Advancing Electric System Resilience with Distributed Energy Resources: A Review of State Policies

Severe weather, cyber-attacks, geomagnetic disturbances, and other hazards and threats have caused or have the potential to cause substantial levels of damage to electricity infrastructure and the global economy. Growth in distributed energy resources (DERs) and increasing attention to the resilience of the electric grid - its ability to "anticipate, absorb, adapt to, and/or rapidly recover" from disruptions, according to the Federal Energy Regulatory Commission (FERC, 2018) - have created an opportunity for energy stakeholders to develop and deploy "resilient DERs," resources in the distribution grid that improve the ability of a customer, critical facility, and/or the distribution system in general to anticipate, absorb, adapt to, and/or rapidly recover from disruptions. This paper explores how existing state regulations intersect with resilience and highlights opportunities where state regulators can employ DERs to advance resilience.

14 SOLAR ENERGY↗

Risk Management for Distributed Energy Resources

The National Institute of Standards and Technology will be hosting on Tuesday, February 2 and Wednesday, February 3, 2021, the second workshop in a new series focusing on the Open Security Controls Assessment Language. NREL extended the scope of the DERCF to include the NIST Risk Management Framework (RMF), addressing the challenges faced by federal energy managers when complying with the NIST RMF for DER systems. The NIST RMF is a cyclical process designed to incorporate principles of security and risk management into an organization’s system policies and procedures. The DER-RM will be downloadable application that runs locally and documents all the major requirements for achieving Authority to Operate the DER.

cybersecurity↗

Co-optimization of repairs and dynamic network reconfiguration for improved distribution system resilience

In this work, a post-disaster distribution system repair and restoration (DSRR) strategy is proposed to improve distribution system resilience. The DSRR strategy is formulated as a two-stage optimization. The first stage is a comprehensive co-optimization of repair crew scheduling, dynamic network reconfiguration, and distributed energy resource (DER) dispatch based on the forecast load profile. The goal is to minimize the accumulative operating cost caused by the load reduction payment as well as DER operating cost. In particular, since the number of available repair crews is usually smaller than the number of faulted lines after a disaster event, the DSRR strategy determines the optimal scheduling for repairing faulted lines. The second stage is a re-dispatch of the DER power output and load shedding based on the real-time load demand of each bus. The proposed algorithm is validated by case studies of the IEEE 33-bus and 123-bus test systems. We consider those scenarios in which faults occur in multiple heavy-loaded feeders. The simulation results demonstrate that the DSRR strategy effectively coordinate the repair scheduling, network reconfiguration and load shedding to minimize the operating cost.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Resilient Operation of Power Distribution Systems Using MPC-Based Critical Service Restoration

Power distribution systems are more prone to disruptions and cause most power system outages. We propose a service restoration technique to recover the system service (electricity delivery) following an extreme event-triggered substation outage. The proposed technique considers the problem of controlling distributed energy resources (DERs) of a distribution system with the objective of achieving maximum load pick up while satisfying network flow and voltage constraints. The problem is formulated as a model predictive control (MPC), where a linearized optimal power flow (OPF) model is employed to describe the network. The formulation is augmented with a ramping (up) reserve product for the DERs to ensure an upward monotonic load restoration as time evolves. We perform simulations considering the IEEE 13-bus test feeder integrated with wind, solar, microturbine, and energy storage devices. We demonstrate the efficacy of the devised technique in restoring the system loads monotonically, without shedding previously restored loads. We also show the benefit of co-optimization of power and reserve products for DERs on service restoration. In addition, the capability of the technique in regulating nodal voltages and reducing renewable power curtailment is demonstrated.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

Defining a Use Case for the ADMS Test Bed: Fault Location, Isolation, and Service Restoration with Distributed Energy Resources

Advanced distribution management systems (ADMS) integrate multiple enterprise-level functions into a single platform and offer advanced applications such as fault location, isolation, and service restoration (FLISR), to utilities to meet their operational needs for a modernized grid. These applications need to operate reliably even as distributed energy resource (DER) penetration increases on distribution systems. The ADMS test bed at the National Renewable Energy Laboratory offers utilities and vendors the opportunity to evaluate the performance of such advanced applications on distribution feeders of the future and to understand their potential benefits for a specific utility. This is done through defining use cases that address specific questions. This paper presents the definition of a use case on the performance of a commercially-available FLISR application on a feeder of an electric cooperative with DERs. After experiments are completed, results from this use case will be disseminated to the electric utility and research community to improve understanding of the challenges and benefits that DERs present to ADMS applications and the operation of a modernized grid.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

Scalable Predictive Control and Optimization for Grid Integration of Large-Scale Distributed Energy Resources

Integrating a large number of distributed energy resources (DERs) into the power grid needs a scalable power balancing method. We formulate the power balancing problem as a look-ahead optimization problem to be solved sequentially by a power distribution system aggregator based on a model predictive control (MPC) framework. Solving large-scale look-ahead control problems requires proper configuration of the control steps. In this paper, to solve large-scale control problems, we propose a variable time granularity where control time steps nearby the current control step have finer resolutions. The aggregator objective includes maximization of power production revenue and minimization of power purchasing expense, renewable power curtailment, and mileage costs for energy storage and electric vehicle (EV) charging stations while satisfying system capacity and operational constraints. The control problem is formulated as a mixed-integer linear program (MILP) and solved using the XpressMP solver. We perform simulations considering a copper plate representation of a large distribution network consisting of 2507 devices (control-lable DERs), including curtailable photovoltaics (PVs), energy storage batteries, EV charging stations, and buildings with heating, ventilation, and air conditioning units (HVACs). We show the effectiveness of the proposed approach in managing DERs interactively for maximum energy trading profit and local supply-demand power balancing. Finally, we demonstrate that the proposed method outperforms other benchmark controllers regarding computation time without compromising operational performance.

DER↗

Tri-Sectional Approximation of the Shortest Path to Long-Term Voltage Stability Boundary with Distributed Energy Resources

Ensuring long-term voltage stability is critical for reliable operations of power grids. High share of distributed energy resources (DERs) can create complicated system operation modes that may invalidate the traditional long-term voltage stability analysis based on typical operation modes. To address this challenge, this paper investigates how to compute the shortest path to the voltage stability boundary in the DER aggregated load space with large dispersion. Instead of working in the Euclidean space, we establish the analysis and computations on the algebraic power flow manifold to better capture the curvature change of the shortest path along the direction of losing stability. A modified optimal control framework is presented for obtaining the ground-truth of the smooth shortest path on the manifold. To efficiently and accurately solve for the shortest path, we further leverage the geometric features of the power flow manifold and propose a tri-sectional approximation model that is scalable for large-scale systems. Several numerical examples, up to the 1354-bus system, with different DER penetration levels and high dimensional renewable power injection variations are evaluated. The simulation results demonstrate that the tri-sectional approximation achieves high accuracy and efficiency to approximate the shortest path to the voltage stability boundary.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Converter-Interfaced CHP Plant for Improved Grid-Integration, Flexibility and Resiliency

GE Research and its partner GE Renewables have proposed the use of an interface converter solution to increase the penetration of small to medium-sized CHP (1MWe to 20MWe) into distribution grids and improve their flexibility and grid support capability. Indeed, the proposed interface converter solution thanks to presence of the grid-ready inverter, allows to streamline the compliance to grid codes requirements, reduce the interconnection delays and costs and ultimately one of the main barriers for CHP adoption by commercial and industrial facilities. An additional benefit provided by the interface converter is the use of the grid-ready inverter for reactive power which eliminates the need of sizing the generator for that capability. These two benefits highly favor the economic feasibility of converter-interfaced CHP. Five user cases, each in one of the leading U.S states for CHP potential reported by the DOE in its estimation of the U.S Technical Potential of CHP, were selected to compare the economic performances of converter-interfaced CHP as compared with directly-coupled. They include a college campus in California, a hospital in New York, a water reclamation plant in Texas, a hotel in Minnesota, and a large office building in Pennsylvania. Results showed that, the presence of the interface converter allows to increase the return on investment (ROI) by 0.5 to 2 percentage points in most of the cases (4 of 5). Indeed, the interface converter by shortening the interconnection process allows to accelerate revenues while reducing interconnection costs. Added to the reduced cost of the required generator these savings trade favorably the capital cost of the converter. The analysis also showed that the profitability of the converter-interfaced CHP is highly sensitive to the energy price, interconnection delay, and converter cost. However, it appears that if the interface converter can shorten the interconnection process by at least 6 months, adopting this solution will be more economically viable than directly-coupled configuration in almost all the +23,000 sites of the U.S Technical Potential CHP. The evaluation of the benefits of a converter-interfaced CHP also showed that it enables higher ROI when coupled with other distributed energy resources (DER) such as battery energy systems (BESS) or solar photovoltaic (PV). Indeed, in those scenario, the grid-ready inverter included in the interface converter eliminates the need of separate inverters if DC-coupling is used. On the technical performance, it has been verified that the presence of the interface converter allows to reduce by 70% to 80% the CHP short-circuit contribution to grid faults. This not only reduces the mechanical and thermal stresses exposed to the CHP electrical components but also increases the grid hosting capacity which ultimately enables higher penetrations CHP. Another key benefit of the interface converter validated with hardware-in-the-loop simulations and testing is its superior capability for reactive power support. Indeed, using a power hardware testbed with two +700kW inverters configured in back-to-back, a microgrid controller and actual facilities loads it was demonstrated that the presence of the interface converter can help maintain a power factor near ~1 or regulate the voltage to ~1.0pu at the point of common coupling. This benefit can be highly valuable if in the future, due to higher penetration of renewable distributed energy resources (DER), utilities start billing demand charge based on kVA instead of kW as currently. It was also validated that converter-interfaced CHP can dispatch heat and power commands and seamlessly switch between the two modes while consistently controlling the power factor or voltage at PCC. Indeed, the power hardware testing showed that grid-connected converter-interfaced CHP can follow either the power or heat demand while maintaining a unity power factor at converter output. This research proved that the adoption of an interface converter as the solution for interconnection of CHP system into the distribution grid can greatly improve the economic feasibility of small to medium-sized CHP as well as the plant power quality, flexibility and resiliency. Additionally, it allows increased penetrations of CHP into the distribution grid, extends their grid support capability, and facilitates the integration of BESS and PV DER by streamlining their collocation within the same facilities. This ultimately provides an opportunity for commercial and small industrial facilities in the U.S to accelerate their energy transition thanks to the high energy efficiency of CHP systems and its reliable, flexible, and resilient microgrid operation when interconnected with an interface converter.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Development of an Interactive Valuation Model for Distributed Energy Resource Value

The Oklahoma Secretary of Commerce & Tourism (OSCT) seeks to address perceived challenges and barriers to the deployment of distributed energy generation resources (DERs), including solar and other technologies, in the state of Oklahoma. The Scope of Work (SOW) outlines follow-on tasks related to the previous CRADA # CRD-18-762. The first task will finalize the Interactive Valuation Model Requirements Document, the final draft of which was provided in June 2018. The second task includes the building, validation, and finalization of the interactive valuation model for expressing distributed energy resource value based on user inputs to be completed by June 30, 2019. Training for how to prepare the data inputs and use the model will also be provided. To address perceived challenges and barriers to the deployment of distributed energy generation resources (DERs), including solar and other technologies, in the state of Oklahoma, the work under this CRADA will: 1) finalize the draft Interactive Valuation Model Requirements Document delivered in June 2018; 2) finish building and validating the interactive valuation model for expressing DER value based on user inputs, and 3) provide training for use of this model.

14 SOLAR ENERGY↗

Zero Export Feeder Through Transactive Markets

This project is aimed at creating a transactive energy market to address the challenges faced by utility providers when increasing distributed energy resource (DER) adoption in their service area. One major challenge is mitigating export back to the grid during times of excess production. The transactive energy market operates at the distribution level and balances the supply and demand on the feeder, thus maintaining a zero-energy export at the primary feeder head. The market participants in this case are the residential customers on the feeder, who bid into the market. Building controls are then optimized based on the settled price. Market performance was demonstrated in this study by simulating different levels of DER penetration on a selected Pepco feeder. The feeder successfully achieved a zero export while providing cost-effective electricity to the participants, demonstrating that this market design can enable high DER penetration on existing feeders.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Security Enhancements for Distributed Energy Resource Systems Interconnected with Distribution Networks: Final Technical Report

The revised IEEE 1547 Standard defines new complex communication-adjustable voltage and frequency regulation and ride-through characteristics, while maintaining the general antiislanding requirement for unintentional islanding situations. Unintentional islanding is prohibited while intentional islanding is specifically allowed, thus effectively enabling microgrid operation mode. Further, IEEE 1547-2018 Standard introduces new requirements in terms of interoperability so that the DER plant/circuit segments may be seamlessly integrated with the utility networks but at the same time become vulnerable to a cyber-attack. Traditional cybersecurity measures including encryption, authentication and role-based access control may not be fully implementable to all communication protocols specified in the IEEE 1547 Standard. Therefore, in this project we have identified, researched, implemented and tested several cyberphysical approaches that rely mostly on the behavior of the DER circuit and may help with validating the incoming command and control action potentially coming through an insecure communications channel. Additionally, we have built semantic models and communications profiles for DER facilities and have implemented lightweight IEC 61850 based publisher-subscriber GOOSE messaging mechanism, with security extensions in terms of authentication and encryption. The project proposed information models for integration into UCA OpenFMB 2.0 profiles focusing on grid code compliance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Nanoscale Ferroelectric Control of Novel Electronic States in Layered Two-Dimensional Materials (Final Report)

In this DOE Early Career project “Nanoscale Ferroelectric Control of Novel Electronic States in Layered Two-Dimensional Materials,” the PI’s group has combined ferroelectric field effect with nanoscale domain imaging and writing to design the electronic and optical properties of two-dimensional (2D) van der Waals materials, including graphene and transition metal dichalcogenides MoS2 and ReS2. The van der Waals materials have been prepared into field effect transistor (FET) devices with ferroelectric gates. Through domain patterning in a ferroelectric polymer PVDF-TrEF top-gate via conductive atomic force microscopy, the team has created programmable Schottky junctions in monolayer MoS 2 , where both barrier height and I-V rectifying polarity can be reconfigured. The transport anisotropy of monolayer to few-layer ReS 2 has been mapped out by defining the entire channel into an insulating state and creating nanoscale conducting paths along different directions through domain writing in the ferroelectric top-gate. The result shows that the conductivity along and perpendicular to the Re-chain can differ by >5.5x10 4 . Theoretical modeling points to the band origin of the transport anomaly and reveals the emergence of a flat band in few-layer ReS 2 . The interfacial epitaxial relation between ReS 2 and PVDF-TrFE further promotes the formation of close-packed, highly ordered PVDF-TrFE nanowires with width of 35 nm and 10 nm. Nonvolatile modulation of quantum Hall effect has been achieved in graphene FETs with a ferroelectric oxide Ba 0.4 Sr 0.6 TiO 3 back-gate. Scattering from the remote surface optical phonon in Ba 0.4 Sr 0.6 TiO 3 limits the room temperature mobility of graphene to be about 3x10 4 cm 2 /Vs. Steep-slope switching has been achieved in MoS 2 FETs back-gated by polycrystalline Pb(Zr,Ti)O 3 , which signals a static-state negative capacitance mode without involving an additional dielectric layer. Piezoresponse force microscopy studies show that the sub-threshold swing can be well correlated with the domain wall density in Pb(Zr,Ti)O 3 . The team also observes an unconventional filtering effect of the second harmonic generation response at the MoS 2 /Pb(Zr,Ti)O 3 heterointerface, which can be accounted for by the alignment between one of the polar axes of MoS 2 and the chiral dipole rotation at the surface of domain wall in Pb(Zr,Ti)O 3 . The research supported by this DOE grant has significantly advanced the fundamental understanding and functional design of ferroelectric/2D van der Waals heterostructures for their implementation towards energy applications.

36 MATERIALS SCIENCE↗

Capacity Markets for Transactive Energy Systems

Capacity markets provide important incentives for resource adequacy in electricity markets and may become more important for providing sufficient revenue and generation capacity with changes to energy market prices driven by increasing levels of zero marginal cost resources. However, current capacity market designs also have important shortfalls that may limit the benefits they can provide to the future grid. Current capacity markets are primarily designed for participation from conventional thermal generators, but markets are evolving with increasing levels of variable renewable energy resources. However, further reforms may be necessary to enable more participation from DERs and demand-side resources. To understand the benefits and shortfalls of current capacity market design, we review the historical reasons electricity markets have needed capacity markets or capacity payments for resource adequacy, and how current capacity market designs may create challenges for incorporating increasing levels of DERs and demand-side resources. We then consider how transactive systems, which allow the coordination of bids and offers for DERs and demand-side resources through a market interaction approach, administered by a Distribution System Operator (DSO), can address traditional resource adequacy problems due to inelastic consumer demand. We also consider the need for a DSO-level capacity market in helping to meet resource adequacy, reliability, and other electricity market objectives. We find that because the missing money in electricity markets is largely driven by incentives to meet resource adequacy goals, and the bulk grid would always supply power to the DSO, that resource adequacy is unlikely to be a determining factor in the need for a DSO-level capacity market. Many current reliability problems could also be addressed by the incorporation of more flexible demand enabled with transactive energy systems. However, other DSO objectives, including resilience, reactive power, voltage control, environmental policies, and energy equity could lead to specific challenges that could be aided by a DSO-level capacity market. We consider the possibility of a DSO-level capacity market in addressing these challenges as well as its potential role in coordinating with the Independent System Operator (ISO) who operates the wholesale market. We conclude with suggestions for future research, including the need to develop analytical models of DSO-level capacity market designs to address these potential objectives and examine their implications for DSOs and consumers.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

EVs-at-RISC: A Secure and Resilient Interoperable SCM Control System Architecture for Electric Vehicle’s-at-Scale (Final Technical Report)

The EVs-at-RISC project was a five-year research, development, and demonstration initiative to create foundational tools for utility-scale fleet aggregation and Smart Charge Management (SCM) of Electric Vehicles (EV), Electric Vehicle Charging Infrastructure (EVCI), and related Distributed Energy Resources (DER). Rather than seeking to develop and demonstrate highly perfected SCM algorithms and control strategies, this project instead focused on creating foundational software solutions that enable unprecedented digital interoperability across the communications technologies and vendor platforms used to manage EV , EVCI, and DER, as well as existing energy management infrastructure operated by utilities, grid operators, and aggregators. This project then extends these novel interoperability capabilities to develop and deploy powerful middleware abstractions across grid edge networks and EVCI/DER fleet aggregations incorporating modern software tools and best practices, such as CI/CD, to bring the immense capabilities of infrastructure-as-code and policy-as-code to modern grid edge network environments. This addresses the foremost systemic issues preventing realization of any net operational benefits from scaled deployment of behind-the-meter EV, EVCI, and DER assets in electric power grids and markets today. The results of this approach and project unlock massive potential for new SCM capabilities to be easily prototyped, evaluated, and deployed at-scale within the existing grid edge network infrastructure and EVCI/DER technology ecosystem. The EVs-at-RISC project achieves this by extending Open Field Message Bus (OpenFMB), a conceptual model for digital interoperability and distributed intelligence in traditional front-of-meter utility SCADA networks, validating our hypothesis that OpenFMB could be similarly used to solve systemic digital interoperability issues in behind-the-meter environments and unlock real-world utility-scale SCM capabilities without requiring any new proprietary vendor solutions or significant infrastructure reconfiguration.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distributed Generation Market Demand (dGen) model

The Distributed Generation Market Demand (dGen) model simulates customer adoption of distributed energy resources (DERs) for residential, commercial, and industrial entities in the United States or other countries through 2050. The dGen model can be used for identifying the sectors, locations, and customers for whom adopting DERs would have a high economic value, for generating forecasts as an input to estimate distribution hosting capacity analysis, integrated resource planning, and load forecasting, and for understanding the economic or policy conditions in which DER adoption becomes viable, and for illustrating sensitivity to market and policy changes such as retail electricity rate structures, net energy metering, and technology costs.

Array↗

Defining a Use Case for the ADMS Test Bed: Fault Location, Isolation, and Service Restoration with Distributed Energy Resources: Preprint

Advanced distribution management systems (ADMS) integrate multiple enterprise-level functions into a single platform and offer advanced applications such as fault location, isolation, and service restoration (FLISR), to utilities to meet their operational needs for a modernized grid. These applications need to operate reliably even as distributed energy resource (DER) penetration increases on distribution systems. The ADMS test bed at the National Renewable Energy Laboratory offers utilities and vendors the opportunity to evaluate the performance of such advanced applications on distribution feeders of the future and to understand their potential benefits for a specific utility. This is done through defining use cases that address specific questions. This paper presents the definition of a use case on the performance of a commercially-available FLISR application on a feeder of an electric cooperative with DERs. Results from this use case will be disseminated to the electric utility and research community to improve understanding of the challenges and benefits that DERs present to ADMS applications and the operation of a modernized grid.

61 RADIATION PROTECTION AND DOSIMETRY↗

Resilient Operation of Power Distribution Systems Using MPC-Based Critical Service Restoration: Preprint

Power distribution systems are more prone to disruptions and cause most power system outages. We propose a service restoration technique to recover the system service (electricity delivery) following an extreme event-triggered substation outage. The proposed technique considers the problem of controlling distributed energy resources (DERs) of a distribution system with the objective of achieving maximum load pick up while satisfying network flow and voltage constraints. The problem is formulated as a model predictive control (MPC), where a linearized optimal power flow (OPF) model is employed to describe the network. The formulation is augmented with a ramping (up) reserve product for the DERs to ensure an upward monotonic load restoration as time evolves. We perform simulations considering the IEEE 13-bus test feeder integrated with wind, solar, microturbine, and energy storage devices. We demonstrate the efficacy of the devised technique in restoring the system loads monotonically, without shedding previously restored loads. We also show the benefit of co-optimization of power and reserve products for DERs on service restoration. In addition, the capability of the technique in regulating nodal voltages and reducing renewable power curtailment is demonstrated.

61 RADIATION PROTECTION AND DOSIMETRY↗