Large-scale simulation-based parametric analysis of an optimal precooling strategy for demand flexibility in a commercial office building

Achieving success with grid-interactive efficient buildings (GEBs) is closely tied to the utilization of flexible loads. A valuable strategy involves the implementation of precooling techniques before high-demand events, such as peak hours, by adjusting zone air temperature setpoints. This leads to a reduction in thermal loads and peak electricity demand during these times, as the building’s thermal mass stores and subsequently releases thermal energy. However, the effectiveness of the pre-cooling optimization is highly contingent on specific conditions such as building thermal properties, weather conditions, utility rate structure, HVAC equipment sizing, etc. Therefore, investigating the impacts of these condition-specific factors is crucial, especially when considering precooling strategies that utilize thermal mass in commercial buildings. In this paper, we first devised a novel heuristic control approach that incorporates parameterized optimal precooling thermostat schedules to enhance demand flexibility in a commercial office building. Subsequently, we conducted a thorough performance evaluation of this control strategy. Here, the optimal thermostat schedule was parameterized using three optimization variables: the precooling start time, the precooling end time, and the precooling temperature setpoint. Utilizing the DOE medium-sized office building as the virtual testbed, we showed that the parameterized schedule effectively approximates model predictive control and requires drastically reduced computational overhead. In addition, we investigated the impact of different influencing factors on the optimal precooling strategy. These factors include building thermal mass, outdoor air conditions, and energy price profiles. Using high-performance computing, we simulated a total of 225 scenarios, consisting of three levels of thermal mass, five typical outdoor air temperature profiles, and fifteen time-of-use price plans. The results demonstrate that optimal thermostat scheduling could save substantial energy cost in medium-sized office buildings with heavy thermal mass but with some energy penalty. Although the potential for cost savings is lower in buildings with low and medium thermal mass, the energy penalty remains consistent in all three thermal mass scenarios. The study also highlights the need to account for zone diversity and recognize that a one-size-fits-all-zone setpoint schedule may not be suitable for all zones and can lead to unnecessary energy wastage. Furthermore, the results highlight that while outdoor air conditions play a role in cost and energy performance, the cooling load exerts a more immediate and substantial influence on cost savings in precooling strategies. Although cost savings are comparable under certain conditions with the same cooling load, observed deviations in energy penalty indicate potential disparities in the efficiency of the HVAC system during the load-shifting process. In addition, the duration of peak pricing and the ratio between peak and off-peak times exhibit clear correlations with cost savings and energy consumption, aligning with intuitive expectations. These findings offer valuable insights for optimizing precooling strategies in office buildings.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Modeling District Heating and Cooling Systems with URBANopt, GeoJSON to Modelica Translator, and the Modelica Buildings Library

The URBANopt project has successfully leveraged OpenStudio/EnergyPlus to model buildings and electrical systems at an urban scale; however, URBANopt has lacked the ability to model district thermal energy systems until recently. This paper will present the modeling infrastructure that was developed specifically for the analysis of district heating and cooling systems, and how it is integrated into the existing URBANopt framework. The paper also discusses the development of new models added to the Modelica Buildings Library to model various district energy system components including loads, energy transfer stations (ETS), distribution networks, and central plants. The paper describes how different building loads can be modeled including time series, TEASER reduced-order models, or Spawn of EnergyPlus models. URBANopt District Energy Systems allows the user to switch between the various configurations.

district heating and cooling↗

Evaluation of thermostat location for multizone commercial building performance

In multi-zone buildings, it is often found that a single shared thermostat controls more than one conditioned zones. Although these shared zones are supposed to have similar thermal needs (e.g., cooling and heating load), in reality, they are not mainly due to different orientations, sizes of windows, occupancy, space types, etc. This can cause unnecessary energy waste or thermal discomfort for the occupants. How to quantify this impact in multizone buildings remains a research gap. Therefore, this study aims to evaluate the impact of different sensor (i.e., thermostat) locations for multizone commercial buildings through a comprehensive modeling study. Here, two different scenarios for the sensor locations were selected to evaluate the impact in terms of energy and thermal comfort. The scenario (1) is that one to five sensors distributed among the five zones, but the sensor readings from selected zones will be used for no-sensor zones, which is no-mean sensor scenario. The scenario (2) is that one to five sensors distributed among the five zones, but the average temperature from the shared zones will be used for each of the shared zones, which is a mean sensor scenario. The uncertainty analysis was performed for different sensor location scenarios.(a)The major findings from an energy perspective, for scenario (1), the differences of cooling energy go as high as 17% more or 12% less, compared with the baseline. For heating energy consumption, the discrepancies go as high as 51% more or 52% less, compared with baseline. For site energy consumption, the discrepancies go as high as 3.2% more or 3.2% less, compared with baseline. For fan energy consumption, the discrepancies go as high as 3.2% more or as low as 1.0% less, compared with baseline. For scenario (2), the discrepancies of cooling energy go as high as 3% more, or 0.5% less, compared with the baseline. For heating energy consumption, the discrepancies, are go as high as 10.1% more or as low as 3.0% less, compared with baseline. For site energy consumption, the discrepancies go as high as 1.3% more or 0.3% less, compared with baseline. For fan energy consumption, the discrepancies go as high as 3.1% more or as low as 1.0% less, compared with baseline.(b) In terms of the indoor thermal comfort, for the no-mean-sensor scenarios, the discrepancies of unmet hours for cooling mode can be as high as 1,200 h, compared with the baseline. The discrepancies of unmet hours for heating mode can be as high as 740 h, compared with the baseline. For the mean-sensor scenarios, the discrepancies of unmet hours for cooling mode can be as high as 750 h, compared with the baseline. The discrepancies of unmet hours for heating mode can be as high as 50 h, compared with the baseline.

42 ENGINEERING↗

Simulations of Grid-Responsive HVAC Cooling Measures via Ice/PCM storage

This study uses EnergyPlus building energy simulations to assess grid-responsive HVAC cooling measures during peak hours having high electricity price, including: lock the high capacity of a two-speed cooling coil during grid-response hours; and use ice/PCM energy storage to drive a chilled water coil and meet the cooling load, when shut off the main electric cooling coil. Here, the impacts on peak power reductions, energy and utility cost savings, and comfort levels in residential buildings of two U.S. cities were revealed.

Shen, Bo↗

Identifying Regions Favorable for Geothermal Heating and Cooling Storage

Space heating and cooling represents the single largest category of in building energy use for U.S. residential and commercial buildings, with heating representing 61% of residential and 46% commercial energy consumption. Building heating technologies are dominated by natural gas technologies, and are an important opportunity for building electrification to enable a transition to a low CO 2 energy system. FLXenabler study is a joint analysis effort among multiple analysis teams at NREL and focused on examining the role of geothermal heating and cooling (GHC) system with thermal energy storage (TES) providing flexibility. Utilizing information from ResStock the amount of energy consumption associated with heating and cooling by state was calculated. We applied adjusted load shapes to estimate the a maximum grid savings potential of using TES to address building space conditioning. Normalizing grid, fuel, and emissions impacts locations with higher favorability for further study in FLXenabler were identified.

15 GEOTHERMAL ENERGY↗

Optimizing Control for Efficient Load Shifting with Thermal Energy Storage in Existing HVAC Systems

This project developed the integration of a direct-contact heat exchanger (DCHX) based thermal energy storage (TES) system with a chiller–air handling unit (AHU) plant to evaluate its potential for reducing building energy costs. Detailed physical models of the TES unit, building envelope, and HVAC components were developed alongside simplified control-oriented models to support both high-fidelity simulation and real-time optimization. Two control strategies were implemented and compared: a rule-based control (RBC) aligned with utility time-of-use (ToU) rates, and a model predictive control (MPC) framework leveraging forecasts of building load, weather, and internal gains.Simulation results show that the RBC strategy reduced daily electricity costs by around 30% by shifting cooling production from on-peak to off-peak hours. In contrast, the MPC strategy achieved significantly greater performance, reducing daily operating costs by up to 44% and peak-hour costs by more than 60%. Both strategies maintained indoor thermal comfort within acceptable limits, with MPC further improving load distribution and reducing equipment cycling.The outcomes confirm that TES integration, particularly when coordinated with advanced predictive control, can provide substantial cost savings and on-peak demand reduction. . These findings directly support the U.S. Department of Energy’s goals for grid-interactive efficient buildings and demonstrate the potential of TES-enabled HVAC systems for scalable deployment across the commercial building.

99 GENERAL AND MISCELLANEOUS↗

Evaluation of phase change thermal storage in a cascade heat pump

Here this study proposes a low-global warming potential cascade heat pump system with integrated phase change material (PCM) for combined space heating and cooling. PCM is embedded in the intermediate heat exchanger that couples an outdoor R290 refrigerant circuit and an indoor CO 2 circuit. We used a clustering method to develop seasonally representative load and ambient temperature profiles for residential buildings in Minneapolis, Minnesota. We simulated the system peak shaving performance on the selected representative days, assuming three different PCM options including ice (0 °C), tetradecane (5.6 °C), and a commercially available PCM, SP9 (10.5 °C). The baseline was the same cascade system without thermal storage. We investigated the effect of both thermal energy storage capacity (kWh th ) and PCM transition temperature on system performance. The results show that higher thermal energy storage capacity shaves more electric energy until it reaches a maximum value set by the load characteristics of the building. SP9, with the highest transition temperature, shaves the most electric energy, while ice shaves the least. Moreover, ice has the highest charging cost, especially in the cooling season when the outdoor circuit has to operate at an evaporating temperature lower than 0 °C to make ice. Our results show that SP9 presents the lowest levelized cost of storage, closely followed by ice. A lower off-peak electricity rate benefits ice more than SP9 or tetradecane because ice has the largest charging cost penalty.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Advancing Mass Timber Buildings: Novel Methods Improve Thermal Assessment and Material Use

For nearly a century, thermal demand calculations for buildings have relied on simplified models developed to match the technical constraints of their era. The first standards, introduced in Germany and Austria in 1929, established climate zones and material conductivity coefficients that, with only incremental updates, still underpin many current assessments. Yet, methods such as Hot box testing, originally designed for lightweight insulation, continue to be applied for mass timber buildings, overlooking thermodynamic characteristics confer real-world advantages. Recent research at Oak Ridge National Laboratory incorporates updated methodologies, aligned with ASHRAE Standard 55 (ASHRAE, 2023) accounting for factors such as thermal inertia, inner surface temperatures, emissivity, solar gains, and dynamic outdoor conditions. These factors better reflect observed heating and cooling loads and highlight opportunities for efficient use of materials in mass timber construction. This work provides a framework for designing comfortable, resilient, and resource-efficient buildings while aligning with performance expectations in energy codes.

Pickett, Robert [International Mass Timber Allianc↗

Community Geothermal: Borefield Design, Thermal Conductivity, and Subsurface Modeling Data - Chicago, IL

This dataset encompasses the development of a geothermal energy system for the West Woodlawn neighborhood in Chicago, Illinois. This project is part of a broader initiative to design and deploy geothermal heating and cooling systems at a community scale. The dataset includes thermal conductivity test results, calculations for borehole sizing based on the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) method, as well as simulated thermal loads based on actual energy usage from individual buildings. Also provided here are files used for numerical modeling via COMSOL Multiphysics to simulate borefield design and subsurface thermal behavior. Two manuscripts are attached, which outline the broad objectives of the project and a description of the numerical modeling methodology and results.

15 GEOTHERMAL ENERGY↗

Optimizing Control for Efficient Load Shifting with Thermal Energy Storage in Existing HVAC Systems

This project developed the integration of a direct-contact heat exchanger (DCHX) based thermal energy storage (TES) system with a chiller–air handling unit (AHU) plant to evaluate its potential for reducing building energy costs. Detailed physical models of the TES unit, building envelope, and HVAC components were developed alongside simplified control-oriented models to support both high-fidelity simulation and real-time optimization. Two control strategies were implemented and compared: a rule-based control (RBC) aligned with utility time-of-use (ToU) rates, and a model predictive control (MPC) framework leveraging forecasts of building load, weather, and internal gains. Simulation results show that the RBC strategy reduced daily electricity costs by around 30% by shifting cooling production from on-peak to off-peak hours. In contrast, the MPC strategy achieved significantly greater performance, reducing daily operating costs by up to 44% and peak-hour costs by more than 60%. Both strategies maintained indoor thermal comfort within acceptable limits, with MPC further improving load distribution and reducing equipment cycling. The outcomes confirm that TES integration, particularly when coordinated with advanced predictive control, can provide substantial cost savings and on-peak demand reduction. . These findings directly support the U.S. Department of Energy’s goals for grid-interactive efficient buildings and demonstrate the potential of TES-enabled HVAC systems for scalable deployment across the commercial building.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

The Cost of Comfort in Your Home: Peak-Time Energy and Cost Savings from Setpoint Adjustment of Space Heating and Cooling

This poster presents the tradeoff between energy costs and thermal comfort in homes. Residential heating and cooling systems use a thermostat control to maintain a comfortable temperature range, but tighter temperature control leads to higher annual energy costs. We estimate the impact of temperature setpoint adjustment on annual energy costs using a residential building model developed at NREL. We show that increasing the allowable temperature range reduces energy costs in all five of the climate zones in the U.S. Annual costs reduced by about $100, with larger savings in areas with more heating and/or cooling loads.

30 DIRECT ENERGY CONVERSION↗

Exploring Grid-Interactive Efficient Building Strategies for Laboratories Through Energy Modeling

Laboratories are often overlooked in demand flexibility research due to constraints on their operations as mission critical facilities, despite the major role they play in an organization's emissions. Laboratories consume 3-4 times more energy than a typical office building and are commonly the largest energy users on any campus. Consequently, most laboratories in the United States are significant contributors to their organization's carbon footprint if their energy needs are met through the combustion of fossil fuels. As part of the initiative to decarbonize laboratories, this report documents an analysis on specifically grid-interactive efficient building (GEB) opportunities for reducing energy costs and emissions associated with laboratory operations. The goal of this initiative was to provide a case study and guidance on how to use OpenStudio and REopt as modeling tools for GEB technologies and strategies in laboratory environments across different climate zones in the United States. The analysis found that efficiency-based GEB strategies had the most significant impact on laboratory operations, while load-shedding and load-shifting GEB strategies produced smaller results. The culmination of these approaches applied across all five climate zones generated on average: 1) 28% energy cost savings and 30% greenhouse gas (GHG) emissions reductions, and 2) 4% enhanced energy cost savings under a time-of-use (TOU) pricing schedule compared to traditional pricing schemes. Grid-interactive efficiency building measures were found to produce the greatest energy savings in both electricity and natural gas, particularly in regions with high electrical loads, such as warm climates for cooling. Laboratories that had high levels of natural gas consumption, meanwhile, experienced the greatest emission reductions. The report concludes with an analysis on the opportunities for flexible loads in lab spaces and how small-scale measures in addition to opaque pricing structures for peak demand could become barriers to demand flexibility planning. The report also explores how electrifying laboratory buildings with heat pumps could reduce energy costs and GHG emissions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Evaluation of Gray-box and Machine Learning Models of a Thermal Energy Storage System with Active Insulation

An interior partition wall integrated with active thermal storage and a dynamic insulation system was built and then installed in an office building in Oak Ridge, Tennessee, TN. This smart wall, termed the Empower Wall, was equipped with embedded pipes in the building envelope core component and an additional pipe network enclosing rigid insulation to switch on and off the active insulation dynamically. The performance of the wall's contribution to cooling load reduction under different parameters has been investigated in previous publications. Aiming to be deployed into model predictive control and other optimization methods, simplified and reliable models for the developed wall and the room accommodating it are required. They are needed to characterize the properties and thermal response of both Empower Wall and building envelope, which form an essential component for accurate indoor temperature or cooling/heating demand prediction. In this study, simplified gray-box and regression models as well as machine learning model were developed and the performance of them were compared and analyzed.

Cui, Borui↗

Development of a metamodelling framework for building energy models with application to fifth-generation district heating and cooling networks

Fully defined physics-based building energy models can accurately represent building systems; however, generating models based on high-level parameters is time consuming and simulation time of complex models can be slow. This article discusses the development of a Metamodelling Framework to create metamodels from a building energy modelling dataset. The framework generates metamodels using either linear regression, random forests, or support vector regressions. A fifth-generation district heating and cooling system analysis use case was used to motivate the development of the framework. The use case required quick and accurate representations of annual building loads reported hourly. Typical annual building modelling approaches can result in a runtime of 10 min. The metamodels runtime was reduced to less than 10 s to load and run an annual simulation with user-defined covariates. The results of the metamodel performance and an abbreviated topology analysis based on the motivating use case will be presented.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Peak cooling load shift capability of a thermal energy storage system integrated with an active insulation system in US climate zones

This study aims to evaluate a thermal energy storage (TES) system integrated with an active insulation system (AIS) to form a TES + AIS integrated wall system as a partition and as a secondary cooling system to shift the peak load and reduce cooling energy consumption. To understand and demonstrate its cooling performance, the TES + AIS integrated wall system was installed in an office building in Oak Ridge, Tennessee. To investigate the effect of the TES + AIS integrated wall system in a typical office building and various climate zones, the US Department of Energy’s prototype office building model was modified to accommodate the proposed system. In this work, results showed that the minimum size of the proposed system to achieve energy savings varies depending on climate conditions. The minimum size of the proposed system for cooling energy saving and shifting peak cooling demand in climate zones 2, 3, and 5 is 29.7 m 2 , whereas it is 44.6 m 2 in zones 4 and 6. By installing the minimum size of the proposed system, 11.3 % to 16.4 % of cooling energy can be shifted during discharge hours in a representative summer day.

25 ENERGY STORAGE↗

GT Flex: A Coordinated Multi-Building Pilot Study

Buildings are a significant and untapped resource for providing utility electric grid services. Recent studies have estimated that buildings could reduce the peak demand on the electric grid in the U.S. by almost 25% through effective combinations of energy efficiency (EE) measures and load flexibility strategies (Langevin et al. 2021). The U.S. Department of Energy (DOE) has established a goal to triple energy efficiency and demand flexibility in both residential and commercial sections by 2030 compared to 2020 levels (Satchwell et al. 2021). Such findings place buildings alongside electric vehicles, photovoltaics, electric batteries, and other distributed energy resources (DERs) as primary technologies needed for supporting high renewable energy generation grids. Coordinating and optimizing multiple buildings and other DERs is more beneficial and valuable when compared with individual buildings and DERs operating as siloed resources, uncoordinated with others (Olgyay et al. 2020). A pilot study at the Georgia Institute of Technology (GIT) was conducted to evaluate value propositions of a multi-building scale project seeking carbon reduction, energy efficiency and grid-interactive capabilities, by demonstrating the means by which stakeholders can determine the technical and financial merits of grid-interactivity and energy efficiency technologies coordinated across multiple assets. The study focused on analyzing technical feasibility of deploying thermal load flexibility strategies at the multi-building scale, coordinated to not exceed existing infrastructure constraints at the pilot site. Results show that campus can provide 3-3.5 MW of potential load shed over a 4-hour event window through coordinated dispatch of thermal cooling load flexibility without exceeding existing infrastructure capacities. Under future high renewable scenarios, this thermal flexibility resource is also valuable when coordinated to reduce curtailment of intermittent renewables. Economic analyses were performed to effectively communicate various value propositions of grid-interactive and efficient building (GEB) thermal flexibility strategies. Load flexibility presents a financial value proposition to the campus today. By conducting rationalized, coordinated dispatch in response to real time price (RTP) fluctuations, the campus can benefit materially from daily price arbitrage. The RTP signal acts as an aggregating mechanism between the utility and customer to call on demand flexibility resources, with a large portion of the benefit deriving from a relatively small number of days. Realizing and maximizing this benefit with thermal load flexibility requires careful attention to the timing of pricing signals and parameterization of dispatch to overcome efficiency penalties. Grid value and signals are expected to evolve over time, and thermal load flexibility shows potential to adapt dispatch logic to support intermittent renewable generation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Analyzing the Impact of Future Weather Data on Energy Consumption in Weatherization Assistant

This study supports the mission of the U.S. Department of Energy’s Weatherization Assistance Program (WAP), which aims to increase the energy efficiency of dwellings and reduce their total residential expenditures. Specifically, we examine how projected future climate conditions may affect residential building energy performance by integrating future weather data into the National Energy Audit Tool (NEAT). Since WAP evaluates the cost-effectiveness of retrofit measures over lifespans of up to 30 years, accounting for evolving climate conditions is increasingly important. To reflect future household energy demands, this study replaces historically based Typical Meteorological Year (TMY3) weather inputs with Future Typical Meteorological Year (fTMY) datasets derived from global climate model (GCM) projections. A simulation-based framework was established to enable NEAT analysis under future weather conditions. This workflow involves converting EPW-format weather files into JSON inputs compatible with NEAT and generating degree-hour metrics needed for load calculations. The fTMY dataset used in this study was developed by Oak Ridge National Laboratory through downscaling of six GCMs under different emission scenarios and covers the period from 2020 to 2100. In contrast, the TMY3 dataset is based on historical weather data from 1961 to 1990. Simulations were conducted for benchmark single-family prototype buildings across ASHRAE climate zones 1–7, which cover all regions of the U.S. except the subarctic Zone 8 in northern Alaska, evaluating both heating and cooling loads under TMY3 and fTMY conditions. Four foundation types were tested, while heating systems were standardized, as NEAT does not differentiate thermal energy load by HVAC system type in its load calculations. Results show that fTMY weather input consistently yield lower heating loads and higher cooling loads across most locations, aligning with expected climate warming trends. Notably, colder regions such as zones 6A, 6B, and 7 experience marked reductions in heating load, while warmer and transitional zones, such as 2A (Lufkin, TX) and 3C (San Francisco, CA), have substantial increases in cooling loads. Although this study does not directly assess the performance of retrofit measures under future climate conditions, it provides a critical foundation for doing so. By quantifying shifts in baseline (i.e., pre-retrofit case) energy loads between historical and future weather files, the study highlights the importance of integrating climate-responsive data into audit tools. These findings will inform future efforts to evaluate the long-term effectiveness and cost-effectiveness of weatherization measures under changing climate conditions.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Benefits assessment of cool skin and ventilated cavity skin: Saving energy and mitigating heat and grid stress

This study assessed the energy-saving and climate-adaptive potential of cool skin and ventilated cavity skin facade technologies in Seoul's high-rise apartment buildings. We created weather scenarios for historical, mid-term future, and long-term future conditions using Coordinated Regional Downscaling EXperiment (CORDEX) method. Building energy simulations were conducted on a South Korean high-rise apartment model to evaluate their performance under different weather conditions. The results indicate that cool skin and ventilated cavity skin technologies can save cooling energy during summers but lead to heating energy penalties in winters. Ventilated cavity skin outperforms cool skin, offering better cooling energy savings and reduced heating penalties. Combining both technologies yields the highest overall energy savings, with 7 %, 9 %, and 10 % cooling energy savings for cool skin, ventilated cavity skin, and the combined package, respectively. However, cool skin increases heating energy consumption by 5 %, while ventilated cavity skin has minimal impact on heating energy. These envelope technologies also reduce peak electricity demand by at least 5 %, 8 %, and 9 %, respectively. They contribute to heat stress reduction, enhance resilience, and decrease extreme heat risks for occupants during power outages by at least 18 % under various weather conditions. Considering the prevalence of aging high-rise apartments in South Korea, adopting these envelope renovation strategies can effectively reduce cooling loads, enhance thermal comfort, and boost resilience under future climates, while avoiding costly reconstruction.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗