Non-local model for surface tension in fluid-fluid simulations

We propose a non-local model for surface tension obtained in the form of an integral of a molecular-force-like function with support 3.5e added to the Navier-Stokes momentum conservation equation. We demonstrate analytically and numerically that with the non-local model interfaces with a radius of curvature larger than the support length behave macroscopically and microscopically, otherwise. For static droplets, the pressure difference Pe,in - Pe,out satisfies the Young-Laplace law for droplet radius greater than 3.5e and other- wise deviates from the Young-Laplace law. The latter indicates that the surface tension in the proposed model decreases with decreasing radius of curvature, which agrees with molecular dynamics and experimental studies of nanodroplets. Using the non-local model we perform numerical simulations of droplets under dynamic conditions, including a rising droplet, a droplet in shear flow, and two colliding droplets in shear flow, and compare results with a standard Navier-Stokes model subject to the Young-Laplace boundary condition at the fluid-fluid interface implemented via the Conservative Level Set (CLS) method. We find good agreement with existing numerical methods and analytical results for a rising macroscopic droplet and a droplet in a shear flow. For colliding droplets in shear flow, the non- local model converges (with respect to the grid size) to the correct behavior, including sliding, coalescence, and merging and breaking of two droplets depending on the capillary number. In contrast, we find that the results of the CLS model are highly grid-size dependent.

Howard, Amanda A.↗

Transient Modelling of HTGR Thermal Load Follow in Modelica

The ability of nuclear power plants to load follow electrical power demand is particularly important as we move to higher variable renewable (VRE) energy production on low carbon energy grids. High temperature gas reactors (HTGRs) are capable of load following by adjusting thermal output, but their high temperatures and thermal inertia significantly impact the power transients they are able to follow. To aid investigation into new integrated energy systems with advanced reactors, it is necessary to have an open-source transient model of a full HTGR primary and secondary. This paper introduces two new open-source models for a HTGR and corresponding balance of plant (BOP) written for the HYBRID library developed at Idaho National Laboratory. A transient thermal load follow test case was taken by the work from Brits et al. to benchmark our open-source model against transient operation results from other proprietary codes that exist. The control scheme for the two new models in combination is discussed and a comparison of the response in transient load follow between the two codes performed.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

A regional nuclear conflict would compromise global food security

A limited nuclear war between India and Pakistan could ignite fires large enough to emit more than 5 Tg of soot into the stratosphere. Climate model simulations have shown severe resulting climate perturbations with declines in global mean temperature by 1.8 °C and precipitation by 8%, for at least 5 y. Here we evaluate impacts for the global food system. Six harmonized state-of-the-art crop models show that global caloric production from maize, wheat, rice, and soybean falls by 13 (±1)%, 11 (±8)%, 3 (±5)%, and 17 (±2)% over 5 y. Total single-year losses of 12 (±4)% quadruple the largest observed historical anomaly and exceed impacts caused by historic droughts and volcanic eruptions. Colder temperatures drive losses more than changes in precipitation and solar radiation, leading to strongest impacts in temperate regions poleward of 30°N, including the United States, Europe, and China for 10 to 15 y. Integrated food trade network analyses show that domestic reserves and global trade can largely buffer the production anomaly in the first year. Persistent multiyear losses, however, would constrain domestic food availability and propagate to the Global South, especially to food-insecure countries. By year 5, maize and wheat availability would decrease by 13% globally and by more than 20% in 71 countries with a cumulative population of 1.3 billion people. In view of increasing instability in South Asia, this study shows that a regional conflict using <1% of the worldwide nuclear arsenal could have adverse consequences for global food security unmatched in modern history.

54 ENVIRONMENTAL SCIENCES↗

Self-Organizing Map-Based Resilience Quantification and Resilient Control of Distribution Systems Under Extreme Events

Due to climate change, extreme weather events are occurring more frequently and with increasing impact. This trend poses a significant challenge for distribution system operators (DSO) to ensure that there is uninterrupted power supply to critical loads in their networks. To embed resilience into DSO's decision-making, resilience needs to be first quantified and then integrated into the system-level optimization. Therefore, this paper first develops a novel self-organizing map (SOM) based method (called SomRes) to quantify the time-varying resilience index of a system that can leverage the powerful classification property of SOMs and removes some of the disadvantages of subjective weight assignment methods. Using SomRes, a resilient resource allocation and operational dispatch algorithm is further developed to enhance system resilience against extreme events by considering the SomRes resilience index directly as the feedback. Here, the proposed resilience quantification approach is benchmarked with a state-of-the-art approach and the efficacy of the proposed resilient dispatch algorithm is demonstrated through several deterministic and statistical case studies on the IEEE 123-bus distribution system. Simulation studies show that the proposed SomRes quantification method is an appropriate indicator of system resilience, and the resilient resource allocation and dispatch strategy can significantly reduce critical load shedding under varying event propagation scenarios.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Direct Air Capture of CO 2 and Delivery to Photobioreactors for Algal Biofuel Production (Final Report)

A mobile DAC system was designed and constructed to pair with photobioreactors growing algae for biofuel production. The DAC system was designed as a versatile research system, rather than a compact production unit. The system was constructed and mounted on a mobile skid to facilitate transportation to the algae production site. Within the DAC system, CO 2 was captured using amine-loaded monoliths that allow for high CO 2 uptake with low pressure drop. The CO 2 is collected using a Global Thermostat patented temperature/vacuum swing adsorption (TVSA) process. Amine sorbents and process conditions were optimized to produce 10 to >20 g CO 2 .h-1. The stability of the amine sorbents was also studied, with sorbent modifications made to improve stability to degradation by oxidation. An Algenol-developed Spirulina strain (Arthrospira platensis AB2293) was selected as the production cyanobacterial strain. AB2293 cultured was inoculum for outdoor production following PBR installation by Algenol. The PBR system was composed of three independent PBRs, with each PBR composed of four hanging bags internally recirculated by a liquid turnover pump. The PBRs were operated outdoors in Atlanta, GA, and integrated with the DAC system. Algae were grown with similar productivity using DAC-CO 2 as algae grown using pure CO 2 obtained commercially (Airgas). Throughout the experimental duration, no discoloration was observed, and cellular morphology was consistent between the two experimental treatments. An LCA including lifecycle greenhouse gas emissions, full life cycle inventory of the Algenol system and the DAC system and integrated DAC+PBR system was developed. Lifecycle greenhouse gas emissions were calculated for capture of carbon dioxide using input from Global Thermostat and the National Renewable Energy Laboratory. Three scenarios for energy provision were evaluated: a natural gas combined heat and power system sized to meet the electricity requirement, a natural gas combined heat and power system sized to meet the process heat requirements, and a system without on-site power that procures the electricity from the grid. In all three cases, as expected, the major contributor to the emissions is the energy consumption associated with the desorption step of the DAC process. The LCA quantified the reduced potential energy and greenhouse gas emissions of heat and mass integration of DAC and Algenol compared to unintegrated DAC and Algenol systems. A life cycle assessment of the role of sorbent productivity and lifetime was also developed. The development of more robust, oxidation resistant DAC sorbents may enable small reductions in energy requirements and in lifecycle greenhouse gas emissions and other environmental impacts. NREL performed techno-economic analysis (TEA) to identify the integration scenario most likely to achieve a 15% cost reduction target versus the baseline. Heat and mass integration of DAC and the PBR is critical to minimizing the MFSP. The baseline case utilizes no heat and mass integration, and the DAC system provides 100% of the CO 2 required by the photobioreactors (20 tonnes/hr), operating for 12 hours/day capturing 40 tonnes CO 2 /operating hour. The minimum fuel selling price (MFSP) of ethanol calculated from the baseline case was $10.68/gal ethanol. This corresponds with a targeted MFSP of $9.07/gal ethanol (or 15% reduction). This target was achieved by integration Option 2a with the greatest cost reduction of 17.8% (or $8.78/gal) and integration Option 2b with a cost reduction of 16.4% (or $8.93/gal). Reductions in MFSP are attributed to two primary process considerations: (a) CO 2 storage at night reduces the capital expenses associated with DAC (i.e., increasing on-stream time); and (b) distributed DAC scenarios (DAC-PBR integration Options 2a and 2b) make use of boiler and DAC CHP flue gas CO 2 (free). Direct air capture on-stream time was one of the largest contributors to MFSP reduction.

09 BIOMASS FUELS↗

Using Energy Storage-Based Grid Forming Inverters for Operational Reserve in Hybrid Diesel Microgrids

In remote arctic communities, where access to a bulk electrical grid interconnection is not available, the implementation of islanded microgrids has been the most viable way to produce and distribute electricity services to their inhabitants. Historically, these islanded grids have relied primarily on diesel generators or hydropower resources to supply the baseload. However, this practice can result in increased expense due to the high costs associated with fuel transportation and the significant amounts of on-site storage necessary when fuel transportation is unavailable during winter months. In order to mitigate this problem, arctic microgrids have started to transition to a hybrid-source operational mode by incorporating renewable energy sources that are inherently variable in nature, such as wind or solar. Due to their highly stochastic behavior, these hybrid-source islanded microgrids can pose potential issues related to power quality due to introduction of rapid net load fluctuations and inability of diesel generators to respond rapidly. In addition, non-firm stochastic sources can require significant idling diesel generator resources to serve as spinning reserves, which is inefficient and wasteful. This work studies the problems that may arise in the transient dynamics of a real-world hybrid diesel microgrid when subjected to a loss of wind generation. Moreover, this work proposes a transition from a diesel spinning reserve to a battery energy-storage system (BESS) operating reserve scheme. The study of the proposed transition is important in establishing the fundamental implication of transient dynamics and the potential benefits of integrating a BESS as a spinning reserve in terms of stability, frequency nadir, and transient voltage deviation. The methods to investigate and validate the transient dynamics relied on both electromagnetic simulation models of GFMIs and a commercially available GFMI in an experimental power hardware-in-the-loop setup. The simulation results showed that the proposed operating reserve scheme improves the power quality of the system in terms of voltage deviation and frequency nadir when the microgrid is subjected to a loss of wind generation scenario. Depending on the simulation cases, adding a GFMI reduced the frequency nadir between 65.3% and 86.7%. Moreover, the reductions in the voltage deviations improved between 3.6% and 23.0%. From these results it can be concluded that the integration of a GFMI can reduce the frequency nadir in a hybrid diesel microgrid, and in turn, reduce diesel consumption, which improves system reliability while reducing fuel expenses. Furthermore, the novelty of this work relies on the fact that the offline simulation results were validated using a power hardware-in-the-loop platform that incorporated a 100 kVA commercially available GFMI as the device under test.

Hernandez-Alvidrez, Javier↗

Parametric study of solid-solid translucent phase change materials in building windows

Thermal energy storage and solar radiation management are crucial to improve the sustainability and energy efficiency of buildings. Compared with the implementation of phase change materials (PCMs) in opaque components, the energy saving potential of incorporating PCMs in transparent glazing windows is much less studied and not well understood. Here we present a comprehensive parametric study of novel PCM windows for building energy saving with a focus on optimizing and quantitatively distinguishing the contributions from the optical and thermal properties of the PCM, which is particularly useful for the design of solid-solid PCM windows. We investigate a reference commercial office building using EnergyPlus by developing an equivalent model of our PCM window that is compatible with EnergyPlus's modeling capabilities. Compared with a clear-clear double-pane window, the integration of 3 mm solid-solid PCMs with optimal properties in warm, mixed, and cold climates can respectively save up to 17.2%, 14.0%, and 5.8% energy for the HVAC (heating, ventilation, and air conditioning) system, and 9.4%, 6.7%, and 3.2% energy for the whole building. We also demonstrate that these energy savings are most sensitive to the solar absorptance of PCMs for all three climates. The optimal transition temperature varies with climate and is related to the climate and solar radiation heat gain. Other issues are also briefly discussed, such as hysteresis, window orientations, and the effect of interior lighting. Finally, although the optimal PCM windows show energy saving performance comparable with low-emissivity windows, the PCM windows provide a unique advantage in terms of shifting HVAC loads which can provide benefits to the electrical grid.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

An open control sequence specification to scale building demand flexibility via analytics software

For over two decades, researchers and practitioners have showcased the ability of large commercial buildings to provide grid services by shedding or shifting load. Various utility demand response (DR) and virtual power plant (VPP) programs throughout the United States are presently utilizing these demand-side resources. However, growth of these programs have been limited, in part due to the high cost necessary to integrate the DR control strategies into the building automation system (BAS). Implementing these strategies involves adjusting control sequences, necessitating dozens of hours of customized programming per building, limiting their adoption to large organizations and progressive owners. Recent efforts by researchers and industry have demonstrated the capability of energy management and information systems (EMIS), originally designed for fault detection and diagnostics, to interface with existing BAS and perform supervisory control to optimize building operations. While these approaches are quickly being adopted by industry, demand flexibility (DF) control strategies remain limited in product offerings. One of the challenges is the lack of documented best-practice DF sequences, despite the rich literature on field implementations. This paper develops a new open-specification for a zone-based temperature adjustment shed strategy for commercial building HVAC systems, describing the specification’s implementation in two EMIS tools in both experimental and field settings. Both implementations successfully reduced electric load by at least 40% on average during the called event, while maintaining temperature limits. This study’s detailed process from specification to deployment shows the potential for scalability as well as highlights challenges related to integration with heterogeneous BAS products.

Granderson, Jessica↗

Exploring Multidimensional Spatial-Temporal Hydropower Operational Flexibilities by Modeling and Optimizing Water-Constrained Cascading Hydroelectric Systems

Because of unique characteristics such as clean and cost-competitive electricity as well as fast-ramping and storage abilities, the power industry continues to evolve its operation strategies for cascading hydroelectric (CHE) systems for providing enhanced values to the grid, especially under the deeper renewable resource integration. However, existing operation practices of CHEs predate the integration of renewables, which could prohibit the effective utilization of their inherent flexibilities in delivering maximum financial benefits and providing valuable grid services to the power system and electricity market operations. Indeed, modeling and optimizing these resource-limited while flexible CHE assets with uncertainties and imperfect information across multiple spatial-temporal dimensions present significant challenges. To facilitate CHE facility operators in effectively coordinating water usage and hydropower plant operations across multiple timescales, this project aims to fill the existing gaps by developing a suite of accurate water inflow (WI) forecast models as well as enhanced CHE modeling and optimization approaches with proper consideration of their unique characteristics, which would help explore their multidimensional spatial-temporal operational flexibility potentials. The developed approaches could better align reservoir operation strategies with variability and uncertainty of future water availability. They can also promote more effective utilization of multidimensional spatial-temporal hydropower operational flexibility potentials by designing long-term evacuation plans of reservoirs and short-term operation of CHEs, along with their coordination with other types of renewables. The project leverages various resources to facilitate the research and development activities, including actual characteristics data of CHE systems and a library of current and future cases of Portland General Electric (PGE). These realistic data enable the project team to study how to maximize the value of CHEs under current and future portfolios and evaluate opportunities to improve operation practices.

13 HYDRO ENERGY↗

Electrification Futures Study: Power Systems Operation with Newly Electrified and Flexible Loads

The Electrification Futures Study (EFS) is a multi-year study designed to analyze the impacts of widespread electrification in the U.S. energy system. In this webinar we present the detailed power systems operational analysis from the final report in the EFS series. For this analysis, we simulate multiple 2050 power systems for the conterminous United States to assess how variations in the magnitude and shape of electricity demand driven by electrification, and the extent of load participation to more-actively provide grid services, might impact the hourly operation, operational costs, and emissions of various power systems in 2050. The impacts of electrification and demand flexibility are overlayed across systems with significantly greater penetrations of variable renewable energy than today. Overall, we find that the high electrification scenarios envisioned in the EFS with significant VRE penetration (66% of annual national generation) can be operated to meet future increased levels of electrified demand. We also find that demand-side flexibility can enhance operational efficiency and reduce overall annual production costs by $5-$10 billion. The complementary relationship between flexible electric vehicle charging loads and solar generation is particularly pronounced, but in the absence of demand-side flexibility electrification can lead to increased wind and solar curtailment. By helping to reduce renewable curtailment, flexibility can also reduce power sector CO2 emissions. The analysis highlights the value of increased integration and coordination of demand- and supply-side resources in future electric system planning and operations—particularly under high electrification futures.

43 PARTICLE ACCELERATORS↗

Techno-Economic Analysis and Optimization of a Compressed-Air Energy Storage System Integrated with a Natural Gas Combined-Cycle Plant

To address the rising electricity demand and greenhouse gas concentration in the environment, considerable effort is being carried out across the globe on installing and operating renewable energy sources. However, the renewable energy production is affected by diurnal and seasonal variability. To ensure that the electric grid remains reliable and resilient even for the high penetration of renewables into the grid, various types of energy storage systems are being investigated. In this paper, a compressed-air energy storage (CAES) system integrated with a natural gas combined-cycle (NGCC) power plant is investigated where air is extracted from the gas turbine compressor or injected back into the gas turbine combustor when it is optimal to do so. First-principles dynamic models of the NGCC plant and CAES are developed along with the development of an economic model. The dynamic optimization of the integrated system is undertaken in the Python/Pyomo platform for maximizing the net present value (NPV). NPV optimization is undertaken for 14 regions/cases considering year-long locational marginal price (LMP) data with a 1 h interval. Design variables such as the storage capacity and storage pressure, as well as the operating variables such as the power plant load, air injection rate, and air extraction rate, are optimized. Results show that the integrated CAES system has a higher NPV than the NGCC-only system for all 14 regions, thus indicating the potential deployment of the integrated system under the assumption of the availability of caverns in close proximity to the NGCC plant. The levelized cost of storage is found to be in the range of 136–145 $/MWh. Roundtrip efficiency is found to be between 74.6–82.5%. A sensitivity study with respect to LMP shows that the LMP profile has a significant impact on the extent of air injection/extraction while capital expenditure reduction has a negligible effect.

25 ENERGY STORAGE↗

Achieving a Net-Zero Future: The Role of Nuclear Energy

Governments and private industry around the world have established aggressive goals to achieve net-zero emissions for the power, industrial, and transportation sectors by 2050. These aggressive goals demand immediate action if we are to be successful, and they require us to think more holistically about our clean energy options. Programs within the U.S. Department of Energy (DOE) are addressing these holistic solutions. Traditionally, electricity generation and management are considered independently from meeting energy demands for industry and transportation. As we seek to eliminate emissions across all energy use sectors we need to reassess how energy demands are met. When we consider overall energy use, only one-third is in the form of electricity. Additional energy demands are in the form of heat or steam for industrial processes, in addition to direct fuel use for transportation. These sectors are much harder to abate, and electrification may not be the best option. Reducing environmental emissions at an affordable cost, while maintaining grid reliability and resilience, will require us to leverage all of the clean energy resources available. The DOE Office of Nuclear Energy (DOE-NE) program on Integrated Energy Systems (IES) is led by researchers at Idaho National Laboratory (INL), and work is conducted in partnership with an array of other DOE laboratories, industry, and academia. The primary focus of IES research is to assess the technical and economic potential of nuclear-driven IES to enhance the flexibility and utilization of nuclear reactors working alongside renewable generators to meet an array of energy demands—thereby maximizing the utilization of clean energy resources across all energy sectors. Various energy applications and product streams beyond electricity are being evaluated, ranging from generation of potable water to production of hydrogen, fertilizers, synthetic fuels, and various chemicals. The DOE-NE program additionally partners with the Hydrogen and Fuel Cell Technologies Office under the DOE Office of Energy Efficiency and Renewable Energy to jointly fund the development of analysis tools, technologies, and nuclear-integrated hydrogen demonstration projects. This presentation will highlight the wide array of R&D being conducted across multiple DOE-funded programs to develop and deploy nuclear-based IES that will be key to achieving our net-zero goals. By working with key collaborators in the nuclear industry, analytical studies are now becoming a reality in demonstration projects.

08 HYDROGEN↗

Fitness-for-Service Analysis of Reactor Components under Flexible Load-Following Operating Conditions

Conventional power-generation plants, including nuclear plants, have been traditionally designed to provide a steady baseload energy capacity, optimizing output efficiency while minimizing variable costs. However, the growing adoption of large-scale renewable energy-generation systems, which rely on intermittent sources such as solar and wind, has introduced more variability into the energy supply in interconnected electricity grids. As a result, the next generation of power plants needs to operate in what is known as the load-following mode, requiring flexible adjustments in electricity production to align with the energy demand on the grid. This transition from the steady baseload operation to load-following operating conditions can significantly increase the number of times various plant components are exposed to transient stresses. This increased thermo-mechanical cycling can lead to accelerated material degradation, thereby elevating the risk of premature failure of a component. It becomes imperative to conduct a comprehensive analysis of fatigue, creep-fatigue, and stress corrosion cracking life, to assess the resilience of the various engineering components under these flexible load-following operating conditions. This study aims to develop a comprehensive numerical model of a light-water reactor pressure vessel (RPV) to investigate its degradation under various operating scenarios. This coupled thermo-mechanical finite element analysis evaluated the stress response of the RPV caused by considering fluctuations in thermal and mechanical loads caused by the varying pressure and temperature occurring during the load-following operation. Critical locations on the RPV are subsequently identified based on the stress response. The stress intensity factors for the postulated flaws at those locations are then calculated, followed by an evaluation of the reactor's life in accordance with the ASME Boiler and Pressure Vessel Code Section XI. This comprehensive life assessment covers a number of transients expected during the flexible load-following operation, providing invaluable insights into the RPV's structural integrity. Moreover, the development methodology can be adapted to other reactor components, as well as components of conventional power stations that are affected by varying operating conditions.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

A Study of Emerging Ancillary Service Markets in Non-Restricted Regions of the Western Power Grid (CRADA Final Report)

Rising penetrations of renewable energy generation in the Western United States pose new requirements for ancillary services, which are the services required, in addition to energy service, in order to maintain the system reliability. This project combines the research capabilities of the National Renewable Energy Laboratory (NREL) and the University of Colorado at Boulder (CU-Boulder) to provide more accurate information to market participants and regulators about the present and future size and composition of ancillary service markets in the non-restructured regions of the West. This information would provide market participants and state and federal regulators with a more transparent view of future ancillary service markets, and allow for more efficient system planning in both the private and public sectors of the electricity market.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Hydrogen Based Energy Storage System for Integration with Dispatchable Power Generator (Phase I Feasibility Study)

This project examined the feasibility of integrating hydrogen generation, storage, and use as a means to decarbonize campus activities while retaining the ability to utilize the existing natural gas fired combined heat and power system installed at the campus of the University of California @ Irvine. Analysis of specific potential sites for the integrated system identified a location adjacent to the existing central plant which resulted in minimization of interconnections. A strategy based on use of commercial electrolyzers and gas storage was identified. Primary technology advancements are required for the gas turbine to accommodate higher levels of hydrogen and the integrated controls. The project indicated challenges for adopting the proposed strategy with the present rates and constraints. The availability of a relatively low-cost biogas resource by the campus already decarbonizes the gas turbine to some extent. In the absence of this resource, procurement of electricity directly from large scale renewable operations could facilitate lower electricity costs. Additional solar resources on campus could also help in this regard. The gas turbine cannot be operated below 50% capacity due to air permit constraints. Using the otherwise curtailed gas turbine operation to generate hydrogen via electrolysis by consuming natural gas is not highly efficient and therefore leads to relatively high costs of electricity returned. Several scenarios demonstrate potential for effective decarbonization, yet most involve lower and lower capacity factor for the legacy gas turbine which is not a good use of the asset. A small gas turbine output with higher efficiency operation would help. As would ability to export electricity to the grid. Certainly current rate structures and operational scenarios are less attractive than other possible future structures which should be pushed for in the future.

03 NATURAL GAS↗

Internal Model-Based Active Damping Strategy for a Back-to-Back Modular Multilevel Converter System for Advanced Grid Support: Preprint

The proposed work focuses on the possibility of achieving the reduction in the size of the interfacing filter for the grid connection for a back-to-back modular multilevel converter system with the use of third order LCL filters. To achieve the same attenuation, it is possible to reduce the size of the interfacing filters by the usage of third order filters. However, this kind of filtering comes with the limitation of having sustained oscillations due to lack of damping especially during transient changes. Therefore, in this work, a methodology has been proposed based on the principle of internal model to cater for this unwanted oscillations. The third order system is modeled inside the microcontroller with the damping enabled. The error between the output from the model and the actual are compared and the error is utilized to accomplish the active damping strategy. The proposed architecture is verified via computer simulations based on MATLAB/Simulink domain and various case study results along with their discussion is presented in this paper.

dq control↗

Study of Storage Requirements and Costs for Shaping Renewables and Nuclear Energy (FY23 Summary Report)

To decarbonize electricity generation primarily by using wind and solar resources, it is likely that additional low (or zero) carbon dioxide (CO 2 ) alternatives will be required for ensuring a reliable electricity supply. This study extends the work and modeling framework that we consolidated in FY 2022, by assessing the zero-CO 2 pathways of a Texas power system in which the availability of variable renewable energy (VRE), nuclear energy, and energy storage types (i.e., battery and thermal energy storage [TES]) are considered the sole resources available for expansion. Using the Risk Analysis Virtual Environment (RAVEN) and Holistic Energy Resource Optimization Network (HERON) frameworks, this study investigates the market of two nuclear energy technologies (i.e., large light-water reactors [LWRs] and LWR-type small modular reactors [SMRs]) under two plausible storage coupling scenarios (i.e., electric coupling and direct thermal coupling). We also explore optimal environments for nuclear energy deployment, and identify key performance characteristics that make nuclear energy economically viable in areas with significant intermittent energy sources. Our analysis encompasses 24 cases. We model the least-cost grid systems, highlight the potential for a coupled LWR-TES approach, and utilize SMRs to achieve deep decarbonization in an affordable, technically feasible manner. We also examine seasonal variations in balancing electricity supply and demand, and account for varying performance, costs, and grid constraints. Overall, the findings of our modeling afford valuable insights for supporting future technology investment decisions in the energy sector.

25 ENERGY STORAGE↗

DSO+T: Integrated System Simulation (DSO+T Study: Volume 2)

This report summarizes an integrated co-simulation model used by the Distribution System Operator with Transactive (DSO+T) study to represent an electrical generation, delivery, and end-load systems for the purposes of assessing the viability and value proposition of transactive energy coordination of flexible assets versus a business-as-usual case. The integrated co-simulation model includes the bulk generation and transmission system, including the day-ahead and real-time scheduling and dispatch of thermal generators. Forty distribution system operators were modelled in detail, including tens of thousands of residential and commercial buildings and their flexible end-loads. These included HVAC systems, residential water heaters, electric vehicles, and stationary, behind-the-meter, batteries. Both wholesale market and end-load results for the business-as-usual case are presented and compared to actual ERCOT system data to assess the accuracy and representativeness of the resulting model.

24 POWER TRANSMISSION AND DISTRIBUTION↗