At least 127 records · Page 7

Distributed Energy Resource (DER) Integration Framework: Regulatory Innovation for DER Compensation and Cost Allocation

Existing regulatory approaches to DER lack the precision and granularity necessary to ensure that DER can continue to scale in a cost-effective manner that is aligned with the public interest. To address this need, with the support of the U.S. Department of Energy’s Office of Electricity, Berkeley Lab and Current Energy Group developed an illustrative regulatory framework. By adopting a technology-neutral and modular approach, the framework enables flexibility and scalability for DER providers, utilities, and regulators. Clear price signals and incentives encourage the provision of valuable grid services, while equitable cost allocation promotes efficient use of distribution capacity and interconnection resources. This approach mirrors traditional ratemaking principles for importing customers and positions DERs as integral components of a dynamic and cost-effective energy future.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power system effects and mitigation recommendations for DER cyberattacks

Extensive deployment of interoperable distributed energy resources (DER) is increasing the power system cyber security attack surface. National and jurisdictional interconnection standards require DER to include a range of autonomous and commanded grid‐support functions, which can drastically influence power quality, voltage, and bulk system frequency. Here, the authors investigate the impact to the cyber‐physical power system in scenarios where communications and operations of DER are controlled by an adversary. The findings show that each grid‐support function exposes the power system to distinct types and magnitudes of risk. The physical impact from cyber actions was analysed in cases of DER providing distribution system voltage regulation and transmission system support. Finally, recommendations are presented for minimising the risk using engineered parameter limits and segmenting the control network to minimise common‐mode vulnerabilities.

24 POWER TRANSMISSION AND DISTRIBUTION↗

GMLC Technical Assistance to States

This presentation provides an overview of the U.S. Department of Energy's Grid Modernization Laboratory Consortium (GMLC) efforts to provide customized technical support specific to state public utility commissions (PUCs), specifically on the integration of distributed energy resources (DERs). The goals are to increase awareness of existing materials and support to help state PUCs move forward on DER interconnection activities, to help participants make connections to colleagues with similar challenges (and solutions), and to help the GMLC/National Renewable Energy Laboratory project team understand context and implementation challenges.

DER↗

Capacity value assessments of wind power

This article describes some of the recent research into the capacity value of wind power. With the worldwide increase in wind power during the past several years, there is increasing interest and significance regarding its capacity value because this has a direct influence on the amount of other (nonwind) capacity that is needed. We build on previous reviews from IEEE and IEA W ind T ask 25 a and examine recent work that evaluates the impact of multiple‐year data sets and the impact of interconnected systems on resource adequacy. We also provide examples that explore the use of alternative reliability metrics for wind capacity value calculations. We show how multiple‐year data sets significantly increase the robustness of results compared to single‐year assessments. Assumptions regarding the transmission interconnections play a significant role. To date, results regarding which reliability metric to use for probabilistic capacity valuation show little sensitivity to the metric. WIREs Energy Environ 2017, 6:e226. doi: 10.1002/wene.226 This article is categorized under: Wind Power > Economics and Policy Wind Power > Systems and Infrastructure Energy Infrastructure > Economics and Policy

Milligan, Michael↗

Interconnection and Interoperability Requirements of Hydrogen Assets to Enable Grid Integration

Traditionally, the inverters used for distributed energy resources (DERs) including solar, energy storage and hydrogen fuel cells are grid following assets. Grid following assets track real power and reactive power setpoints decided by either a local autonomous controller or a remote controller like a microgrid controller. In the past five years, multiple challenges have increased the need for grid forming inverters that can interface to a wide variety of energy resources. These grid forming inverters are becoming critical assets for power systems to enable the replacement of existing rotational machines and provide grid services such as grid resiliency services and black-start. Hydrogen assets (fuel cells) have the potential to successfully replace rotating machines and act as voltage and frequency master by leveraging the long-duration and seasonal energy storage capabilities of hydrogen technologies. This poster presents the progress made in budget period 1 of the proposed work. We will leverage an existing ARIES platform experimental setup to run power-hardware-in-the-loop and controller-hardware-in-the-loop experiments with grid forming fuel cell inverters to develop and document the standardization requirements.

electrolyzer↗

Challenges in reducing the computational time of QSTS simulations for distribution system analysis.

The rapid increase in penetration of distributed energy resources on the electric power distribution system has created a need for more comprehensive interconnection modelling and impact analysis. Unlike conventional scenario - based studies , quasi - static time - series (QSTS) simulation s can realistically model time - dependent voltage controllers and the diversity of potential impacts that can occur at different times of year . However, to accurately model a distribution system with all its controllable devices, a yearlong simulation at 1 - second resolution is often required , which could take conventional computers a computational time of 10 to 120 hours when an actual unbalanced distribution feeder is modeled . This computational burden is a clear l imitation to the adoption of QSTS simulation s in interconnection studies and for determining optimal control solutions for utility operations . Our ongoing research to improve the speed of QSTS simulation has revealed many unique aspects of distribution system modelling and sequential power flow analysis that make fast QSTS a very difficult problem to solve. In this report , the most relevant challenges in reducing the computational time of QSTS simulations are presented: number of power flows to solve, circuit complexity, time dependence between time steps, multiple valid power flow solutions, controllable element interactions, and extensive accurate simulation analysis.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Rapid QSTS Simulations for High-Resolution Comprehensive Assessment of Distributed PV

The rapid increase in penetration of distributed energy resources on the electric power distribution system has created a need for more comprehensive interconnection modeling and impact analysis. Unlike conventional scenario-based studies, quasi-static time-series (QSTS) simulations can realistically model time-dependent voltage controllers and the diversity of potential impacts that can occur at different times of year. However, to accurately model a distribution system with all its controllable devices, a yearlong simulation at 1-second resolution is often required, which could take conventional computers a computational time of 10 to 120 hours when an actual unbalanced distribution feeder is modeled. This computational burden is a clear limitation to the adoption of QSTS simulations in interconnection studies and for determining optimal control solutions for utility operations. The solutions we developed include accurate and computationally efficient QSTS methods that could be implemented in existing open-source and commercial software used by utilities and the development of methods to create high-resolution proxy data sets. This project demonstrated multiple pathways for speeding up the QSTS computation using new and innovative methods for advanced time-series analysis, faster power flow solvers, parallel processing of power flow solutions and circuit reduction. The target performance level for this project was achieved with year-long high-resolution time series solutions run in less than 5 minutes within an acceptable error.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Recommendations for Trust and Encryption in DER Interoperability Standards

Recently developed Distributed Energy Resource (DER) interoperability standards include communication and cyber security requirements. In 2018, the US national interconnection standard, IEEE 1547, was revised to require DER to include a Sun Spec Modbus, IEEE 2030.5 (Smart Energy Profile, SEP 2.0), or IEEE 1815 (DNP3) communication interface but does not include any normative overarching cybersecurity requirements. IEEE 2030.5 and associated implementation requirements for California, known as the California Smart Inverter Profile (CSIP), prescribe the greatest security features - including encryption, authentication, and key management requirements. Sun Spec Modbus and IEEE 1815 security requirements are not as comprehensive, leading to implementation questions throughout the industry. Further, while the security features in IEEE 2030.5 are commonly used in computing platforms, there are still questions of how well the technologies will scale in highly-distributed, computationally-limited inverter environments. In this paper, (a) the elements of IEEE 2030.5 encryption, authentication, and key management guidelines are analyzed, (b) potential scalability gaps are identified, and (c) alternative technologies are explored for possible inclusion in DER interoperability or cyber security standards.

42 ENGINEERING↗

Systems and methods for detecting and mitigating cyber attacks on power systems comprising distributed energy resources

Extensive deployment of interoperable distributed energy resources (DER) on power systems is increasing the power system cybersecurity attack surface. National and jurisdictional interconnection standards require DER to include a range of autonomous and commanded grid-support functions which can drastically influence power quality, voltage, and the generation-load balance. Investigations of the impact to the power system in scenarios where communications and operations of DER are controlled by an adversary show that each grid-support function exposes the power system to distinct types and magnitudes of risk. The invention provides methods for minimizing the risks to distribution and transmission systems using an engineered control system which detects and mitigates unsafe control commands.

97 MATHEMATICS AND COMPUTING↗

Systems and methods for detecting and mitigating cyber attacks on power systems comprising distributed energy resources

Extensive deployment of interoperable distributed energy resources (DER) on power systems is increasing the power system cybersecurity attack surface. National and jurisdictional interconnection standards require DER to include a range of autonomous and commanded grid-support functions which can drastically influence power quality, voltage, and the generation-load balance. Investigations of the impact to the power system in scenarios where communications and operations of DER are controlled by an adversary show that each grid-support function exposes the power system to distinct types and magnitudes of risk. The invention provides methods for minimizing the risks to distribution and transmission systems using an engineered control system which detects and mitigates unsafe control commands.

Johnson, Jay Tillay↗

Smarter Grid Solutions | National Renewable Energy Laboratory: Active Management Integration: June 2015 - November 2016

This report presents the project results for the NREL INTEGRATE demonstration project: Active Network Management (ANM) Integration. Consistent with the INTEGRATE program's objective of increasing the grid's clean energy hosting capacity and providing grid services in a holistic manner, the project demonstrated the use of ANM to enable very high penetrations of solar PV and wind energy systems. Results obtained using a representative North American distribution system showed ANM's autonomous distributed control doubled the interconnected wind and solar systems by managing thermal and voltage constraints in real-time. These generators flexibly interconnected to the grid via ANM's end-to-end control architecture, and were managed and coordinated with other smart distributed energy resources (DER; e.g. EVs, battery ESS, controllable load) to unlock the grid's dynamic hosting capacity. As a smart grid application to standardize grid integration of diverse renewable generation sources, ANM provides the industry with a scalable, cost-effective alternative to traditional transmission and distribution (T&D) reinforcements. This project considered three use cases of the application of ANM: a Smart Home demonstration of ANM control of residential scale devices (PV, EV, and battery ESS); a Smart Campus demonstration of high penetration megawatt-scale DER (PV, EVs, battery ESS, and controllable load) behind a single point-of-common-coupling (PCC), and a Smart Distribution demonstration that combined prior use cases along with additional community/utility-scale DER at very high aggregate penetration levels. The Smart Distribution use case provided an integrated perspective of ANM across all distribution grid DER device scales (incorporating aggregated Smart Homes and the Smart Campus) in order to showcase how these devices can support smart grid services to manage DER related constraints in a safe and reliable manner; and likewise how ANM integrates with grid modernization initiatives. The ANM system was deployed in NREL's Energy Systems Integration Facility (ESIF), and project industry advisors attended an on-site demonstration and a set of workshops in order to review project outcomes and evaluate the relevance of ANM for increasing the grid hosting capacity. The outcomes of this effort include an assessment of opportunities for field deployment of ANM to address existing interconnection challenges, as well as consolidating project advisor suggestions for investment in ANM and potential future pilots for more advanced schemes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Smart Contracts for Power Grid Applications Using the Advanced DLT Cyber Grid Guard Testbed

In this study is presented two power system applications with distributed ledger technology (DLT) and smart contracts (SC) that were assessed in a Cyber-Grid-Guard System (CGGS) advanced testbed, with protective relays, power meters, communication devices, DLT devices, synchronized time source, clock displays and real time simulator. This CGGS testbed was set in the Advanced Protection Lab, 252 lab space of the Grid Research Integration and Deployment Center (GRID- C), at Oak Ridge National Laboratory. In power grids, customer-owned distributed energy resources (DERs) are more frequent than in the past, and the numbers of points of interconnection (POI) with customer-owned DERs have increased. Disruptive operation from DERs presents a risk to grid operations, and protective relays located at the POI are used to isolate out-of-tolerance or poorly behaving of DERs. Ensuring the integrity of data from the relays at the POI, and DLT could enhance the security of the power grids. The first application is a SC to define and control the allowable total power factor (TPF) of the DER (wind farm) output, and the terms of the SC are implemented using DLT with a CGGS for a customer-owned DER. The TPF SC was implemented by the CGGS using DLT. The experimental model was performed with a real-time simulator using a CGGS and relay in-the-loop. The data collected from the CGGS were used to execute the TPF SC. The TPF limits were between +0.9 and +1.0, and the breakers’ operation in the POI was controlled by the relay using the SC. The events were collected from the real-time simulator, CGGS, and SEL 700GT relay to validate a successful application of the TPF SC using DLT. The second application is a SC to measure and control the allowable voltage service limits (VSL) by the CGGS using DLT. The tests were performed by using a real-time simulator, CGGS and relay in-the-loop. The data was collected from the CGGS that executed the SC. The main constraints were defined based on ANSI C84.1 service voltage limits, and the operation of the breakers in the POI. The events were collected from the CGGS, and SEL 700GT relay to assess a successful operation of the VSL SC using DLT.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Photovoltaic Microinverter Testbed for Multiple Device Interoperability

IEEE Standard 1547-2003 conformance of several interconnected microinverters was performed by Sandia National Laboratories (SNL) to determine if there were emergent adverse behaviors of co-located aggregated distributed energy resources. Experiments demonstrated the certification tests could be expanded for multi-manufacturer microinverter interoperability. Evaluations determined the microinverters' response to abnormal conditions in voltage and frequency, interruption in grid service, and cumulative power quality. No issues were identified to be caused by the interconnection of multiple devices.

42 ENGINEERING↗

The "Perfect Storm" for Distributed Wind Markets

Close to 1 GW of distributed wind has been installed across all 50 states, the District of Columbia, Puerto Rico, and the U.S. Virgin Islands. Yet the number of installations varies greatly by state, even when wind resources are similar. This article examines three key factors that over the past thirteen years have shown to be enablers of success for distributed wind installations in the United States: 1) favorable policy environments, including consistent incentives, administrative support for cutting through red tape, and favorable interconnection, net metering, and permitting policies; 2) high electricity prices that would be displaced by wind energy generation, and, 3) favorable wind resources, enabling steady production of energy. Not all conditions need to be met simultaneously, yet of the studied markets for distributed wind in Iowa, New York, Washington, and Oregon, the most successful ones exhibit at least two out of the three conditions mentioned. We describe steps that policymakers, regulators, and market players have taken in the past to increase distributed wind installations in the United States.

Foster, Nikolas AF↗

Secondary Networks and Protection: Implications for DER and Microgrid Interconnection

Secondary networks are used to supply power to loads that require very high reliability and are in use around the world, particularly in dense urban downtown areas. The protection of secondary network systems poses unique challenges. The addition of distributed energy resources (DERs) to secondary networks can compound these challenges, and deployment of microgrids on secondary networks will create a new set of challenges and opportunities. This report discusses secondary networks and their protection, the challenges associated with interconnecting DERs to a secondary network, issues expected to be associated with creating microgrids on secondary networks, standards that deal with these challenges and issues, and suggestions for research and development foci that would yield new means for addressing these challenges.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Foundations for the Future Power System: Inverter-Based Resource Interconnection Standards

As power systems evolve to become reliant on solar, wind, batteries, and other inverter-based resources (IBRs), it is essential that those resources meet certain minimum performance and capability criteria designed to ensure the power system operates stably and reliably. Because those criteria, as enshrined in interconnection standards, take years to develop and are very long lived, they need to account for not only the present state of the power system but also its expected future state over the lifetime of the power plants to which they will apply. In addition, they need to be specific enough to ensure reliability without over specifying and, thereby, impeding innovation. Because power systems are shifting rapidly from a state where IBRs make up a small to medium portion of generation to one where the generation will, at times, come predominantly from IBRs, interconnection standards are especially challenging to develop today. Good interconnection standards can make the power system more reliable and less costly to operate, whereas poorly designed standards can lead to major problems, like the famous German 50.2-Hz problem, which introduced a risk of losing many gigawatts of solar on a frequency excursion and resulted in many IBRs being retrofitted at great cost to mitigate a major system reliability risk. Readying the power system by specifying forward-looking technical minimum functional capabilities for IBRs can be an effective approach to avoid future retrofits.

data models↗

An Overview of Behind-the-Meter Solar-Plus-Storage Regulatory Design: Approaches and Case Studies to Inform International Applications

Behind-the-meter energy storage systems paired with distributed photovoltaic (DPV) - with the capability to act as both generation and load - represent a unique and disruptive power sector technology capable of providing a range of important services to customers, utilities, and the broader power system. How should regulators, utilities, and policymakers manage the range of challenges and opportunities that increased behind-the-meter energy storage deployment will bring to the power system, in particular when these systems are paired with DPV? This report is intended to offer key regulatory considerations for facilitating DPV-plus-storage programs for retail customers; relevant cases from U.S. states are provided as examples of how novel regulatory issues related to behind-the-meter energy storage systems paired with DPV are being addressed in practice. At a high level, designing a regulatory framework that aligns DPV-plus-storage deployment with larger policy objectives requires thoughtful deliberation across a range of technical and economic issues. While this report attempts to segment many of these issues into distinct topics to enhance reader understanding, in reality, DPV-plus-storage regulatory issues are all closely integrated, and design decisions on a single aspect often have broader implications. With that in mind, this report outlines a series of steps that can be employed by regulators to approach DPV-plus-storage regulatory design.

14 SOLAR ENERGY↗

Scalable Distributed Reachability Analysis for Cyber-Physical Networked Microgrids with Communication Latency

Due to the high penetration of power-electronic-interfaced distributed energy resources (DERs), a microgrid's inertia is significantly reduced, making it sensitive to cyberand physical operational changes. When multiple microgrids are interconnected to form networked microgrids for improving system's resilience, the changes of one microgrid can quickly escalate to the overall system. In cyber-physical networked microgrids, the communication latency varies a lot. To efficiently quantify the impact of the communication latency on the dynamics of networked microgrids, a scalable distributed reachability analysis approach is presented in this paper. Reachable sets are calculated for each microgrid and then composited for the overall system dynamics evaluation. Extensive tests in the full paper will demonstrate the influence of communication latency on system dynamics and validate reachable sets can bound a system's all dynamic trajectories subject to latency changes. The test results also offer an insight into designing and managing the communication network for enhancing the system's resilience.

Li, Yan↗