Off-policy deep reinforcement learning with automatic entropy adjustment for adaptive online grid emergency control

Electric overloading conditions and contingencies put modern power systems at risk of voltage collapse and blackouts. Load shedding is crucial to maintain voltage stability for grid emergency control. However, the rule- or model-based schemes rely on accurate dynamic system models and face considerable challenges in adapting to various operating conditions and uncertain event occurrences. Here, to address these issues, this paper proposes a novel deep reinforcement learning (DRL)-based voltage stability control algorithm with automatic entropy adjustment (AEA) for grid emergency control. Various dynamic network components for complex system operations are modeled to construct the DRL environment. An off-policy soft actor-critic architecture is developed to maximize the expected reward and policy entropy simultaneously. The AEA mechanism is proposed to facilitate the policy maximum entropy procedure, and the proposed method can automatically provide effective discrete and continuous actions against various fault scenarios. Our approach accomplishes high sampling efficiency, scalability, and auto-adaptivity of the control policies under high uncertainties. Comparative studies with the existing DRL-based control methods in IEEE benchmarks indicate salient performance improvement of the proposed method for dynamic system emergency control.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Towards intelligent emergency control for large-scale power systems: Convergence of learning, physics, computing and control

Here, this paper has delved into the pressing need for intelligent emergency control in large-scale power systems, which are experiencing significant transformations and are operating closer to their limits with more uncertainties. Learning-based control methods are promising and have shown effectiveness for intelligent power system control. However, when they are applied to large-scale power systems, there are multifaceted challenges such as scalability, adaptiveness, and security posed by the complex power system landscape, which demand comprehensive solutions. The paper first proposes and instantiates a convergence framework for integrating power systems physics, machine learning, advanced computing, and grid control to realize intelligent grid control at a large scale. Our developed methods and platform based on the convergence framework have been applied to a large (more than 3000 buses) Texas power system, and tested with 56 000 scenarios. Our work achieved a 26% reduction in load shedding on average and outperformed existing rule-based control in 99.7% of the test scenarios. The results demonstrated the potential of the proposed convergence framework and DRL-based intelligent control for the future grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Coordinated frequency regulation among asynchronous AC grids with an MTDC system

With the increasing penetration level of renewable power, the power systems’ inertias are decreasing. To ensure that the frequency is above the threshold of the under frequency load shedding, one effective way is to share the spinning reserves among asynchronous AC grids through HVDC systems. In this paper, a coordinated frequency regulation scheme that enables spinning reserves sharing is proposed for such hybrid AC/DC grids. This scheme is a communication-free method that consists of the droop control, the inertia emulation control and the frequency safety control. The combined response of the three controls can increase not only the frequency nadir but also the settled frequency of the disturbed grid. In addition, the hysteresis comparators and the power injection limits are adopted in the frequency regulation scheme to reduce the coupling effect among AC grids. Thus, under small and harmless disturbance, the frequency regulation scheme will be inactive; the disturbance in strong AC grids would not affect the weak AC systems. The frequency regulation scheme coordinates well with the automatic generation control of the grids. Furthermore, the feasibility and effectiveness of the proposed frequency regulation scheme are verified through simulation studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Security constrained optimal power shutoff for wildfire risk mitigation

Abstract Electric grid faults are increasingly the source of ignition for major wildfires. To reduce the likelihood of such ignitions in high risk situations, utilities use preemptive de‐energization of power lines, commonly referred to as Public Safety Power Shutoffs (PSPS). Besides raising challenging trade‐offs between power outages and wildfire safety, PSPS removes redundancy from the network at a time when component faults are likely to happen. This may leave the network particularly vulnerable to unexpected line faults that may occur while the PSPS is in place. Previous works have not explicitly considered the impacts of these outages. To address this gap, the Security Constrained Optimal Power Shutoff problem is proposed which uses post‐contingency security constraints to model the impact of unexpected line faults when planning a PSPS. This model enables, for the first time, the exploration of a wide range of trade‐offs between both wildfire risk and pre‐ and post‐contingency load shedding when designing PSPS plans, providing useful insights for utilities and policy makers considering different approaches to PSPS. The efficacy of the model is demonstrated using the EPRI 39‐bus system as a case study. The results highlight the potential risks of not considering security constraints when planning PSPS and show that incorporating security constraints into the PSPS design process improves the resilience of current PSPS plans.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

A Unified Analytical Method to Quantify Three Types of Fast Frequency Response from Inverter-Based Resources

With more inverter-based resources (IBRs), our power systems have lower frequency nadirs following N-1 contingencies, and undesired under-frequency load shedding (UFLS) can occur. To address this challenge, IBRs can be programmed to provide at least three types of fast frequency response (FFR), e.g., step response, proportional response (P/f droop response), and derivative response (synthetic inertia). However, these heterogeneous FFR challenge the study of power system frequency dynamics. Thus, this paper develops an analytical frequency nadir prediction method that allows for the consideration of all three potential forms of FFR provided by IBRs. The proposed method provides fast and accurate frequency nadir estimation after N-1 generation tripping contingencies. Our method is grounded on the closed-form solution for the frequency nadir, which is solved from the second-order system frequency response model considering the governor dynamics and three types of FFR. The simulation results in the IEEE 39-bus system with different types of FFR demonstrate that the proposed method provides an accurate and fast prediction of the frequency nadir under various disturbances.

fast frequency response↗

Resilient co-expansion planning between gas and electric distribution networks against natural disasters

Resiliently designed and constructed integrated gas-electric distribution networks (GEDNs) against natural disasters are crucial to social welfare. In this study, a two-stage robust optimisation-based co-expansion planning model is proposed to attain an integrated GEDN with a given resilience level, by optimising the investment strategies of hardening and selective expansion of power distribution feeders and natural gas pipelines, as well as the location and capacity of natural-gas-fired distributed generation. In the first stage, the overall annual investment and operation cost is minimised under normal operation conditions while in the second stage, the feasibility of the investment decisions under the identified worst-case natural disaster scenario is checked with an adjustable load shedding cost criterion. The proposed model is formulated as a mixed integer second-order cone programming problem with the column and constraint generation algorithm employed to seek the optimal solution. Case studies on two integrated GEDNs demonstrate the performance of the proposed methodology.

Zou, Bo↗

Strategic Placement and Sizing of Distributed Generation for Resilience Enhancement of Distribution Grids With Microgrid Formation

The rise in frequency and severity of extreme weather events highlights the need for resilient power distribution networks. Microgrids can help improve the resilience of distribution grids by providing continuous power supply using local distribution generation (DG) when the distribution grid fails. In this paper, we propose an approach for optimal placement and sizing of DG to form multiple microgrids throughout the distribution network by restoration actions such as switching operations in case of distribution grid outages caused by extreme weather events. Considering the randomness of damaged distribution lines, the DG placement and sizing problem is formulated as a two-stage stochastic mixed-integer program, with the first stage determining the placement and size of DG, and the second stage focusing on minimizing the amount of load shedding through network restoration and microgrid formations for each scenario. Due to the large number of scenarios, the sample average approximation (SAA) method is employed to solve the problem. The results of case studies on a modified IEEE 33 bus distribution grid demonstrate the effectiveness of the proposed DG placement and sizing strategy in improving the resilience of distribution grids by allowing the formation of multiple microgrids. In addition, the robustness and accuracy of the SAA method are validated through various case studies.

Distributed generation planning↗

Correlation between Generator Trips and Locational Marginal Prices (LMPs)

Generally, disturbances in an interconnected network have an influence the stability and the economy of the power grid. Some phenomenon such as load shedding have proven to have a huge impact on real time electricity prices. Generation trip is considered one of the most common events in a power grid that may change the wholesale electricity market. In this paper, a locational marginal price (LMP) measure is used to notice how the electricity prices change with generator trip events at different locations of U.S. power grid. The study results help to find whether there is a clear correlation between generator trips and the changes in the electricity real-time market.

Alharbi, Abdulelah↗

Hy-DAT: A Tool to Address Hydropower Modeling Gaps Using Interdependency, Efficiency Curves, and Unit Dispatch Models

As the power system continues to be flooded with intermittent resources, it becomes more important to accurately assess the role of hydro and its impact on the power grid. While hydropower generation has been studied for decades, dependency of power generation on water availability and constraints in hydro operation are not well represented in power system models used in the planning and operation of large-scale interconnection studies. There are still multiple modeling gaps that need to be addressed; if not, they can lead to inaccurate operation and planning reliability studies, and consequently to unintentional load shedding or even blackouts. As a result, it is very important thathydropower is represented correctly in both steady-state and dynamic power system studies. In this paper, we discuss the development and use of the Hydrological Dispatch and Analysis Tool (Hy-DAT) as an interactive graphical user interface (GUI), that uses a novel methodology to address the hydropower modeling gaps like water availability and inter-dependency using a database, and algorithms, to generate accurate representative models for power system simulation.

Wang, Dewei↗

Fast Frequency Response using Reinforcement Learning-Controlled Wind Turbines

To fulfill the auxiliary grid services such as load regulation, spin and non-spin reserve, and frequency support during emergencies, power system operators often require certain wind farms to operate in de-loaded modes. By leveraging the fast response capability of wind farms, the reserved power in deloaded modes can significantly enhance the stability and reliability of power grids. This paper presents a novel methodology that incorporates wind turbines into reinforcement learning-based solutions for frequency response. The proposed approach employs the state-of-the-art reinforcement learning algorithm, surrogategradient- based evolution strategy (GSES), for continuous control of the wind farm output. Our methodology is tested on a modified IEEE-39 bus system, and simulation outcomes demonstrate that the proposed approach can reliably support the frequency of the power system and prevent unnecessary load shedding.

Gao, Wei↗

Deep Reinforcement Learning for Distribution System Cyber Attack Defense with DERs

The use of smart inverter capabilities of distributed energy resources (DERs) enhances the grid reliability but in the meanwhile exhibits more vulnerabilities to cyber-attacks. This paper proposes a deep reinforcement learning (DRL)-based defense approach. The defense problem is reformulated as a Markov decision making process to control DERs and minimizing load shedding to address the voltage violations caused by cyber-attacks. The original soft actor-critic (SAC) method for continuous actions has been extended to handle discrete and continuous actions for controlling DERs' setpoints and loadshedding scenarios. Numerical comparison results with other control approaches, such as Volt-VAR and Volt-Watt on the modified IEEE 33-node, show that the proposed method can achieve better voltage regulation and have less power losses in the presence of cyber-attacks.

active distribution systems↗

Implementational Aspects for the Characterization of Low-Inertia in Power Systems

The replacement of conventional generating units with non-conventional renewable energy resources impacts the stability of the power system. While the general goal of supplying demand could be achieved from both generation resources, inverter-based energy resources are different from traditional synchronous machines in the sense that they do not inherently provide inertia to the system. The latter obviously worsen the system ability to maintain the balance between supply and demand after certain contingencies such as generator outages. With high integration of renewable-based generation resources, there is a reduction in total system inertia, which could lead to systems with less time to react for frequency restoration in case of such unexpected unit failures. While conceptually it is true, there is a missing gap in the field of power system stability community in terms of test-bed power systems for characterizing low-inertia conditions. In this paper, a framework for low-inertia power systems is presented. The purpose of the test-bed is to establish an environment for testing and conducting research on power systems experiencing low-inertia issues. The frequency nadir, the rate of change of frequency, and the under-frequency load shedding scheme are used as a measure of the healthiness of power grids.

Baquedano-Aguilar, Mario D.↗

Managing Power Systems-Induced Wildfire Risks Using Optimal Scheduled Shutoffs

The increasing demands for electricity and the increase in extreme weather conditions are putting unprecedented pressure on our electric grids. Often, this pressure leads to electrical component failures, which might ignite wildfires. This work develops a novel model to balance the reliability of power network operations and the risk of wildfire ignition by opti- mizing the operational schedule of power transmission networks considering time-varying risk measures that include exogenous and operational factors. Energy storage systems are considered to deliver power during peak wildfire hours and enable temporal load shifting. The problem is formulated as a mixed-integer linear program that maximizes a weighted sum of the served power demand and the reduction in grid-induced wildfire risk. The results demonstrate the ability of the model to significantly reduce wildfire risk without considerable load shedding.

power systems operations↗

Photovoltaic Inverter Momentary Cessation: Recovery Process is Key

Momentary cessation refers to an inverter control mode. When the inverter terminal voltage falls below (or exceeds) a certain level, the inverter ceases to output any current, but attempts to maintain (or quickly regain) phase-locked loop synchronization to allow for quick reinjection of current when the voltage recovers to a certain point. This paper presents a photovoltaic (PV) momentary cessation model developed in PSS/E. Simulations are presented for a high voltage transmission line fault contingency in the Hawaiian island of Oahu power system on a validated PSS/E model, modified to include a custom distributed PV inverter model, and different near-future distributed PV penetration levels. Simulations for the island power system include different penetration levels of PV, and different recovery times (ramp rates and delays) after momentary cessation. The results indicate that during low voltage events, such as faults, momentary cessation can produce severe under frequency events, causing significant load shed and shortly thereafter, in some cases, over frequency events that cause generation to trip offline. The problem is exacerbated with higher penetration levels of PV. If momentary cessation is used (as is typically the case for distribution-connected resources), the recovery process after momentary cessation should be carefully considered to minimize impacts to bulk power system stability.

14 SOLAR ENERGY↗

Operability of a Power System with Synchronous Condensers and Grid-Following Inverters

Growing shares of inverter-based resources gener-ally correlate with a reduction in inertia as synchronous genera-tors are displaced. Along the path to high shares of inverter-based resources, in particular with only conventional grid-following inverter controls, a proffered solution is the use of synchronous condensers as a source of inertia to maintain the frequency-power balance relationship. An outstanding question is whether only grid-following inverters and synchronous condensers yield a viable power system; i.e., all frequency response is derived from inverters. A validated electromagnetic transient model of the Maui system, with many nonlinear elements such as load-shedding, line tripping, and inverter ride through criteria disabled, is used to investigate the stability of such a system. Two types of perturbations were applied, a 15% generation loss and a fault event, and it was found that the system remains stable.

grid-following inverters↗

Network Reconfiguration for Enhanced Operational Resilience Using Reinforcement Learning

This paper proposes a reinforcement learning-based approach for distribution network reconfiguration(DNR) to enhance the resilience of the electric power supply. Resilience enhancements usually require solving large-scale stochastic optimization problems that are computationally expensive and sometimes infeasible. The exceptional performance of reinforcement learning techniques has encouraged their adoption in various power system control studies, specifically resilience-based real-time applications. In this paper, a single agent framework is developed using an Actor-Critic algorithm (ACA) to determine statuses of tie-switches in a distribution feeder impacted by an extreme weather event. The proposed approach provides a fast-acting control algorithm that reconfigures the feeder topology to reduce or even avoid load shedding. The problem is formulated as a discrete Markov decision process in such a way that a system state captures the system topology and its operational characteristics. An action is made to open or close a specific set of tie-switches after which a reward is calculated to evaluate the practicality and advantage of that action. The iterative Markov process is used to train the proposed ACA under diverse failure scenarios and is demonstrated on the 33-node distribution feeder system. Results show the capability of the proposed ACA to determine proper switching action of tie-switches with accuracy exceeding 93%.

actor critic↗

Robust System Separation Strategy Considering Online Wide-Area Coherency Identification and Uncertainties of Renewable Energy Sources

With the fast growth of renewable energy sources (RES), more and more uncertainties are involved and influencing the stable operation of power systems. Controlled islanding is the last measure to prevent power system blackouts, thus this paper aims to propose a novel model of system separation based on Online Coherency Identification and Adjustable Robust Optimization Programming (OCI-AROP) for minimizing load shedding considering the uncertainties of RES. First, Fuzzy C-Means (FCM) clustering method with F-statistics is utilized to identify the coherent generator groups with the frequency data measured by Phasor Measurement Units (PMUs). Then, the OCI-AROP model considering coherent group constraints, connectivity constraints and robustness constraints about RES are presented. Finally, the case studies on IEEE-39 bus system and WECC-179 bus system are employed to demonstrate the effectiveness of the proposed OCI-AROP model, and comparisons among the OCI-AROP model and the other models are also given to show its superiority.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Physics-Informed Evolutionary Strategy Based Control for Mitigating Delayed Voltage Recovery

Here, in this work we propose a novel data-driven, real-time power system voltage stability control method based on the physics-informed guided meta evolutionary strategy (ES). The main objective is to quickly provide an adaptive control strategy to secure system voltage stability. The problem is challenging due to the high-dimensional feature of the power system model and the fast-changing and uncertain nature of power system operation scenarios. To this end, a model-free and derivative-free guided ES method is applied. The method is further combined with a meta-learning strategy to make the learnt control policy automatically adapted to unseen operation conditions and fault scenarios, which is highly desired for real-time emergency control. Last but not least, physical knowledge is embedded in the above method through a trainable action mask technique to rule out unnecessary load shedding actions for better learning and control performance. Case studies on the IEEE 300-bus system and comparisons with other state-of-the-art benchmark methods verify the superiority of the proposed physics-informed guided meta ES method in realizing fast and adaptive power system voltage stability control.

42 ENGINEERING↗