Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Microgrid operation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 91 records · Page 5

Integrated Synchronization Control of Grid-Forming Inverters for Smooth Microgrid Transition

This paper develops an integrated synchronization control technique for a grid-forming inverter operating within a microgrid that can improve the microgrid's transients during microgrid transition operation. This integrated synchronization control includes the disconnection synchronization control and the reconnection synchronization control. The simulation results show that the developed synchronization control works effectively to smooth the angle change of the grid-forming inverter during microgrid transition operation. Thus, the microgrid's transients are significantly improved compared to the case without synchronization control.

control↗

Management of Risk and Uncertainty Through Optimized Co-Operation of Transmission Systems and Microgrids with Responsive Loads (Final Report)

The evolution of the power system to the reliable, efficient and sustainable system of the future will involve development of both demand- and supply-side technology and operations. Ambitious national and state-level goals around the decarbonization of electricity relies on the integration of very high levels of renewable resources, most of which are variable and intermittent. The use of demand response is an ideal approach to counterbalance the intermittency of renewable generation and brings the consumer into the spotlight. Until recently, very little research had been conducted on the co-optimization of these two systems due to computational limitations. However, advances in computational capabilities, and the judicious use of decomposition methods and innovative approximation methods for high-dimension dynamic programming made this goal a viable objective for this project, leading to a fundamental shift in the ability to integrate and fully utilize demand-side resources. To this end, the modeling framework developed introduces a novel co-optimization framework, to include the operations of both the transmission and distribution systems (or microgrids) in operational decision making. This framework was used to analyze renewable and distributed generation along with responsive demand and to compare the capability of co-optimized systems to perform with higher levels of variable renewables. Results show that the use of a bi-level optimization approach is an appropriate structure, capable of co-optimizing a transmission system with multiple distribution systems and microgrids. While increasing the number of connected systems provides increasing flexibility for renewables integration this can also the economic benefits to the low-voltage subsystems with each additional system connected. Comparison of a traditional single-level decision structure with the co-optimization approach illustrates a reduction in overall system cost under co-optimization, while specific cost allocations to transmission and distribution systems are changed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design Power Control Strategies of Grid-Forming Inverters for Microgrid Application

This paper develops and compares two control schemes in the application control layer of a non-phase-locked loop (non-PLL) grid-forming (GFM) inverter to gain insight and understanding into how the two schemes affect the dynamic responses of GFM inverters and the transition operation of microgrids. The first scheme adopts power tracking based on an outer current loop in grid-connected mode and droop control in islanded mode, and the second uses droop control in both grid-connected and islanded modes. Analytical study is developed to compare the performance of these two strategies from various aspects, including fundamental differences, transition operation, power tracking, and P-Q capability with low point-of-common-coupling (PCC) voltages. Extensive simulation testing is carried out to validate the control performance of these two control strategies, and the simulation testing confirms the findings of the analytic study. Finally, the second strategy is recommended because of its superior control performance and ease of implementation. The analysis and results are useful in developing reliable control schemes for non-PLL GFM inverters because increasing numbers of inverters will work as non-PLL grid-forming sources in future grids because of their improved stability and reliability.

grid-forming↗

Reactive Power Control Methods for Islanded Operation

As feeder-level microgrid controls begin to incorporate multiple GFM DER and voltage regulation equipment, island reactive power dispatch strategies can be improved. Although Volt-Var Optimization (VVO) control is typical in an Advanced Distribution Management System (ADMS), most microgrid controllers do not apply VVO during island operations. This report investigates reactive power control strategies for feeder-level microgrid operations. It also proposes evaluation metrics that can be applied to analyze the performance improvements of the new microgrid control strategy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design Power Control Strategies of Grid-Forming Inverters for Microgrid Application: Preprint

This paper compares two control schemes in the application control layer of a non-PLL grid-forming (GFM) inverter to gain the insights and understanding of how the two schemes affect the dynamic responses of the GFM inverters and the transition operation of microgrids. Both schemes can achieve smooth microgrid transition operation and power tracking, however, the first scheme expects to exhibit more transients due to the feedforward of the inverse dynamic model of the output filter. Simulation results show that both control schemes achieve successful transition operation with smooth transients, and the second control scheme exhibits slightly better transients in the system frequency during islanding operation and the first one has slightly superior transients in the system frequency during reconnection operation. The power tracking performance in the grid-connected mode is evaluated, which shows that the first scheme has better active power tracking and the second one has better reactive power tracking. The analysis and results are useful to develop reliable control schemes for non-PLL GFM inverters because more and more inverters will work as non-PLL grid-forming sources in the future grids due to better stability and reliability.

grid-forming inverter↗

Interoperable, Inverter-Based Distributed Energy Resources (DERs) Enable 100% Renewable and Resilient Utility Microgrids

Project overcomes frequency stability and system control issues when operating distribution microgrids in a low inertia, high PV penetration environment without fossil fuel generators. The team implemented a grid-forming inverter and advanced control features at SDG&E's Borrego Springs Microgrid to demonstrate islanding and blackstart using renewable resources. Simulation and emulation in advance of deployment de-risks field operations.

battery energy storage systems↗

Microgrid Energy Management System Integration with Advanced Distribution Management System

The Integrated Distribution Management System (IDMS) project was initiated to demonstrate the interactive operation of microgrid systems and the distribution systems with which they interconnect. The key technologies for this are the microgrid management system and the utility distribution management system. The IDMS project successfully demonstrated that a utility’s advanced distribution management system/distributed energy resources management system (ADMS/DERMS) could effectively manage microgrids to provide visibility and control functionalities as well as use the microgrid as a dispatchable resource to support the utility grid. The DERMS accomplishes this by determining active and reactive power needs at the point of common coupling (PCC) using advanced applications like volt/VAR watt optimization (VVWO) and load relief (LR) with the underlying core applications state estimation (SE) and load flow (LF). The ADMS/DERMS can use the microgrid as a resource to resolve and prevent violations in the grid and to optimize the operational working state of the grid. The IDMS project demonstrated that a utility-operated ADMS with embedded DERMS functionality can flexibly manage a variety of microgrids and other aggregated distributed energy resources (DER) in concert with the wider distribution grid. Microgrids can provide grid services in any number of different ways to meet the operational needs of the distribution utility. The manner of aggregation — microgrid or virtual power plant — is not necessarily relevant to the utility as long as the grid services from the aggregated DER are available and can be managed by its ADMS/DERMS for the stability and reliability of the grid. The IDMS project demonstrated this integrated ADMS concept by combining hardware/software-in-the-loop testing with commercial products from different vendors and a utility’s network model. The project integrated the Schneider Electric EcoStruxure™ ADMS with DERMS with the Schweitzer Engineering Laboratories (SEL) POWERMAX ® Microgrid Control System, and the simulated resources with energy company PECO’s model of a utility-owned microgrid, establishing an operational relationship in which the utility manages the operational functionality of a microgrid at the PCC and that provides the utility with the capability to control the comprehensive power system, inclusive of the macrogrid and microgrid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Networked Microgrid Framework and Testbed for Communication, Controls, and Optimization Testing

This paper presents the development and experimental results of a networked AC microgrid testbed located at Oak Ridge National Laboratory. The testbed comprises two, 480V three-phase, four wire microgrids designed to operate standalone, grid-tied, or as a network of microgrids. This testbed represents both the state of the industry, by incorporating grid-assets commonly found in real microgrids, and the state of the art, as it is a platform to evaluate advanced controllers. The main elements of this networked microgrid testbed are presented in this paper including a Scenario Manager, local microgrid controls, and a networked microgrid control. The Scenario Manager has the objective of emulating real-world conditions. The local microgrid controller oversees standalone, grid-tied, or islanded operation. The microgrid control is a higher-level control that coordinates interaction between islanded microgrids. This paper delves into these controllers and validates their operation in the networked microgrid testbed showcasing the operational flexibility and advance control capabilities.

Ferrari Maglia, Max↗

Management of Risk and Uncertainty Through Optimized Co-Operation of Transmission Systems and Microgrids With Responsive Loads (Final Report)

The evolution of the power system to the reliable, efficient and sustainable system of the future will involve development of both demand- and supply-side technology and operations. Ambitious national and state-level goals around the decarbonization of electricity relies on the integration of very high levels of renewable resources, most of which are variable and intermittent. The use of demand response is an ideal approach to counterbalance the intermittency of renewable generation and brings the consumer into the spotlight. Though individual consumers are interconnected at the low-voltage distribution system, these resources are typically modeled as variables at the transmission network level. Demand-side participation cannot be leveraged effectively without explicitly including the distribution system dynamics in the optimization-based wholesale market operations. This project grew from a vision for co-optimized interaction of distribution systems, or microgrids, with the high-voltage transmission system. In this framework, microgrids encompass consumers, distributed renewables and storage. The energy management system of the lower voltage system (distribution or microgrid) can also sell (buy) excess (necessary) energy from the transmission system. Until recently, very little research had been conducted on the co-optimization of these two systems due to computational limitations. However, advances in computational capabilities, and the judicious use of decomposition methods and innovative approximation methods for high-dimension dynamic programming made this goal a viable objective for this project, leading to a fundamental shift in the ability to integrate and fully utilize demand-side resources. To this end, the modeling framework developed introduces a novel co-optimization framework, to include the operations of both the transmission and distribution systems (or microgrids) in operational decision making. This framework was used to analyze renewable and distributed generation along with responsive demand and to compare the capability of co-optimized systems to perform with higher levels of variable renewables. An ideal microgrid is defined as an electric entity capable of operating in both interconnected (with the high-voltage grid) and islanded mode. As such, the microgrid should incorporate generating units (traditional units and intermittent) and if needed, exchange power with the high-voltage grid. The interplay between the microgrid and high-voltage grid motivated the development of the co-optimization approach to ensure efficient performance of the interconnected network. Results show that the use of a bi-level optimization approach is an appropriate structure, capable of co-optimizing a transmission system with multiple distribution systems and microgrids. While increasing the number of connected systems provides increasing flexibility for renewables integration this can also the economic benefits to the low-voltage subsystems with each additional system connected. Comparison of a traditional single-level decision structure with the co-optimization approach illustrates a reduction in overall system cost under co-optimization, while specific cost allocations to transmission and distribution systems are changed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Jet Fuel Production at the Pittsburgh Airport: GTL via Fischer-Tropsch Synthesis

The Pittsburgh International Airport (PIT)—with the Allegheny County Airport Authority (which manages PIT)—has established itself as a leader in resiliency by becoming the first major United States (U.S.) airport to have a self-sustaining microgrid, providing electricity, heating, and cooling for airport operations. The microgrid is powered by natural gas and solar power produced on the airport property and was completed in Summer 2021. This study examines the feasibility of producing jet fuel at the airport to provide a secure supply of aviation fuel, furthering PIT’s ability to weather supply disruptions and operate self-sufficiently. Gas-to-liquids (GTL) is a commercially available technology that converts natural gas to liquid hydrocarbons, including synthetic jet fuel. A GTL facility at PIT could convert natural gas from onsite wells to jet fuel, effectively doubling the onsite fuel stores in the event of a supply disruption. Moreover, GTL provides a pathway to renewable jet fuel production and reduced greenhouse gas (GHG) emissions from the aviation sector, particularly if renewable natural gas (RNG) is used as a feedstock or other renewable energy sources are used for energy inputs. This study has found that it would be technically feasible to construct and operate a GTL facility on PIT’s property. The approximately 6,000-barrel per day (BPD) facility evaluated would produce nearly 70 million (MM) gallons (gal) of synthetic jet fuel per year, which could supplant nearly all (85 percent) current jet fuel consumption at PIT. Given the current blend limitation of 50 percent Fischer-Tropsch fuels by volume, the plant would have excess production capacity available for the United States Air Force (USAF) Pittsburgh Air Reserve Station and the USAF 171st Air Refueling Wing co-located at the airport.

03 NATURAL GAS↗

Using Energy Storage-Based Grid Forming Inverters for Operational Reserve in Hybrid Diesel Microgrids

In remote arctic communities, where access to a bulk electrical grid interconnection is not available, the implementation of islanded microgrids has been the most viable way to produce and distribute electricity services to their inhabitants. Historically, these islanded grids have relied primarily on diesel generators or hydropower resources to supply the baseload. However, this practice can result in increased expense due to the high costs associated with fuel transportation and the significant amounts of on-site storage necessary when fuel transportation is unavailable during winter months. In order to mitigate this problem, arctic microgrids have started to transition to a hybrid-source operational mode by incorporating renewable energy sources that are inherently variable in nature, such as wind or solar. Due to their highly stochastic behavior, these hybrid-source islanded microgrids can pose potential issues related to power quality due to introduction of rapid net load fluctuations and inability of diesel generators to respond rapidly. In addition, non-firm stochastic sources can require significant idling diesel generator resources to serve as spinning reserves, which is inefficient and wasteful. This work studies the problems that may arise in the transient dynamics of a real-world hybrid diesel microgrid when subjected to a loss of wind generation. Moreover, this work proposes a transition from a diesel spinning reserve to a battery energy-storage system (BESS) operating reserve scheme. The study of the proposed transition is important in establishing the fundamental implication of transient dynamics and the potential benefits of integrating a BESS as a spinning reserve in terms of stability, frequency nadir, and transient voltage deviation. The methods to investigate and validate the transient dynamics relied on both electromagnetic simulation models of GFMIs and a commercially available GFMI in an experimental power hardware-in-the-loop setup. The simulation results showed that the proposed operating reserve scheme improves the power quality of the system in terms of voltage deviation and frequency nadir when the microgrid is subjected to a loss of wind generation scenario. Depending on the simulation cases, adding a GFMI reduced the frequency nadir between 65.3% and 86.7%. Moreover, the reductions in the voltage deviations improved between 3.6% and 23.0%. From these results it can be concluded that the integration of a GFMI can reduce the frequency nadir in a hybrid diesel microgrid, and in turn, reduce diesel consumption, which improves system reliability while reducing fuel expenses. Furthermore, the novelty of this work relies on the fact that the offline simulation results were validated using a power hardware-in-the-loop platform that incorporated a 100 kVA commercially available GFMI as the device under test.

Hernandez-Alvidrez, Javier↗

Inverter Controls for Smooth Transition Operation and Voltage Balancing of Networked Microgrids

With increasing penetrations of distributed energy resources (DERs), researchers have extensively studied the formation and networking of microgrids to improve reliability during distribution system outages. However, these operations might require DERs in the microgrids to switch between grid-following (GFL) and grid-forming (GFM) modes of operation. A smooth transition between the operation modes should be ensured to have a stable system operation and to avoid nuisance tripping. Additionally, as we network microgrids, inverter control schemes with voltage-balancing controls are needed for unbalanced distribution networks. This paper presents the design of a GFM and GFL capable inverter control scheme for reliable operation in networked microgrids with mechanisms for 1) smooth transition between the GFL and GFM modes, and 2) negative sequence voltage control for voltage balancing. Using electromagnetic transient (EMT) simulations, the control scheme is first tested on a simple two-source power system using a digital real-time simulator. Next, a real-world distribution feeder with unbalanced loading and multiple DERs is used to demonstrate stable operation during the networking of microgrids with voltage balance support.

distributed energy resources↗

Networked Microgrid Cybersecurity Architecture Design Guide: A New Jersey TRANSITGRID Use Case

Microgrids require reliable communication systems for equipment control, power delivery optimization, and operational visibility. To maintain secure communications, Microgrid Operational Technology (OT) networks must be defensible and cyber-resilient. The communication network must be carefully architected with appropriate cyber-hardening technologies to provide security defenders the data, analytics, and response capabilities to quickly mitigate malicious and accidental cyberattacks. In this work, we outline several best practices and technologies that can support microgrid operations (e.g., intrusion detection and monitoring systems, response tools, etc.). Then we apply these recommendations to the New Jersey TRANSITGRID use case to demonstrate how they would be deployed in practice.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Practice Summary: Improved Reliability via Optimization in Residential Microgrids

Southern Company is an electric utility that is embracing residential microgrids as a platform for distributed energy. The first residential microgrid in the southeastern United States was constructed in Hoover, Alabama, as a testbed for development. To operate the microgrid, we developed an optimization model for unit commitment and economic dispatch. We report the optimization model was implemented in a microgrid central controller and tested under various operational scenarios. Challenges also include developing a pricing algorithm to deliver price forecasts to the residential homes in the microgrid and open-source software restrictions.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

FY 2021 Isolated Grids and Grid-Connected Turbine Reference Systems; Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL)

For individuals, businesses, and communities focused on building resilient electrical grid infrastructure, wind energy can provide an affordable, accessible, and compatible distributed energy resource option that also enhances the capabilities of local grid operations. The Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL) project is a multi-year distributed wind research effort, driven through a partnership between four Department of Energy National Laboratories and industry to develop and improve the planning, design, and operation of wind-centered microgrids to complement solar, energy storage, and other distributed energy resources for grid-tied and isolated operation (U.S. Department of Energy, 2021). This report documents the application of methods developed through the initial three years of the MIRACL project to two real-world distributed wind reference systems. Specifically, the methods demonstrated in this report include 1) a market valuation framework to comprehensively value the services distributed wind can provide and 2) a resilience framework that enables stakeholders to characterize distribution system resilience and compare grid investment decisions from a resilience perspective. Additional methods mentioned in this report include distributed hybrid system design methods for grid resilience, advanced control co-simulation platforms, and power hardware-in-the-loop (PHIL) models. Preliminary results from these additional methods are presented in this report and will be demonstrated and/or applied to the reference systems in the coming year. The purpose of applying these methods to reference systems is to drive technology transfer of the theories, methodologies, and technologies developed under the MIRACL project and increase the number of referenceable case studies available to stakeholders interested in additional value-added capabilities of wind systems beyond bulk energy supply (i.e. kilowatt-hours).

17 WIND ENERGY↗

Power Hardware-in-the-Loop Interfaces for Inverter-Based Microgrid Experiments Including Transitions: Preprint

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop (HIL) simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such microgrid interfaces are particularly challenging to model when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents two PHIL interfaces for such microgrids and the preliminary experimental results: One interface is suitable for those who have access to a power amplifier that can operate as a controllable current source, and the other is for those who need a solution that uses a voltage-mode power amplifier.

battery energy storage system↗

Networked Microgrid Energy Management Considering Ownership and Control Structures: A Comparison

With the growing deployment of microgrids, networked microgrids have emerged for their additional advantages of economy, reliability and resilience by coordinating the operation of multiple microgrids. As microgrids are operated with different ownership, objectives and functionalities, the formed networked microgrids show characteristics of mixed ownership, inconsistent objectives and various functionalities. To enable the coordinated operation of networked microgrids, three control structures, i.e., centralized, distributed and decentralized, have been constructed in the literature. However, the data sharing enabling these different paradigms and the resulted value propositions are not well defined, leading to poor resource management and resilience, etc. To solve this issue, a complete comparison of networked microgrid energy management under centralized, distributed and decentralized structures are performed. As a novel contribution, the required minimum data exchange of networked microgrid energy management under three control structures are identified, respectively. The value propositions are calculated and compared against each other by the results of case studies.

control structures↗

Operational Resilience of Nuclear-Renewable Integrated-Energy Microgrids

The increasing prevalence and severity of wildfires, severe storms, and cyberattacks is driving the introduction of numerous microgrids to improve resilience locally. While distributed energy resources (DERs), such as small-scale wind and solar photovoltaics with storage, will be major components in future microgrids, today, the majority of microgrids are backed up with fossil-fuel-based generators. Small modular reactors (SMRs) can form synergistic mix with DERs due to their ability to provide baseload and flexible power. The heat produced by SMRs can also fulfill the heating needs of microgrid consumers. This paper discusses an operational scheme based on distributed control of flexible power assets to strengthen the operational resilience of SMR-DER integrated-energy microgrids. A framework is developed to assess the operational resilience of SMR-DER microgrids in terms of system adaptive real-power capacity quantified as a response area metric (RAM). Month-long simulation results are shown with a microgrid developed in a modified Institute of Electrical and Electronics Engineers (IEEE)-30 bus system. The RAM values calculated along the operational simulation reflect the system resilience in real time and can be used to supervise the microgrid operation and reactor’s autonomous control.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗