ComStock Measure Scenario Documentation: Chiller Replacement

Building on a 3-year effort to calibrate and validate the U.S. Department of Energy's ResStock (TM) and ComStock (TM) models, this work produces national datasets that empower analysts working for federal, state, utility, city, and manufacturer stakeholders to answer a broad range of questions regarding their commercial building stock. ComStock is a highly granular, bottom-up model that uses multiple data sources, statistical sampling methods, and advanced building energy simulations to estimate the annual energy consumption (at a subhourly resolution) of the commercial building stock across the United States. The baseline model intends to represent the U.S. commercial building stock as it existed in 2018. The methodology and results of the baseline model are discussed in the final technical report of the End-Use Load Profiles project. The goal of this work is to develop energy efficiency and demand flexibility end-use load shapes that cover high-impact, market-ready (or nearly market-ready) measures. "Measures" refers to various "what-if" scenarios that can be applied to buildings. An end-use savings shape is the difference in energy consumption between a baseline building (or collection of buildings) and a building with an energy efficiency or demand flexibility measure applied. It results in a time-series profile broken down by end use and fuel (electricity or on-site gas, propane, or fuel oil use) at each time step, as well as annual aggregations. This report describes the modeling methodology for a single end-use savings shape measure - chiller replacement - and briefly introduces key results. The full public dataset can be accessed on the ComStock (TM) data lake or via the Data Viewer at comstock.nrel.gov. The public data set enables users to create custom aggregations of results for their use case (e.g., filter to a specific county).

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

End-Use Load Profiles for the U.S. Building Stock

The End-Use Load Profiles for the U.S. Building Stock project uses New ResStock and ComStock models to statistically represent the energy use of U.S. buildings. The project's hybrid approach combines best-available ground truth data, such as submetering studies and statistical disaggregation of whole-building interval meter data, with the reach, cost-effectiveness, and granularity of physics-based and data-driven building stock modeling to deliver a nationally-comprehensive data set at a fraction of the historical cost.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

ResStock: Annual Baseline Results with Component Loads

The ResStock Analysis Tool was developed by NREL with support from the U.S. Department of Energy to provide a new approach to large-scale residential analysis by combining large public and private data sources, statistical sampling, detailed sub hourly building simulations, and high-performance computing. This combination achieves unprecedented granularity and accuracy in modeling the diversity of the housing stock and the distributional impacts of building technologies in different communities. The annual baseline energy results from a national-scale ResStock run use typical meteorological year 3 (TMY3) files for energy simulations. Results include heating and cooling loads for individual components of each building. Component loads describe the heating/cooling load that can be attributed to specific elements of a home, such as heat transfer through walls or internal gains. Additionally, these results include the standard ResStock outputs for housing characteristics and numerous energy outputs by end-use and fuel. A snapshot of the ResStock version used to produce this data, including a configuration file for the run can be found using the Source Code resource link.

Array↗

ComStock Measure Documentation: Lighting Control for Load Shedding

This report describes the modeling methodology for a single end-use savings shape measure - lighting control for load shedding - and briefly introduces key results. The lighting control for load shedding measure applies lighting dimming control to reduce the lighting load during the building's electricity peak window every weekday. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start and end times of the predicted peak window, and then adjusts the lighting dimming level by a percentage reduction from the original schedules during the peak window to reduce the peak demand. The measure is applicable to (large, medium and small) offices, warehouses, and primary and secondary schools, which correspond to approximately 68% of the stock floor area of commercial buildings in ComStock analysis. The measure demonstrates 2%-7% daily peak demand reduction performance for applicable buildings, and 0.43% total site energy savings (0 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Urban building energy modeling (UBEM) tools: A state-of-the-art review of bottom-up physics-based approaches

Regulations corroborate the importance of retrofitting existing building stocks or constructing new energy-efficient districts. There is, thus, a need for modeling tools to evaluate energy scenarios to better manage and design cities, and numerous methodologies and tools have been developed. Among them, Urban Building Energy Modelling (UBEM) tools allow the energy simulation of buildings at large scales. Choosing an appropriate UBEM tool, balancing the level of complexity, accuracy, usability, and computing needs, remains a challenge for users. The review focuses on the main bottom-up physics-based UBEM tools, comparing them from a user-oriented perspective. Five categories are used: (i) the required inputs, (ii) the reported outputs, (iii) the exploited workflow, (iv) the applicability of each tool, and (v) the potential users. Moreover, a critical discussion is proposed, focusing on interests and trends in research and development. The results highlighted major differences between UBEM tools that must be considered to choose the proper one for an application. Finally, barriers of adoption of UBEM tools include the needs of a standardized ontology, a common three-dimensional city model, a standard procedure to collect data, and a standard set of test cases. This feeds into future development of UBEM tools to support cities’ sustainability goals.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

ComStock Measure Documentation: Thermostat and Lighting Control for Load Shedding

This report describes the modeling methodology for an upgrade package of two end-use savings shape measures - Thermostat Control for Load Shedding and Lighting Control for Load Shedding - and briefly introduces key results. The package combines thermostat control for load shedding and lighting control for load shedding measures to reduce the HVAC and lighting load during the building's electricity peak window every weekday. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start and end times of the predicted peak window, and then relaxes the thermostat setpoints and dims the lighting level from the original schedules during the peak window to reduce the peak demand. The measure is applicable to (large, medium and small) offices, warehouses, and primary and secondary schools, which correspond to approximately 68% of the stock floor area of commercial buildings in ComStock analysis. The measure demonstrates 3%-10% daily peak demand reduction performance for applicable buildings, and 0.97% total site energy savings (0 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

ComStock Measure Documentation: Thermostat and Lighting Control for Load Shedding + Photovoltaics With 40% Rooftop Coverage

This report describes the modeling methodology for an upgrade package of two end-use savings shape measures - Thermostat Control for Load Shedding and Lighting Control for Load Shedding - and briefly introduces key results. The package combines thermostat control for load shedding, lighting control for load shedding, and PV with 40% rooftop coverage measures to reduce the net building load during the building's electricity peak window every weekday. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start and end times of the predicted peak window, and then relaxes the thermostat setpoints and dims the lighting level from the original schedules during the peak window to reduce the peak demand, while applying the fixed rooftop PV application for onsite electricity generation. The measure is applicable to (large, medium and small) offices, warehouses, and primary and secondary schools, which correspond to approximately 68% of the stock floor area of commercial buildings in ComStock analysis. The measure demonstrates 5%-15% daily peak demand reduction performance for applicable buildings, and around 1% total site energy savings (0 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.

14 SOLAR ENERGY↗

Air Handling Unit Shutdowns During Scheduled Unoccupied Hours: US Commercial Building Stock Prevalence and Energy Impact

Commercial buildings account for 18% of U.S. energy consumption, with 44% used for heating, ventilation, and air conditioning (HVAC). American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) 90.1 requires HVAC systems to shutdown fans and outdoor air ventilation during unoccupied times, only allowing fans to cycle on, without outdoor air, to maintain thermostat setpoints. However, it is minimally understood how often existing building operations align with energy code requirements and the energy implications of not doing so. This study used building automation system data from 843 buildings containing 5706 air handling units (AHUs) to determine three unoccupied AHU shutdown control schemes ranging in efficiency and then estimated their prevalence in the U.S. commercial building stock, segmented by building type. ComStock was then used to analyze the energy savings potential of implementing the most energy efficient unoccupied shutdown control scheme in non-participating buildings across the U.S commercial building stock. Results show that only 23% of AHUs align completely with the ASHRAE 90.1 requirement. ComStock modeling results show 4% annual stock energy savings by switching all non-participating buildings to the most efficient scheme, with 19% annual energy savings demonstrated for the median building switching from the least efficient scheme to the most efficient. Findings also show 114.5 TBtu electricity and 75.8 TBtu natural gas fuel savings when converting to the most efficient scheme. Furthermore, these findings help stakeholders understand the high prevalence of buildings not aligning with the ASHRAE-90.1 requirements for unoccupied AHU shutdowns and the energy savings potential of utilizing the most efficient unoccupied AHU shutdown scheme.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

End-Use Savings Shapes Measure Documentation: Thermostat Control for Load Shedding in Large Offices

This documentation focuses on a single End-Use Savings Shape measure - thermostat control for load shedding. The thermostat control for load shedding measure applies heating and cooling temperature setpoint offsets for reducing the heating and cooling load during peak window. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start and end times of the peak window, and then adjusts the thermostat cooling and/or heating setpoints by an offset value from original schedules during the peak window to reduce the HVAC or whole building daily peak load. The measure is flexible and allows users to adjust the heating and cooling offset values respectively, but for this study, the adjustment for heating and cooling setpoints are set to -2 degrees Celsius and +2 degrees Celsius by default. The measure provides options of adding rebound control period (default 2 hours) after peak windows for the setpoints to be ramped back to default values, to prevent the system from generating higher peak demand with step changes of setpoints in post-peak periods . This measure is applicable t o large offices equipped with electric HVAC system (either electric cooling only or both electric heating and cooling), which account for approximately 8.72% of the ComStock floor area. The thermostat control for load shedding measure demonstrates 2-5% daily peak demand reduction and 0.068% total site energy savings (3 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

End-Use Savings Shapes Measure Documentation: Thermostat Control for Load Shifting in Large Offices

This documentation focuses on a single end-use savings shape measure - thermostat control for load shifting. The thermostat control for load shifting measure applies heating and cooling temperature setpoint adjustment for pre-conditioning before the peak window. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start time of the peak window, and then adjusts the thermostat cooling or heating setpoints by a specified offset value from original schedules to precool or preheat the space , for a specified length of time before the start of peak window, and thus shifts load in the peak window to the pre-conditioning period. The measure is flexible and allows users to adjust the heating and cooling offset values and length of pre-conditioning period, but for this study, the load shifting strategy is applied as pre-cooling only (adjusting only cooling setpoints). The default adjustment for cooling setpoints is set to -1 degrees Celsius , and the default duration of pre-cooling is 1 hour. This measure is applicable to large offices equipped with electric HVAC system, which account for approximately 8.72% of the ComStock floor area. The thermostat control for load shifting measure demonstrates -1% daily peak demand reduction and 0% total site energy savings (0 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Addressing the Split Incentive Challenge for Enhanced Solar Adoption in Multifamily Rental Properties [Abstract]

The split incentive problem is particularly pronounced in rental markets, where landlords prioritize investments that directly increase property value or rental income. Since energy savings from solar photovoltaic (PV) systems primarily benefit tenants, landlords may perceive little return on investment unless mechanisms exist to recapture some of the financial gains. The primary objective of this project is to develop a publicly available, web-based tool to analyze the U.S. Department of Energy’s ResStock database, which models the U.S. residential building stock. The tool allows users to filter buildings by location, type, HVAC system, square footage, and other characteristics, and outputs typical electric load profiles. By leveraging location-specific electric load data, Fram Energy aims to advance business strategies that address the split incentive barrier and promote the adoption of solar PV installations in rental properties. In addition, a machine learning model will be developed to weigh the marginal contribution of building features across the dataset in predicting electricity demand, supporting guided decision making in forecasting electric load profiles. Lastly, based on each building’s location, load profile, and utility’s electricity rate, an optimized solar photovoltaic array and battery energy storage system will be sized to provide energy arbitrage opportunities.

14 SOLAR ENERGY↗

ResStock Measure Documentation: Residential Two-Stage Geothermal Heat Pump (4.0 COP, 20.5 EER) With Envelope Improvements and Advanced Air Sealing

The goal of this work is to develop energy efficiency, demand flexibility, and other retrofit end-use load shapes (electricity, gas, propane, or fuel oil) that cover a majority of the high-impact, market-ready (or nearly market-ready) measures. "Measures" refers to retrofits that can be applied to buildings during modeling. An "end-use savings shape" is the difference in energy consumption between a baseline building and a building with an energy efficiency, demand flexibility, or other retrofit measure applied. It results in a time-series profile that is broken down by end use and fuel (electricity or on-site gas, propane, or fuel oil use) at each time step. ResStock is a highly granular, physics-based, bottom-up model that uses multiple data sources, statistical sampling methods, and advanced building energy simulations to estimate the annual subhourly energy consumption of the residential building stock across the United States. The baseline model intends to represent the U.S. residential building stock as it existed in 2018. Technical documentation for the inputs and assumptions in the baseline building stock model is available in Reyna et al. (2025). Calibration and validation of the baseline model results are available in the final technical report of the End-Use Load Profiles project (Wilson, et al. 2022). This document focuses on a single end-use savings shape measure: Residential Two-Stage Geothermal Heat Pump (GHP) (4.0 COP, 20.5 EER) With Envelope Improvements. This measure combines a two-stage GHP with envelope improvements as a single package. As this package is a combination of two other measures, this document focused on documenting the results associated with this combination of technologies, with individual measure documents for two-stage GHPs and envelope improvements providing the information on the details of these measures. When the two technologies are combined, envelope improvements can modestly reduce energy consumption by a further 10%-15%, but also reduce the required size of the ground heat exchanger and heat pump by approximately 33% on average across all sites. The cost of installing envelope improvements in these homes is likely to be more than paid for by the reduction in equipment and drilling costs in these buildings for the majority of the stock.

15 GEOTHERMAL ENERGY↗

ResStock Measure Documentation: Residential Single-Stage Geothermal Heat Pump (3.8 COP, 18.6 EER)

The goal of this work is to develop energy efficiency, demand flexibility, and other retrofit end-use load shapes (electricity, gas, propane, or fuel oil) that cover a majority of the high-impact, market-ready (or nearly market-ready) measures. "Measures" refers to retrofits that can be applied to buildings during modeling. An "end-use savings shape" is the difference in energy consumption between a baseline building and a building with an energy efficiency, demand flexibility, or other retrofit measure applied. It results in a time-series profile that is broken down by end use and fuel (electricity or on-site gas, propane, or fuel oil use) at each time step. ResStock is a highly granular, physics-based, bottom-up model that uses multiple data sources, statistical sampling methods, and advanced building energy simulations to estimate the annual subhourly energy consumption of the residential building stock across the United States. The baseline model intends to represent the U.S. residential building stock as it existed in 2018. Technical documentation for the inputs and assumptions in the baseline building stock model is available in Reyna et al. (2025). Calibration and validation of the baseline model results are available in the final technical report of the End-Use Load Profiles project (Wilson et al. 2022). This documentation focuses on a single end-use savings shape measure: Residential Single-Stage Geothermal Heat Pump (GHP).?Single-stage GHPs are able to reduce energy consumption by 31% for the entire stock. Additional results provided below detail how savings changes for sections of the housing stock with different base heating fuel and in different climate zones, as well as the savings potential by state for both heating and cooling. Utility bills and electric panel impacts are also shown and discussed.

15 GEOTHERMAL ENERGY↗

Highly Resolved Reference Projections of Building Energy Use for the Contiguous United States: Building Sector Energy Baselines, Projection Methods, and Results

This report describes one methodology of projecting energy consumption of the US residential and commercial building sectors using NREL's ResStock™ and ComStock™ as well as growth rates derived from EIA's Annual Energy Outlook (AEO). The impetus for this work is to provide an intermediate method for compiling demand-side sectoral energy projections that is suitable for grid-scale analysis, such as NREL's Standard Scenarios. ResStock and ComStock are physics-based and statistically representative building stock models of the US residential and commercial sector, respectively. Using the 2012 actual meteorological year (AMY) weather data, the sectoral energy baselines are simulated and then segmented along key dimensions (e.g., geography, dwelling/building type). The segmented results are then scaled using the corresponding annual growth rates derived from the 2021 AEO reference case to produce energy projections out to 2050. The compiled result is a demand-side grid model (dsgrid) data set suitable for use in NREL's large-scale grid models, such as the Regional Energy Deployment System (ReEDS). This simple projection method does not endogenously represent how the building stock could evolve through time. Most notably, it does not reflect large-scale electrification, for example, the conversion of space heating, water heating, clothes drying, and cooking from primary fossil fuels to electricity, as this is not part of AEO's reference case assumptions. Nonetheless this approach is more resolved and potentially extensible compared to the current method used by Standard Scenarios's reference case, which augments a sector's total load based on a single growth rate from AEO.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

End-Use Savings Shapes Measure Documentation: Boiler Replacement with Air-Source Heat Pump Boiler and Electric Boiler Backup

Building on the successfully completed effort to calibrate and validate the U.S. Department of Energy's ResStock TM and ComStock TM models over the past three years, the objective of this work is to produce national data sets that empower analysts working for federal, state, utility, city, and manufacturer stakeholders to answer a broad range of analysis questions. The goal of this work is to develop energy efficiency, electrification, and demand flexibility end-use load shapes (electricity, gas, propane, or fuel oil) that cover a majority of the high-impact, market-ready (or nearly market-ready) measures. "Measures" refers to energy efficiency variables that can be applied to buildings during modeling. An end-use savings shape is the difference in energy consumption between a baseline building and a building with an energy efficiency, electrification, or demand flexibility measure applied. It results in a time-series profile that is broken down by end use and fuel (electricity or on-site gas, propane, or fuel oil use) at each timestep. ComStock is a highly granular, bottom-up model that uses multiple data sources, statistical sampling methods, and advanced building energy simulations to estimate the annual sub hourly energy consumption of the commercial building stock across the United States. The baseline model intends to represent the U.S. commercial building stock as it existed in 2018. The methodology and results of the baseline model are discussed in the final technical report of the End-Use Load Profiles project. This documentation focuses on a single end-use savings shape measure—boiler replacement by air-source heat pump boiler. This measure replaces space heating natural gas boilers by air-source heat pump boilers when applicable and helps quantify the decarbonization as well as the energy savings potential from the replacement. The measure resulted higher savings in natural gas consumption compared to the increase in electricity consumption, with a ratio of 2.9. The total natural gas energy consumption was reduced by 20%, whereas the total electricity consumption was increased by 2.5%.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

End-Use Savings Shapes Measure Documentation: Boiler Replacement with Air-Source Heat Pump Boiler and Natural Gas Boiler Backup

Building on the successfully completed effort to calibrate and validate the U.S. Department of Energy's ResStock (™) and ComStock (™) models over the past three years, the objective of this work is to produce national data sets that empower analysts working for federal, state, utility, city, and manufacturer stakeholders to answer a broad range of analysis questions. The goal of this work is to develop energy efficiency, electrification, and demand flexibility end-use load shapes (electricity, gas, propane, or fuel oil) that cover a majority of the high-impact, market-ready (or nearly market-ready) measures. "Measures" refers to energy efficiency variables that can be applied to buildings during modeling. An end-use savings shape is the difference in energy consumption between a baseline building and a building with an energy efficiency, electrification, or demand flexibility measure applied. It results in a time-series profile that is broken down by end use and fuel (electricity or on-site gas, propane, or fuel oil use) at each timestep. ComStock is a highly granular, bottom-up model that uses multiple data sources, statistical sampling methods, and advanced building energy simulations to estimate the annual subhourly energy consumption of the commercial building stock across the United States. The baseline model intends to represent the U.S. commercial building stock as it existed in 2018. The methodology and results of the baseline model are discussed in the final technical report of the End-Use Load Profiles project. This documentation focuses on a single end-use savings shape measure - boiler replacement with air-source heat pump boiler with natural gas boiler backup. This measure replaces natural gas boilers for HVAC application by air-source heat pump boilers when applicable and use natural gas boiler backup when the heat pump boiler could not operate due to outdoor air conditions which are below its cutoff temperature. This measure helps to quantify the decarbonization as well as the energy savings potential from the replacement. The measure resulted higher savings in natural gas consumption compared to the increase in electricity consumption, with a ratio of 3. The total natural gas energy consumption was reduced by 41%, whereas the total electricity consumption was increased by 5.3%.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗