Interconnection Cost Analysis in the PJM Territory

Electric transmission system operators (ISOs, RTOs, or utilities) require new large generators seeking to connect to the grid to undergo a series of impact studies before they can be built. This process establishes what new transmission equipment or upgrades may be needed before a project can connect to the system and assigns the costs of that equipment. Berkeley Lab has collected interconnection cost data from interconnection studies for the PJM Territory, representing nearly 86% of all new unique generators requesting interconnection from 2000 to 2022. Project-level cost summary data are available for download on this page. We find: -Average interconnection costs have grown as the number of interconnection requests have escalated -Projects that have completed all required interconnection studies have the lowest cost compared to applicants still actively working through the interconnection process or those that have withdrawn. -Broader network upgrade costs are the primary driver of recent cost increase. -Potential interconnection costs for wind, storage, and solar are larger than for natural gas -Larger generators have greater interconnection costs in absolute terms, but economies of scale exist on a per kW basis. -Interconnection costs vary by location Berkeley Lab will publish a series of short analytical papers of generator interconnection costs to the transmission system for MISO, PJM, SPP, ISO-NE and NYISO, which you can find at https://emp.lbl.gov/interconnection_costs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Generator Interconnection Cost Analysis in the Southwest Power Pool (SPP) Territory

Electric transmission system operators (ISOs, RTOs, or utilities) require new large generators seeking to connect to the grid to undergo a series of impact studies before they can be built. This process establishes what new transmission equipment or upgrades may be needed before a project can connect to the system and assigns the costs of that equipment. Berkeley Lab has collected interconnection cost data for 845 projects from interconnection studies for the Southwest Power Pool (SPP) Territory. The studies were performed between 2002 and 2023 and include all of the most refined cost estimates available. Project-level cost summary data are available for download on this page. We find: -Project-specific interconnection costs can differ widely. -Average interconnection costs are stable for projects that complete all interconnection studies but have escalated for those that withdraw. -Broader network upgrade costs are the primary driver of recent cost increases, especially for withdrawn projects. -Potential interconnection costs of all solar and wind requests have been greater than those of storage and natural gas projects. -Economies of scale exist for completed wind and solar projects but not for other fuel types or withdrawn projects. -Interconnection costs vary by location. Berkeley Lab publishes a series of short analytical papers of generator interconnection costs to the transmission system for MISO, PJM, SPP, ISO-NE and NYISO, which you can find at https://emp.lbl.gov/interconnection_costs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Interconnection Cost Analysis in ISO-New England

Electric transmission system operators (ISOs, RTOs, or utilities) require new large generators seeking to connect to the grid to undergo a series of impact studies before they can be built. This process establishes what new transmission equipment or upgrades may be needed before a project can connect to the system and assigns the costs of that equipment. Berkeley Lab has collected interconnection cost data for 194 projects in New England from interconnection studies performed between 2010 and 2021. Project-level cost summary data are available for download on this page. We find: -Interconnection costs have grown over time, especially for projects that withdraw. -Interconnection costs are highest for onshore wind, followed by solar and storage. Natural gas and offshore wind projects tend to cost less to interconnect, in comparison. -Economies of scale exist for solar and possibly storage projects, but not for other resource types. -Wind and solar projects requesting capacity network resource interconnection service have higher interconnection costs, despite being evaluated using the same interconnection standard in the analyzed studies. -Low and high interconnection costs can be found throughout the ISO-NE footprint. -Costs are split fairly evenly between investments at the point of interconnection and within the broader network for active and withdrawn projects, while complete projects incur most costs at the point of interconnection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

5G Securely Energized and Resilient: Task 2 and 3 Progress Report

The 5G Securely Energized and Resilient project implemented at the National Renewable Energy Laboratory is sponsored by the Office of the Under Secretary of Defense and is designed to demonstrate the successful deployment of 5G-6G (FutureG) technologies in the context of electrical microgrid scenarios. Through implementation of this project, cybersecurity researchers were able to design a platform to better understand the fundamental system architecture, limitations, and benefits of 5G systems supporting energy system requirements. Although the work for this project was developed in the context of “FutureG Advanced Component Development & Prototypes,” which is a U.S. Department of Defense effort to ensure communications system resilience in the context of military deployments, the results can also apply to communications for electrical grids in general. Several key points were established in Tasks 2 and 3 of this project that are further expanded on in the body of this document.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Speed to Power: Solutions for Accelerating Large Load Connections

Rapid growth in demand from data centers and other large loads is creating a range of new challenges for electricity planners, investors, system operators, and regulators, leading to bottlenecks that have slowed connection of large loads to the electric grid. In response, innovative solutions for accelerating large load connections are beginning to emerge across the U.S. Drawing on an extensive document and literature review, this report identifies more than 40 potential solutions for accelerating large load connections, organized into five functional areas: load forecasting, interconnection, resource planning and procurement, markets and operations, and cost allocation and ratemaking. The five functional areas provide a framework for organizing challenges and solutions to large load connection bottlenecks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Opportunity Assessment for U.S. Industry: Energy-Efficient Cooling Technologies in Mexico

Mexico's rapidly expanding room air conditioner (AC) market presents a strategic opportunity for U.S. manufacturers to strengthen North American supply chains while addressing critical energy infrastructure challenges. With demand for room AC units in residential and commercial buildings projected to drive a 26 GW increase in Mexico’s peak electrical load by 2050, high-efficiency air conditioning systems offer both substantial market opportunities and essential grid stability benefits.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Balancing Authority Data Reformatted

We collect the data from the electricity balancing authorities (BAs) that operate the grid. A balancing authority ensures, in real time, that power system demand and supply are finely balanced. This balance is needed to maintain the safe and reliable operation of the power system.

17 WIND ENERGY↗

An economic assessment of behind-the-meter photovoltaics paired with batteries on the Hawaiian Islands.

Due to natural variability and uncertainty, the ever-increasing penetration of solar generation in Hawaii presents challenges to power grid operators to maintain reliable system operation. Demand response (DR) has the potential to be a cost-effective tool for Hawaii to reach its aggressive renewable energy goals while maintaining the reliability of power grids. The Hawaii Public Utilities Commission has approved the Hawaiian Electric Company's revised portfolio of DR programs. The companies have released a grid services purchase agreement and subscribed an initial tranche of load into their DR programs. This paper presents innovative analytical methods and comprehensive economic assessment for distributed photovoltaics (PV) paired with battery energy storage systems (BESSs) for two new DR programs, including fast frequency response and capacity grid service. Optimal dispatch and sizing methods are proposed for the paired system considering different tariff schedules and PV compensation programs across five islands. It was found that while the best resource configuration and potential economic benefits vary with tariff structure, a BESS paired with PV can be optimally dispatched to generate multiple value streams simultaneously. Compensation from DR programs is an important value stream to help increase the cost-effectiveness of the integrated system.

Battery energy storage system↗

Clean Grid Vision: A U.S. Perspective - Chapter 4. Demand-Side Development

This chapter focuses on recent developments on the demand side of the electricity system in the United States and beyond. After decades of slow-moving change in power system technology, business models, regulatory structures, and even financing schemes, changes on the demand side are accelerating rapidly. These changes are also more tightly linking the supply side with the demand side. This chapter provides high-level summaries of traditional subjects like demand-side management, which includes energy efficiency and demand response, and then transition to a subject that has gathered increasing attention as the most dynamic change likely to impact power systems in the coming decades: beneficial electrification. In each case, we attempt to address the impacts on system flexibility to the degree possible. These demand-side subjects are widely considered essential elements of a clean grid strategy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimizing Power Line Undergrounding Decisions under Varying Wildfire Risk and Weather Scenarios

Abstract—The threat of wildfire ignitions from electric power equipment has led utilities to increasingly turn to preemptive power shutoffs, which, while effective in reducing grid-induced wildfire risk, can cause significant load loss. Undergrounding power lines is an alternative strategy for preventing grid-induced wildfires. However, undergrounding lines is costly, so an efficient undergrounding plan must balance reductions in wildfire risk and load loss with the cost of undergrounding lines. We propose a robust optimization model to identify which power lines to underground to maximize load served while limiting wildfire risk across a range of wildfire risk and weather scenarios. Since solving this problem may be computationally heavy for large power grids and many operating scenarios, we present a delayed constraint generation algorithm to iteratively add scenarios until an optimal solution is found. We evaluate the performance of this framework on the RTS-GMLC with scenarios representing a year of operating conditions and compare it with a stochastic programming formulation. Our results indicate that our undergrounding model is successful in reducing load shed and risk compared to baseline cases in which no mitigation action is taken and only power shutoffs are implemented (no undergrounding). The robust formulation also reduces more load shed than the stochastic formulation in the most extreme scenarios. Index Terms—grid resilience, optimization, transmission systems, underground power lines, wildfire risk.

Taylor, S. [Department of Electrical and Computer ↗

Compact and Low-cost Microinverter for Residential Systems

Concerns regarding climate change from the use of fossil fuels have expedited the growth of renewable energy sources. One such form of renewables, solar energy, is already playing and will continue to play a major role in meeting U.S clean energy targets. Expanding solar power usage in residential networks is a critical step in the decarbonization and clean electricity movement. To achieve a carbon-free grid by promoting solar power to the general public, an aggressive cost reduction in solar power systems is essential. The power density of the equipment used in the solar power system is necessary to solve the challenges of solar power installation. This project aims to research, explore, and assess the possibility of reducing the microinverter cost and volume to achieve the next generation microinverters (NGMs) targets for residential solar photovoltaic applications.

14 SOLAR ENERGY↗

Noise and error analysis and optimization in particle-based kinetic plasma simulations

In this paper we analyze the noise in macro-particle methods used in plasma physics and fluid dynamics, leading to approaches for minimizing the total error, focusing on electrostatic models in one dimension. We begin by describing kernel density estimation for continuous values of the spatial variable x, expressing the kernel in a form in which its shape and width are represented separately. The covariance matrix of the noise in the density is computed, first for uniform true density. The bandwidth of the covariance matrix C(x,y) is related to the width of the kernel. A feature that stands out is the presence of constant negative terms in the elements of the covariance matrix both on and off-diagonal. These negative correlations are related to the fact that the total number of particles is fixed at each time step; they also lead to the property ∫C(x,y)dy = 0. We investigate the effect of these negative correlations on the electric field computed by Gauss's law, finding that the noise in the electric field is related to a process called the Ornstein-Uhlenbeck bridge, leading to a covariance matrix of the electric field with variance significantly reduced relative to that of a Brownian process. For non-constant density, p(x), still with continuous x, we analyze the total error in the density estimation and discuss it in terms of bias-variance optimization (BVO). For some characteristic length l, determined by the density and its second derivative, and kernel width h, having too few particles within h leads to too much variance; for h that is large relative to l, there is too much smoothing of the density. The optimum between these two limits is found by BVO. For kernels of the same width, it is shown that this optimum (minimum) is weakly sensitive to the kernel shape. Next, we repeat the analysis for x discretized on a grid. In this case the charge deposition rule is determined by a particle shape. An important property to be respected in the discrete system is the exact preservation of total charge on the grid; this property is necessary to ensure that the electric field is equal at both ends, consistent with periodic boundary conditions. We find that if the particle shapes satisfy a partition of unity property, the particle charge deposited on the grid is conserved exactly. Further, if the particle shape is expressed as the convolution of a kernel with another kernel that satisfies the partition of unity, then the particle shape obeys the partition of unity. This property holds for kernels of arbitrary width, including widths that are not integer multiples of the grid spacing. Furthermore, we show results relaxing the approximations used to do BVO optimization analytically, by doing numerical computations of the total error as a function of the kernel width, on a grid in x. The comparison between numerical and analytical results shows good agreement over a range of particle shapes. We discuss the practical implications of our results, including the criteria for design and implementation of computationally efficient particle shapes that take advantage of the developed theory.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

Impact of Transportation Electrification on the System's Dynamic Frequency Response

Transportation electrification is an integral component of the energy decarbonization transition. This paper investigates the impact of distributed energy resources (DERs), including distributed photovoltaics (DPV) and electric vehicles (EVs), in the primary frequency response of the power grid. Increasing DER adoption poses challenges to maintaining grid frequency stability. However, DERs' ability to provide fast frequency regulation services-primary frequency response (PFR) and secondary frequency response (SFR)-can be exploited to recover the frequency after an N-1 contingency event in the system. This paper also investigates the importance of a droop control strategy through dynamic models of DPV and EV to provide the primary frequency regulation services following the contingency event. A dynamic EV model, based on the PVD1 model Western Electricity Coordinating Council (WECC) introduced, has been used for the simulation. Further, DERs' primary frequency response is studied for five different cases of DER penetration levels after the system is exposed to the generator trip. Additionally, different frequency regulation capacities of EVs are analyzed. The studies show that an increment in DERs capacity providing effective PFR can improve the system frequency nadir and stabilize the frequency faster after the generation trip contingency.

distributed energy resources↗

Evaluation of IEC 62443 Standard Gaps for Electric Grid Substation Model Use Case

This report presents an evaluation of the IEC 62443 standards in the context of electric grid substations, as part of a collaborative effort among Sandia National Laboratories (SNL), Idaho National Laboratory (INL), and the National Renewable Energy Laboratory (NREL). The primary objective is to assess the applicability of these standards to enhance cybersecurity measures for industrial automation and control systems (IACS) within the energy sector. The evaluation identifies strengths, such as the scalability of security levels and the structured lifecycle guidance provided by IEC 62443. However, it also highlights significant gaps, including limited integration of physical security, insufficient guidance for legacy systems, and challenges in addressing emerging threats like supply chain vulnerabilities. Recommendations for refining the standards are proposed, including the need for tailored guidance for securing legacy systems, integrating physical security with cybersecurity frameworks, and enhancing interoperability across multi-vendor environments. By addressing these gaps, the IEC 62443 standards can be strengthened to ensure comprehensive cybersecurity for electric grid substations, thereby supporting the resilience and reliability of critical energy infrastructure.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Experimental Validation of a Modular All-Electric Power Take-Off Topology for Wave Energy Converter Enabling Marine Renewable Energy Interconnection

Power electronic converters are an enabling technology for the emerging marine energy applications, such as using ocean waves to produce electricity. This paper outlines the power take-off system and its key components used in a wave energy converter offering modularity and scalability to generate power efficiently. The proposed power take-off system was implemented based on a modular multilevel converter and could be deployed to convert any alternating current electrical energy to a different alternating current for interconnection to grid or non-grid applications. Examples of widespread deployment are supplying electricity to coastal communities or producing clean drinking water. The analysis using both the simulation tests and laboratory experiments verified the design objectives and basic functionality of the developed power take-off system. An acceptable response using a field programmable gate array-based controlled laboratory testbench was achieved, complying with guidelines specified in the prevalent industry standards. Seamless operation during steady-state and transients for the studied wave energy converter was achieved as supported by the obtained results. The key findings of this work were experimentally examined under different load conditions, direct current bus voltage fluctuations, and generator speed–torque regulation. The ability of the power take-off system to generate high-power quality of the waveforms, e.g., against adhering to the IEEE 519-2022 standard for total harmonic distortion limits, is also confirmed.

Engineering↗

Grid Value Analysis of Geothermal Systems for End-Use Applications

Fuel based end-uses for residential, commercial, and industrial consumers require a technology change to achieve economy-wide decarbonization. Space heating accounts for 42% of residential and 32% of commercial energy demand, much of which is currently met through carbon emitting fuels. Industrial energy use is heavily fuel based with electricity currently representing 13% of energy demand. Geothermal heat pumps (GHPs) and geothermal direct use can eliminate the need for CO2 emitting and simultaneously allow for more efficient electrification of end uses. Past work has assessed the impact on total energy costs and generation investments but did not identify specific grid services benefited. Energy usage in residential and commercial structures was assessed by leveraging data from ComStock and ResStock models. These models utilize housing attributes, occupancy patterns, weather data, and sophisticated energy simulations to generate hourly load profiles for individual buildings identified by unique IDs associated with their locations. Industrial sector energy use was evaluated using information from the Manufacturing Energy Consumption Survey (MECS) as well as plant utilization data from the US Census to estimate hourly plant operations. The change in end-use demand for electricity, natural gas, and other fuels was calculated for different technologies that could meet this need. Using the ReEDS capacity expansion model, we produce regional price profiles that capture the grid benefit associated with the amount and timing of energy shifts in the power system from the adoption of geothermal systems relative to other technologies that could meet space heating, space cooling, and process heat requirements. We find that geothermal systems for meeting end-use demand add value to the energy system. In buildings where geothermal systems increase grid costs, these values are offset by reduced fuel costs and benefits to externalities, including emissions and health impacts.

decarbonization↗

A Novel Framework to Evaluate the Costs and Potential of Bioenergy in Decarbonization of the U.S. Economy

The long-term strategy of the United States targets reaching economy-wide net-zero emissions by 2050 and a carbon-neutral electricity grid by 2035 (U.S. Department of State and U.S. Executive Office of the President, 2021). Meeting these targets would require considerable changes to the energy system. Some key characteristics of illustrative net-zero energy systems include increased penetration of renewable energy and carbon sources, use of CO2 capture and storage (CCS) in hard-to-abate sectors, and a greater role for energy carriers such as electricity and hydrogen (Davis et al, 2018). Another common feature of such energy systems is the need for carbon dioxide removal (CDR) approaches (Horowitz et al, 2022). Across all these characteristics of net-zero energy systems, bioenergy and biomass feedstock is anticipated to play an important role. Biomass feedstock serves as a renewable carbon source. This can enable conversion of such feedstock into fuels and energy carriers for hard-to-abate sectors such as aviation. Indeed, the U.S. Government has a target to meet all jet fuel demand by 2050 from sustainable aviation fuel (SAF), where biofuel pathways are likely to have an important role (EERE, 2020). Bioenergy is also highly versatile with the possibility to convert feedstock into electricity, hydrogen, liquid fuels, heat or high-value products, based on biomass type, demand and technology availability (Clarke et al, 2022). Combination of bioenergy with CCS can also nominally deliver CDR (Fuhrman et al, 2023). As such, the share of bioenergy is expected to grow by at least five time across scenarios studied for the long-term strategy of the U.S. between 2020 and 2050 (Horowitz et al, 2022). Notwithstanding the role of bioenergy in the energy systems, its deployment, costs and scalability are influenced by a number of factors. Some of these factors pertain to policy interventions such as imposition of a binding decarbonization target either at an economy-wide level or the sectoral level. Resource availability and type of biomass feedstock also varies considerably across regions. From a technological perspective, the readiness of bioenergy conversion pathways is subject to high variability. This influences the costs of deployment. Moreover, the sourcing of feedstock, grid carbon intensity, and co-product handling approaches all affect the life cycle efficacy of bioenergy. The latter, in turn, is particularly important in determining the extent to which bioenergy with CCS or BECCS can effectively deliver CDR (Fajardy and Mac Dowell, 2017).

air emission↗

A review of energy storage for power system resilience: Functions, metrics, and applications

Aging infrastructure, increasing operational complexity, and surging electricity demand from artificial intelligence and electrification are straining the grid and heightening the risks of disruptions, making resilience a critical priority. Energy storage is increasingly deployed to provide critical power supply, fast grid support, and rapid restoration. However, current practice lacks consistent metrics and systematic methodologies to rigorously quantify the resilience benefits of storage. This paper provides a comprehensive review of energy storage in resilience enhancement, focusing on functional roles, quantification metrics, and integration strategies. A structured resilience metrics library is compiled and categorized to encompass both technical and economic performance aspects. Existing methodologies for resilience-oriented storage planning and operations are critically examined. Key technical and practical challenges are identified, and future research directions are outlined to strengthen storage contributions to grid resilience.