 24-bus system illustrate the effectiveness of the proposed framework. In the broader context, this resilient IRP framework aligns with energy sustainability goals by promoting robust and resilient transmission networks, as the optimal placement of DERs for resilience enhancement not only strengthens the system’s ability to withstand and recover from disruptions but also contributes to efficient resource utilization, advancing the overarching goal of energy sustainability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Forming and Following Background, Future, and Strategies

The landscape of the U.S. power structure with respect to microgrid configuration strategies that utilize grid forming and grid following converters is becoming relevant. Inverter based control and coordination strategies are every changing due to critical failures and limitations. Understanding current state of grid forming and following converter technology and their normal operational guidelines will lead into the next stage of future research. Grid forming and following converter control strategies and ratio of assets review two case studies to develop an understanding of the current landscape.

29 - ENERGY PLANNING, POLICY AND ECONOMY↗

Optimizing design and dispatch of a resilient renewable energy microgrid for a South African hospital

Lack of access to reliable energy is a major concern for countries in sub-Saharan Africa. The national grids are unable to consistently satisfy demand. Therefore, users turn to distributed generation systems in the form of back-up generators. However, such systems are usually designed based on a rule of thumb. We employ a mixed-integer linear programming model that considers several options such as renewable energy, combined heat and power, and storage technologies, in addition to those on-site, to provide optimal design and dispatch decisions that minimize total cost. We apply this model to a case study for a hospital in South Africa, considering its need for reliable electricity in light of multiple outages that might occur over the course of a year, as well as its high heating and cooling loads. Our results show that optimal design and dispatch decisions for the distributed generation system address reliability challenges, regardless of the time at which they occur. And, these solutions yield millions of dollars in savings, suggesting that technologies such as the absorption chiller may be overlooked in typical designs; its integration can reduce demand charges even in the absence of combined heat and power. We show that total cost is most sensitive to changes in site electrical demand, followed by capital cost, fuel cost, photovoltaic production, and monthly demand charges; changes in fuel cost primarily affect system sizes of combined heat and power and the absorption chiller, while photovoltaic system size is more sensitive to the changes in capital and fuel costs, photovoltaic resource availability, and hourly electrical demand. Finally, an outage simulator demonstrates the ability of our optimized system to sustain with no interruptions in power five-hour outages with probability 1.0 and ten-hour outages with probability 0.65, significant improvements over 0.5 and 0.0, respectively, under a business-as-usual case.

24 POWER TRANSMISSION AND DISTRIBUTION↗