On the Configuration of the US Western Interconnection Voltage Stability Boundary

Abstract—Stability limits are considered in power system planning and operations to estimate the available stability margins and, if possible, to maximize the utilization of transmission facilities. These important tasks are influenced by configuration of the stability boundary. The paper introduces a new fast approach to explore the voltage stability boundary of a large system and reveal its detailed multidimensional structure. The 17939-bus U.S. Western Interconnection planning model was used to illustrate the method. Significant peculiarities of the boundary’s configuration were identified, including its nonconvexity, discontinuity, branching and internal singularities (“holes”) that were not known before and could not been found by traditional methods. Experiments using WECC system are performed to evaluate the computation time using different methods. Our results show that the proposed methods are very promising in reducing calculation time and complexity

Makarov, Yuri V.↗

Real-Time Federated Cyber-Transmission-Distribution Testbed Architecture for the Resiliency Analysis

With the ongoing automation driven by the push toward the smart electric grid and the advancement in associated cyber infrastructure, the interaction between physical [electric transmission and distribution (T&D) systems], cyber (communication, automation, and control), and human (grid operators and decision-makers) is increasingly becoming more complex. This creates the requirement of analyzing the effect of the transmission system on the distribution system and vice versa with consideration of the additional complexity of the cyber infrastructure. Such an integrated testbed will also help with resiliency analysis, where resiliency refers to the ability of the system to continue serving energy to the critical loads even with limited extreme contingencies. Interaction of the physical power grid with the cyber layer can be effectively modeled using real-time (RT) simulator for developing and validating various operational and control algorithms. Testbeds using RT simulators with multiple capabilities have been developed at different institutions. Still, no single existing testbed can offer full scalability while simultaneously meeting high fidelity requirements for resiliency experimentation. Co-simulating federated testbed assets can provide a scalable experimentation platform that can be leveraged for verification and validation. In this article, an architecture is developed for federated cyber-physical testbed. A local federation with two real-time simulators is developed: real-time digital simulator (RTDS) and OPAL-RT have been interfaced using VILLAS framework for end-to-end testing. Also, a real-time linear predictor is developed and integrated here to address the communication latency impact on geographically allocated federated RT simulation. Finally, resiliency analysis tools are formulated and utilized for T&D systems. Finally as an illustrative use case, the resiliency of a T&D test system is simulated, and the results are analyzed. A 179-bus Western Electricity Coordinating Council (WECC) transmission system is developed using OPAL-RT/ HYPERSIM, and a modified IEEE 13 node feeder system is modeled in RTDS/RSCAD and interfaced for resiliency analysis.

42 ENGINEERING↗

A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-Based Resources

This paper presents a small-signal stability analysis tool for large-scale power systems with high penetration of inverter-based resources (IBRs). Firstly, a network transfer function matrix (NTFM), which represents the information of the system topology, transmission lines, loads, IBRs locations, etc., is derived to model the entire power system network. Secondly, small-signal perturbation method is applied to obtain the sequence impedance/admittance models of the block-box IBRs considering the frequency cross-coupling effects. With the obtained NTFM as well as IBR models, a multi-input, multi-output (MIMO) feedback system is constructed, and the generalized Nyquist criterion (GNC)-based stability method is employed to analyze the stability of the entire power system. Furthermore, based on the developed stability analysis method, sensitivity analysis is conducted on an unstable case to identify which parameter has a high impact on the system stability. As a result, different test cases based on a modified IEEE 14- bus system as well as a reduced 240-bus WECC system are studied to verify the proposed stability analysis tool.

42 ENGINEERING↗

Positive-Sequence Modeling of Droop-Controlled Grid-Forming Inverters for Transient Stability Simulation of Transmission Systems

Here, this paper describes a positive-sequence model to represent two widely reported droop-controlled grid-forming inverters for bulk power systems simulation study. Methods of how to develop the equivalent voltage source behind impedance to represent inverters with and without inner control loops, modeling of P-f and Q-V droop controls, active and reactive power limiting modeling, and modeling of fault current limiting controls are described in detail. The model is implemented in commercially available positive-sequence simulation tools and compared with detailed electromagnetic transient models in both a single-grid-forming-inverter infinite-bus system and a modified IEEE 39-bus system. Finally, the model is tested on the full US Western Electricity Coordinating Council (WECC) system. Study results show that the model has a good level of accuracy compared to the detailed EMT models, and at the same time also achieves a high computational efficiency, which is suitable for the bulk power system simulation study.

42 ENGINEERING↗

On Parallelizing Single Dynamic Simulation Using HPC Techniques and APIs of Commercial Software

Time-domain simulations are heavily used in today’s planning and operation practices to assess power system transient stability and post-transient voltage/frequency profiles following severe contingencies to comply with industry standards. Because of the increased modeling complexity, it is several times slower than real time for state-of-the-art commercial packages to complete a dynamic simulation for a large-scale model. With the growing stochastic behavior introduced by emerging technologies, power industry has seen a growing need for performing security assessment in real time. This paper presents a parallel implementation framework to speed up a single dynamic simulation by leveraging the existing stability model library in commercial tools through their application programming interfaces (APIs). Several high performance computing (HPC) techniques are explored such as parallelizing the calculation of generator current injection, identifying fast linear solvers for network solution, and parallelizing data outputs when interacting with APIs in the commercial package, TSAT. The proposed method has been tested on a WECC planning base case with detailed synchronous generator models and exhibits outstanding scalable performance with sufficient accuracy.

Diao, Ruisheng↗

An Extended IEEE 118-Bus Test System With High Renewable Penetration

This article describes a new publicly available version of the IEEE 118-bus test system, named NREL-118. The database is based on the transmission representation (buses and lines) of the IEEE 118-bus test system, with a reconfigured generation representation using three regions of the US Western Interconnection from the latest Western Electricity Coordination Council (WECC) 2024 Common Case [1]. Time-synchronous hourly load, wind, and solar time series are provided for over one year (8784 hours). The public database presented and described in this manuscript will allow researchers to model a test power system using detailed transmission, generation, load, wind, and solar data. This database includes key additional features that add to the current IEEE 118-bus test model, such as: the inclusion of 10 generation technologies with different heat rate functions, minimum stable levels and ramping rates, GHG emissions rates, regulation and contingency reserves, and hourly time series data for one full year for load, wind and solar generation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Communication enabled – fast acting imbalance reserve (CE-FAIR)

This letter presents a new frequency control strategy that takes advantage of communications and fast responding resources like PV generation, energy storage, wind generation, and demand response, termed collectively as converter interfaced generators (CIGs). The proposed approach uses an active monitoring of power imbalances to rapidly redispatch CIGs. This approach differs from previously proposed frequency control schemes in that it employs feed-forward control based on a measured power imbalance rather that relying on a frequency measurement. As a result, time-domain simulations of the full Western Electricity Coordinating Council (WECC) system are conducted to demonstrate the effectiveness of the proposed method, showing improved performance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Calibrating Parameters of Power System Stability Models Using Advanced Ensemble Kalman Filter

With the ever increasing penetration of renewable energy, smart loads, energy storage, and new market behavior, today's power grid becomes more dynamic and stochastic, which may invalidate traditional study assumptions and pose great operational challenges. Thus, it is of critical importance to maintain good-quality models for secure and economic planning and real-time operation. Following the 1996 Western Systems Coordinating Council (WSCC) system blackout, North American Electric Reliability Corporation (NERC) and Western Electricity Coordinating Council (WECC) in North America enforced a number of policies and standards to guide the power industry to periodically validate power grid models and calibrate poor parameters with the goal of building sufficient confidence in model quality. The PMU-based approach using online measurements without interfering with the operation of generators provides a low-cost alternative to meet NERC standards. This paper presents an innovative procedure and tool suites to validate and calibrate models based on a trajectory sensitivity analysis method and an advanced ensemble Kalman filter algorithm. The developed prototype demonstrates excellent performance in identifying and calibrating bad parameters of a realistic hydro power plant against multiple system events.

Huang, Renke (ORCID:0000000230947073)↗

Frequency Response Assessment and Enhancement of the U.S. Power Grids towards Extra-High Photovoltaic Generation Penetrations – an Industry Perspective

Nonsynchronous generations such as photovoltaics (PVs) are expected to undermine bulk power systems (BPSs)' frequency response at high penetration levels. Though the underlying mechanism has been relatively well understood, the accurate assessment and effective enhancement of the U.S. interconnections, frequency response under extra-high PV penetration conditions remains an issue. In this paper, the industry-provided full-detail interconnection models were further validated by synchrophasor frequency measurements and realistically-projected PV geographic distribution information were used to develop extra-high PV penetration scenarios and dynamic models for the three main U.S. interconnections, including Eastern Interconnection (EI), Western Electricity Coordinating Council (WECC), and Electric Reliability Council of Texas (ERCOT). Up to 65% instantaneous PV and 15% wind penetration were simulated and the frequency response change trend of each U.S. interconnection due to the increasing PV penetration level were examined. Most importantly, the practical solutions to address the declining frequency response were discussed. This paper will provide valuable guidance for policy makers, utility operators and academic researchers not only in the U.S. but also other countries in the world.

14 SOLAR ENERGY↗

Optimal Black Start Allocation for Power System Restoration

Equipment failures, operator errors, natural disasters and cyber-attacks can and have caused extended blackouts of the electric grid. Even though such events are rare, preparedness for them is critical because extended power outages endanger human lives, compromise national security, or result in economic losses of billions of dollars. Since most of the generating units cannot restart without connecting to an energized grid, the system operator relies on a few units with the ability to start autonomously, called Black Start (BS) units, to restore the power system. Allocating and maintaining these units is costly and can severely impact the restoration security and time. We formulate an optimization problem to optimally allocate BS units in the grid, while simultaneously optimizing over the restoration sequence. We extend existing optimal allocation models by including grid considerations such as active power nodal balance, transmission switching, nodal reactive power support and voltage limits. In order to aid the branch and bound tree that solves the resulting large scale mixed integer program, we propose a randomized heuristic that is executed multiple times in parallel on a high-performance computing environment to find feasible solutions. Here, we proceed to solve the IEEE-39, the IEEE-118, and a simplified WECC system with 225 nodes and 136 generators to near optimality.

97 MATHEMATICS AND COMPUTING↗

PMU-Based Monitoring and Mitigation of Delayed Voltage Recovery Using Admittances

This project analyzes the delayed voltage recovery phenomenon by simplifying the Western Electricity Coordinating Council (WECC) composite load model using the load admittance and the thermal relay dynamics. From this analysis, a closed form expression approximating the recovery time is derived and the key load parameters impacting the behavior of voltage recovery are identified. A monitoring scheme based on the measured load admittance is then proposed to detect the onset of stalling, even in the presence of voltage oscillations, and estimate the duration of the delayed voltage recovery. A mitigation scheme utilizing smart thermostats and offline learning is also derived to ensure that the voltage recovers to the pre-contingency voltage within a specified time. Both the monitoring and mitigation schemes only need local measurements at a substation making them promising for online applications. Results for the monitoring and mitigation schemes are described in detail for the IEEE 162 bus system validating the various assumptions used for the analysis and establishing the connection between the delayed voltage recovery phenomenon and load admittance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Approximate Latent Factor Algorithm for Scenario Selection and Weighting in Transmission Expansion Planning

One major difficulty in transmission expansion planning is selecting the representative scenarios to use to evaluate candidate transmission networks. The variability in demand and renewable generation makes the inclusion of several scenarios critical when calculating reliability and cost, but including too many scenarios in an optimization is computationally intractable. To reduce the number of representative operating conditions needed to obtain an accurate approximation of the system, we propose a method rooted in multivariate statistics that exploits the latent correlative structure between different scenarios and network configurations. The proposed algorithm includes an objective and rigorous way to select a subset of scenarios that provide as much information about the system as possible, and a method to accurately approximate the system cost from that scenario subset. The result is a set of scenarios and weights that are easily incorporated into traditional transmission expansion planning formulations. We apply this to a 312-bus WECC model with 8,736 distinct operating conditions. The transmission plans found with the proposed method are more reliable and have a lower total cost than those from other scenario reduction techniques, as well as a smaller error between the expected system performance from the optimization objective and the actual system performance.

42 ENGINEERING↗

A Homotopy-Based Method for Robust Computation of Controlling Unstable Equilibrium Points

This paper proposes a homotopy-based method for efficiently computing and precisely determining controlling unstable equilibrium points (CUEPs) in transient stability analysis and screening using direct methods. The proposed method is intended to overcome potential numerical convergence problems associated with computing CUEPs. These convergence problems are mostly due to irregularities in the region of convergence of CUEPs which make it difficult to determine suitable initial points. The most commonly used initial points in computing CUEPs are minimum gradient points (MGPs) on the stability boundary which in turn rely on the determination of exit points (EPs-points at which sustained-fault trajectories exit system stability boundaries). However, determination of MGPs and EPs are computationally involved and sophisticated numerical methods have been introduced such as stability-boundary-following procedure and shadowing method to correct the solution trajectory. The proposed method does not depend on MGPs and also does not require accurate EPs. The proposed method maps the solution from EPs to the CUEPs. The proposed method is applied on several known systems including the NE 39 bus system and the reduced WECC system and the results are provided. The results are compared with the traditional methods such as Boundary of stability region based CUEP method (BCU method).

42 ENGINEERING↗

Robust System Separation Strategy Considering Online Wide-Area Coherency Identification and Uncertainties of Renewable Energy Sources

With the fast growth of renewable energy sources (RES), more and more uncertainties are involved and influencing the stable operation of power systems. Controlled islanding is the last measure to prevent power system blackouts, thus this paper aims to propose a novel model of system separation based on Online Coherency Identification and Adjustable Robust Optimization Programming (OCI-AROP) for minimizing load shedding considering the uncertainties of RES. First, Fuzzy C-Means (FCM) clustering method with F-statistics is utilized to identify the coherent generator groups with the frequency data measured by Phasor Measurement Units (PMUs). Then, the OCI-AROP model considering coherent group constraints, connectivity constraints and robustness constraints about RES are presented. Finally, the case studies on IEEE-39 bus system and WECC-179 bus system are employed to demonstrate the effectiveness of the proposed OCI-AROP model, and comparisons among the OCI-AROP model and the other models are also given to show its superiority.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forced Oscillation Source Location of Bulk Power Systems Using Synchrosqueezing Wavelet Transform

Forced oscillation source location (FOSL) plays a significant role in mitigating forced oscillations (FOs), which threaten the power system stability. Here, this paper proposes a data-driven approach for FOSL in power systems using synchrosqueezing wavelet transform (SWT). The proposed approach conducts SWT on the measured system responses to obtain the SWT matrix. Then, the SWT-based dissipating energy flow (DEF) model in time-frequency domain and dissipating energy spectrum (DES) model in frequency domain are derived from the traditional DEF model. Further, the characteristics of SWT-based DEF and DES are revealed by referring to the traditional DEF, and the FOSL criteria of the SWT-based DEF and DES can be hereby obtained. Using the obtained FOSL criteria, the FO source can be located from the measured responses. The performance of the proposed FOSL method is evaluated by simulation data of the WECC 179-bus test system and field-measurement PMU data of the ISO New England. The results confirm the accuracy and efficiency of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forced Oscillation Source Location in Power Systems Using MVMD-assisted DEF in TF Plane

Fast and accurate forced oscillation source location (FOSL) is critical for mitigating forced oscillations in power systems. Here, to overcome the shortcomings of traditional dissipating energy flow (DEF) in decomposing the forced oscillation components from the measurement responses, a multivariate variational mode decomposition (MVMD)-assisted FOSL is proposed in this paper to locate the forced oscillation sources from measurements in time-frequency (TF) plane. The multi-channel measurement matrix of each generator is formed, then the multi-channel modes are decomposed from the formed multi-channel measurement matrix using the MVMD. Further, the intrinsic mode functions (IMFs) associated with the forced oscillation mode are distinguished from the decomposed modes according to the relative energy weights. With the distinguished IMFs, the MVMD-assisted DEF calculation method is developed to locate the forced oscillation source. Finally, the performance of the proposed method is evaluated using the simulation data of the WECC 179-bus test system and IEEE-NASPI Oscillation Source Location Contest as well as the actual PMU data of ISO New England. The results validated the effectiveness and accuracy of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Data-Driven Event Detection of Power Systems Based on Unequal-Interval Reduction of PMU Data and Local Outlier Factor

With the deployment of phasor measurement units (PMU) and wide area measurement system (WAMS), it is feasible to have an insight into the events occurred in power systems based on measured data. Thus, a novel data-driven algorithm based on local outlier factor (LOF) is proposed in this work to detect and locate events in power systems using reduced PMU data. First, the unequal-interval reduction method is presented to reduce the scale of PMU data in sub-stations and reconstruct it in master station of WAMS, which can relieve the burden of communication systems. Then, principle component analysis (PCA)-based similarity search method is proposed to measure the differences of operation state between any two buses. Next, LOF is presented to detect the abnormal events in power systems, and employed to determine the region of the event source. Finally, six cases from the Western electricity coordinating council (WECC) 179-bus power system, a case from the South China power system (SCPS), and a case from the Guangdong power system (GDPS) are utilized to demonstrate the effectiveness of the proposed algorithm. Overall, the results show that proposed algorithm is effective and can be applied to event detection, event location, and online monitoring, which can enhance the situation awareness ability of power system operators.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗