At least 91 records · Page 5

Analytical Voltage Sensitivity Analysis for Unbalanced Power Distribution System

Large scale integration of distributed energy resources and electric vehicles in a transactive energy environment present new challenges in terms of voltage stability and fluctuations in a power distribution system. The impact of different level of DER/EV penetration on the voltages across the network is typically quantified through voltage sensitivity analyses. Existing methods of voltage sensitivity analysis are computationally expensive and prior efforts to develop analytical approximation lacks generality and have not been effectively validated. The objective of this work is to provide a new analytical method of voltage sensitivity analysis that has low computational cost and also allows for stochastic analysis of voltage change. This paper first derives an analytical approximation of change in voltage at a particular bus due to change in power consumption at other bus in a radial three phase unbalanced power distribution system. Then, the proposed method is shown to be valid for different load configurations, which demonstrates its generality. The results from our analytical approach is validated via classical load flow simulation of the test system based on IEEE 37 bus network. The proposed method is shown to have good accuracy, and computation complexity is of order O(1), compared to O(n3) in classical sensitivity analysis approaches.

Munikoti, Sai↗

Network-Level Optimization for Unbalanced Power Distribution System: Approximation and Relaxation

The nonlinear programming (NLP) problem to solve distribution-level optimal power flow (D-OPF) poses convergence issues and does not scale well for unbalanced distribution systems. The existing scalable D-OPF algorithms either use approximations that are not valid for an unbalanced power distribution system, or apply relaxation techniques to the nonlinear power flow equations that do not guarantee a feasible power flow solution. In this paper, we propose scalable D-OPF algorithms that simultaneously achieve optimal and feasible solutions by solving multiple iterations of approximate, or relaxed, D-OPF subproblems of low complexity. The first algorithm is based on a successive linear approximation of the nonlinear power flow equations around the current operating point, where the D-OPF solution is obtained by solving multiple iterations of a linear programming (LP) problem. The second algorithm is based on the relaxation of the nonlinear power flow equations as conic constraints together with directional constraints, which achieves optimal and feasible solutions over multiple iterations of a second-order cone programming (SOCP) problem. Finally, it is demonstrated that the proposed algorithms are able to reach an optimal and feasible solution while significantly reducing the computation time as compared to an equivalent NLPD-OPF model for the same distribution system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Planning for Resilient Power Distribution Systems using Risk-Based Quantification and Q-Learning

Grid hardening is one of the most effective approaches that reduce the component failures and restoration efforts thus increasing the resilience of the power systems against extreme events. However, hardening and upgrading the entire system is prohibitively expensive and hence the optimal design of a distribution network is challenging. This paper adopted a reinforcement learning algorithm to identify the optimal hardening strategy to enhance the resilience of power distribution systems. Adopting the Q-learning algorithm as the reinforcement learning technique, we found the sequential optimal action for hardening measures to enhance the grid's resilience for the given budget. To identify the optimal strategy through Q-learning, Conditional Value at Risk (CVaR) is used as a rewarding metric. A study on the IEEE 123-bus test feeder validate the effectiveness of the proposed model and show how to effectively allocate budget limited resources to plan a resilient power distribution network.

Paul, Shuva↗

Transmission line design for a power distribution system at 20 kHz for aircraft

A low inductance, low characteristic impedance transmission line was designed for a 20 kHz power distribution system. Several different conductor configurations were considered: strip lines, interdigitated metal ribbons, and standard insulated wires in multiwire configurations (circular and rectangular cylindrical arrangements). The final design was a rectangular arrangement of multiple wires of the same gauge with alternating polarities from wire to wire. This offered the lowest inductance per unit length (on the order of several nanohenries/meter) and the lowest characteristic impedance (on the order of one Ohm). Standard multipin connectors with gold-plated elements were recommended with this transmission line, the junction boxes to be internally connected with flat metal ribbons for low inductance, and the line to be constructed in sections of suitable length. Computer programs for the calculation of inductance of multiwire lines and of capacitances of strip lines were developed.

Zelby, L. W.↗

Enhancing Power Distribution System Resilience with Fusion-GNN: A Dynamic Graph Representation Learning Approach

This paper explores the applications of Fusion Graph Neural Network (FuGNN) on power distribution systems. FuGNN effectively models dynamic networks with evolving topology and features. Applied to power system network reconfiguration, FuGNN demonstrates its feasibility in optimizing switch configurations to minimize unserved loads and operational costs during extreme events. Additionally, FuGNN supports various downstream tasks, such as node feature prediction, further enhancing its versatility and applicability in power system resilience.

Liu, Boming↗

Joint Planning of EV Fast Charging Stations and Power Distribution Systems With Balanced Traffic Flow Assignment

To tackle the challenges introduced by the fast-growing charging demand of electric vehicles (EVs), the power distribution systems (PDSs) and fast charging stations (FCSs) of EVs should be planned and operated in a more coordinated fashion. However, existing planning approaches generally aim to minimize investment costs in PDSs while ignoring the risk of worsening traffic conditions. To overcome this research gap, this article integrates the interests of traffic networks into PDS and FCS joint planning model to mitigate negative impacts on traffic conditions caused by installing FCSs. First, a novel microscopic method that is different from traditional assignment methods is proposed to simulate the influences of FCSs on traffic flows and EV charging loads. Then, a multiobjective joint planning model is developed to minimize both the planning costs and unbalanced traffic flows. A new bilayer Benders decomposition algorithm is designed to solve the proposed joint planning model. Numerical results on two practical systems in China validate the feasibility of our microscopic method by comparing the simulated results with real data. Compared with existing approaches, it is also demonstrated that the proposed joint planning approach helps to balance traffic flow assignments and relieve traffic congestion.

bilayer expanded Benders decomposition↗

High-Frequency ac Power-Distribution System

Loads managed automatically under cycle-by-cycle control. 440-V rms, 20-kHz ac power system developed. System flexible, versatile, and "transparent" to user equipment, while maintaining high efficiency and low weight. Electrical source, from dc to 2,200-Hz ac converted to 440-V rms, 20-kHz, single-phase ac. Power distributed through low-inductance cables. Output power either dc or variable ac. Energy transferred per cycle reduced by factor of 50. Number of parts reduced by factor of about 5 and power loss reduced by two-thirds. Factors result in increased reliability and reduced costs. Used in any power-distribution system requiring high efficiency, high reliability, low weight, and flexibility to handle variety of sources and loads.

Hansen, Irving G.↗

An Asynchronous Real-time Co-simulation Platform for Modeling Interaction between Microgrids and Power Distribution Systems

This paper presents the modeling framework of an asynchronous, real-time co-simulation platform for modeling the interactions between microgrids and power distribution systems. Components of each microgrid are simulated on the OPAL-RT eMEGASIM platform so that electromagnetic transients of the inverter units are modeled at a time step of 100 microseconds. The 3-phase unbalanced distribution feeder that microgrids are connected to is simulated by using the OPAL-RT ePHASORSIM so that load transients, capacitor switching, and tap-changing events can be modeled. A MATLAB-based microgrid controller will interface controllable microgrid components through the Modbus communication. This co-simulation framework allows different microgrid controller logic to be developed and tested on a hardware-in-the-loop testbed considering both the inverter-level transient and the dynamic response of loads and utility equipment. Because the controller communicates with controllable devices via actual communication links, the impact of communication errors, delays, or denial-of-service can also be properly quantified.

Xie, Fuhong↗

Short circuit protection for a power distribution system

Sensing circuit detects when the output from a matrix is present and when it should be present. The circuit provides short circuit protection for a power distribution system where the selection of the driven load is accomplished by digital logic.

Owen, J. R., III↗

OE0000878-Master thesis Observability Analysis of Power Distribution Systems with Distributed Energy Resources Using Correlational Measurements

In this thesis, an observability analysis framework is proposed for power distribution systems. The framework analyzes the sufficiency of the available measurements for monitoring the system. In the areas of the network where sufficient sensors have been deployed, the complex voltage at the nodes may be estimated. The framework also provides a metric that quantifies the accuracy of these voltage estimates. Due to the cost of sensors and the size of distribution systems, it is frequently the case that the available measurements are insufficient for complete observability of the system. In this thesis, the author proposes the use of Correlational Measurements (CMs) for improving distribution system observability by leveraging correlation between loads and between Distributed Energy Resources (DERs). Load correlation due to class-residential, commercial, industrial, etc.- is captured via correlational load measurements, the first type of CM. Injection correlation of DERs-such as wind turbines located in proximity-is captured via correlational DER measurements, the second type of CM. This thesis presents the CM formulation and derives modified node voltage and branch current based state estimators (NVSE and BCSE) accommodating CMs. Additionally, this thesis contains an on-line parameter estimation scheme for CMs that improves the accuracy of state estimates over time. The observability analysis framework with CMs is demonstrated through simulations on the IEEE 123 Node Distribution Test Feeder. It is shown that the introduction of CMs leads to improved observability of the system with only a 0.7% decrease in state estimation accuracy for NVSE and a 0.5% increase in state estimation accuracy for BCSE.

John, Yohan M↗

MPC4CLR (Model-Predictive-Control-for-Critical-Load-Restoration-in-Power-Distribution-Systems) [SWR-22-24]

Model predictive control (MPC) is a system or process control technique for making decisions under uncertainty via rolling look-ahead optimizations at each control step where only the current step decisions are applied, and the rest are discarded. In this work, we developed an MPC for a critical load restoration (CLR) in power distribution systems to recover system service (electricity delivery) following an extreme event-triggered substation outage. The method considers the problem of controlling distributed energy resources (DERs) of the distribution system with the objective of achieving maximum load pick up while satisfying distribution network flow and voltage constraints. A linearized optimal power flow (OPF) model is employed to represent the physics of the network. The problem formulation is augmented with a ramping (up) reserve product for the DERs to ensure improved and upward monotonic load restoration as time evolves. Simulation analysis and performance tests are performed using a modified IEEE 13-bus test feeder integrated with wind, solar, microturbine, and energy storage battery. The software is developed using various software packages in Julia and Python. The MPC model is implemented using the JuMP optimization language in Julia while the data analytics including renewable generation and load demand forecasts, running the MPC simulation and visualizations is performed in Python.

Eseye, Abinet Tesfaye↗

Multi-kw dc power distribution system study program

The first phase of the Multi-kw dc Power Distribution Technology Program is reported and involves the test and evaluation of a technology breadboard in a specifically designed test facility according to design concepts developed in a previous study on space vehicle electrical power processing, distribution, and control. The static and dynamic performance, fault isolation, reliability, electromagnetic interference characterisitics, and operability factors of high distribution systems were studied in order to gain a technology base for the use of high voltage dc systems in future aerospace vehicles. Detailed technical descriptions are presented and include data for the following: (1) dynamic interactions due to operation of solid state and electromechanical switchgear; (2) multiplexed and computer controlled supervision and checkout methods; (3) pulse width modulator design; and (4) cable design factors.

Berkery, E. A.↗

Decentralized Low-Rank State Estimation for Power Distribution Systems

This article considers the low-observability state estimation problem in power distribution networks and develops a decentralized state estimation algorithm leveraging the matrix completion methodology. Matrix completion has been shown to be an effective technique in state estimation that exploits the low dimensionality of the power system measurements to recover missing information. This technique can utilize an approximate (linear) load flow model, or it can be used with no physical models in a network where no information about the topology or line admittance is available. The direct application of matrix completion algorithms requires solving a semi-definite programming (SDP) problem, which becomes computationally challenging for large networks. We therefore develop a decentralized algorithm that capitalizes on the popular proximal alternating direction method of multipliers (proximal ADMM). The method allows us to distribute the computation among different areas of the network, leading to a scalable algorithm. By doing all computations at individual control areas and only communicating with neighboring areas, the algorithm eliminates the need for data to be sent to a central processing unit and thus increases efficiency and contributes to the goal of autonomous control of distribution networks. We illustrate the advantages of the proposed algorithm numerically using standard IEEE test cases.

41 EE - Solar Energy Technologies Office (EE-4S)↗

OPERATIONAL TOPOLOGY ESTIMATION OF THREE PHASE UNBALANCED POWER DISTRIBUTION SYSTEMS WITH OUTAGES

Distribution grid, in general, is constructionally loopy but a radially operated network. Opening and closing of suitable tie-switches allows transition from one radial topology to another. Tie-switches ensure reliability and provide restoration paths when faults (outages) occur. The estimation of the system's current operational topology is a precursor to implementing any optimal control actions (during normal operation) or restorative actions (during outage condition). The existing literature in topology detection suffers with several limitations including: (1) computationally intensive nonlinear formulations that are not scalable for large distribution systems, (2) methods requiring exhaustive search for the correct topology by enumerating the complete topological search space, and (3) approaches requiring large volumes of time-series measurements and are not applicable for estimating continuously changing operational topology. Furthermore, the existing literature on distribution grid topology estimation cannot be extended to estimate the operational topology during outage conditions. For operational topology estimation during outages, our objective is to estimate both energized radial feeder and the outaged sections. Starting with a radial topology, these methods identify outaged feeder sections and hence, are inapplicable when the current radial operational topology is not known. In this work, we present a mathematical programming approach to estimate the operational topology of a three-phase unbalanced power distribution system under both outage and normal operating conditions. The aforementioned limitations of existing literature were countered by modeling the problem as a mixed-integer linear programming (MILP) problem which minimizes the errors in available measurements while satisfying the power flow and structural constraints of the system. Specically, a minimum weighted least absolute value estimator is proposed that uses the instantaneous line flow measurements, historical/ forecasted load data, and ping measurements from a limited set of smart meters and solves an MILP to identify the operational topology based on a linearized three-phase unbalanced power flow model. The proposed approach is tested on IEEE 123-bus feeder and 1069 bus multi-feeder test system and the numerical results prove the applicability of the proposed method to large three phase unbalanced grids with high errors in measurements. It is observed that the approach performs well even at high percentages of measurement errors.

GANDLURU NAGA, ANANDINI↗

Advanced Propulsion Power Distribution System for Next Generation Electric/Hybrid Vehicle: Preliminary System Studies - Phase 1

The report essentially summarizes the work performed in order to satisfy the above project objective. In the beginning, different energy storage devices, such as battery, flywheel and ultra capacitor are reviewed and compared, establishing the superiority of the battery. Then, the possible power sources, such as IC engine, diesel engine, gas turbine and fuel cell are reviewed and compared, and the superiority of IC engine has been established. Different types of machines for drive motor/engine generator, such as induction machine, PM synchronous machine and switched reluctance machine are compared, and the induction machine is established as the superior candidate. Similar discussion was made for power converters and devices. The Insulated Gate Bipolar Transistor (IGBT) appears to be the most superior device although Mercury Cadmium Telluride (MCT) shows future promise. Different types of candidate distribution systems with the possible combinations of power and energy sources have been discussed and the most viable system consisting of battery, IC engine and induction machine has been identified. Then, HFAC system has been compared with the DC system establishing the superiority of the former. The detailed component sizing calculations of HFAC and DC systems reinforce the superiority of the former. A preliminary control strategy has been developed for the candidate HFAC system. Finally, modeling and simulation study have been made to validate the system performance. The study in the report demonstrates the superiority of HFAC distribution system for next generation electric/hybrid vehicle.

Bose, Bimal K.↗

Critical Load Restoration using Distributed Energy Resources for Resilient Power Distribution System

Extreme weather events have a significant impact on the aging and outdated power distribution infrastructures. These high-impact low-probability (HILP) events often result in extended outages and loss of critical services, thus, severely affecting customers' safety. This calls for the need to ensure resilience in distribution networks by quickly restoring the critical services during a disaster. This paper presents an advanced feeder restoration method to restore critical loads using distributed energy resources (DERs). A resilient restoration approach is proposed that jointly maximizes the amount of restored critical loads and optimizes the restoration times by optimally allocating grid's available DER resources. The restoration problem is modeled as a mixed-integer linear program with the objective of maximizing the resilience to post-restoration failures while simultaneously satisfying grid's critical connectivity and operational constraints and ensuring a radial operation for a given open-loop feeder configuration. Simulations are performed to demonstrate the effectiveness of the proposed approach using IEEE 123-node feeder with 5 DERs supplying 11 critical loads and IEEE 906-bus feeder with 3 DERs supplying 17 critical loads. The impacts of DER availability and fuel reserve on restored networks are assessed and it is shown that the proposed approach is successfully able to restore a maximum number of critical loads using available DERs.

resilience, microgrids, reactive power, energy res↗