At least 775 records · Page 43

Alkaline Zinc Passivation Mechanism is Controlled by Hydroxide Concentration

We studied Zn passivation and oxide growth in Zincate (Zn(OH) 4 2− ) in 4 and 8 M KOH solutions using an electrochemical quartz crystal microbalance (EQCM), building on our initial work at 1 M KOH where passivation was kinetically controlled. A porous passivating oxide spontaneously forms on Zn electrodes when KOH is above 4 M and saturated with zincate. However, passivation does not occur when bulk zincate concentration is decreased, resulting in continual Zn dissolution. EQCM data suggests that the passivation mechanism is strongly affected by pOH. Mass transport and kinetic processes in the 4 M KOH electrolytes couple and govern Zn passivation. At 8 M, KOH concentration shifts passivation to mass transport control. We explain this by the increased solubility of Zn(OH) 3 − with increasing pOH. The variation in the mechanism of passivation implications for how passivation is handled in Zn-alkaline batteries. The importance of controlling the mass transport increases with increased pOH, suggesting that electrode design, additives, and potential flow should be optimized. At lower pOHs, kinetics and mass transport must be balanced to manage passivation effectively. Additionally, the changing nature of the native oxide layer on the surface has implications for the evenness of deposition and dissolution on the Zn electrode.

Wittman, Reed M. [Oak Ridge National Laboratory (O↗

PANDEMIC: Occupancy driven predictive ventilation control to minimize energy consumption and infection risk

During the SARS-CoV-2 (COVID-19) pandemic, governments around the world have formulated policies requiring ventilation systems to operate at a higher outdoor fresh air flow rate for a sufficient time, which has led to a sharp increase in building energy consumption. Therefore, it is necessary to identify an energy-efficient ventilation strategy to reduce the risk of infection. In this study, we developed an occupant-number-based model predictive control (OBMPC) algorithm for building ventilation systems. First, we collected the occupancy and Heating, ventilation, and air conditioning system (HVAC) data from March to July 2021. Then, four different models (Auto regression moving average-based multilayer perceptron (ARMA_MLP), Recurrent neural networks (RNN), Long short-term memory networks (LSTM), and Nonhomogeneous Markov with change points detection (NH_Markov)) were used to predict the number of room occupants from 15 min to 24 h ahead with an interval output. We found that each model could predict the number of occupants with 85% accuracy using a one-person offset. Furthermore, the accuracy of 15 min of the ahead prediction could reach 95% with a one-person offset, but none of them could track abrupt changes. The occupancy prediction results were used to calculate the ventilation demand using the Wells-Riley equation, and the upper bound can maintain an infection risk lower than 2% for 93% of the day. This OBMPC model could reduce the coil load by 52.44% and shift the peak load by 3 h up to 5 kW compared with 24 × 7 h full outdoor air (OA) system when people wear masks in the space. The occupancy prediction uncertainty could cause a 9% to 26% difference in demand ventilation, a 0.3°C to 2.4°C difference in zone temperature, a 28.5% to 44.5% difference in outdoor airflow rate, and a 10.7% to 28.2% difference in coil load.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Impact of Control on Availability and Cycling of Residential HVAC in a Real-World Experiment

Demand response is an important emerging part of smart grids and there is a large stream of research from theoretical and modeling perspectives. However, there is relatively little experimental evidence that could help researchers and building operators make informed decisions on best practices for modeling, developing, and deployment of control mechanisms. We contribute to the body of experimental research by providing numerical insights into the role and availability of residential HVAC systems for control. We share the findings on the duration of the cooling cycle, off cycle, and temperature settling time of HVAC systems from data collected from a smart neighborhood located in Atlanta, GA.

cycling↗

Connected Loads – Grid Connected Appliances: Deployment IoT Solution for Fault Detection and Diagnostics

As one of the most energy-intensive end-uses in the commercial buildings sector, supermarkets consume around 50 kWh/ft 2 ( or 537.6 kWh/m 2 ) of electricity annually, or more than 2 million kWh of electricity per year for a typical store. The biggest consumer of energy in a supermarket is its refrigeration system, which accounts for 40–60% of its total electricity usage and is equivalent to about 2–3% of the total energy consumed by commercial buildings in United States, or around 0.5 quadrillion Btu (or 0.53 quadrillion KJ). Also, the supermarket refrigeration system is one of the biggest consumers of refrigerants. Current supermarket refrigeration systems rely on high global warming potential hydrofluorocarbon refrigerants. Reducing refrigerant usage or using environment friendly alternatives can result in significant climate benefits. Transcritical CO2 refrigeration systems have attracted more attention in recent years because of their zero-carbon emission advantages compared with traditional refrigerants. These systems are widely used in commercial buildings such as supermarkets. The refrigeration system can also be adapted to handle flexible building loads and be integrated into grid response transactive control to balance the supply and demand of the electric grid. Even minor improvements in the efficiency and operational reliability of supermarket refrigeration systems can create significant value in terms of saving energy, improving food quality, protecting the environment, reducing carbon footprint, and enhancing electric grid resilience. For decarbonization, the new administration has set a target to reduce greenhouse gas emissions by 50– 52% by 2030 and targeting a carbon-neutral economy by 2050. For electrification, the goal is to achieve 100% clean electricity by 2035. Such decarbonization and electrification in the building sector require that energy consumption in buildings be reduced significantly. Therefore, the building sector must continuously adopt new technologies to achieve its energy and carbon emission goals. One of the most fundamental technologies is the Internet of Things (IoT). IoT has proven to be an effective solution for the building domain, including building information/energy modeling, smart buildings, etc. Although much progress has been made in the development of IoT-based building energy systems, there is still a lack of reliable, scalable, and affordable IoT-based automated fault and degradation diagnostics (AFDDs) solutions. Such solutions would enable deployment of advanced algorithms into real systems to archive the projected energy benefits. This study reviews existing IoT solutions developed for building energy– related application and developed a simple but effective AFDD IoT deployment solution, including developing a suitable IoT architecture and conducting easy and scalable deployment by leveraging a common cloud-based IoT service.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Shape Control of Colloidal Semiconductor Nanocrystals through Thermodynamically Driven Aggregative Growth

The optoelectronic properties of colloidal semiconductor nanocrystals (NCs) can be manipulated by changing their geometric shapes. The precise synthetic control over particle morphologies, however, has remained elusive. Conventional growth techniques rely on the kinetic assembly of atomic units, where supersaturation and precipitation processes can lead to a broad distribution of particle shapes. In this paper, we demonstrate that replacing atomic precursors with small-size nanocrystals as building blocks for larger colloids offers an easier, more predictive control over nanoparticle shape evolution. The reported growth strategy is illustrated via shape-selective syntheses of CdSe and CdS NC cubes, spheres, rods, as well as unprecedented “donut” and ring-like structures. Growth of desired particle morphologies was achieved by choosing an appropriate reaction solvent that minimizes the surface free energy through a unique shape formation. This so-called "aggregative growth mechanism" is explained using a thermodynamic model for interacting viscous colloids. We expect that this novel growth strategy will offer a viable platform for shape–selective synthesis of many inorganic colloids, providing pathways to optimizable optoelectronic materials.

36 MATERIALS SCIENCE↗

Optimal Renewable Resource Allocation and Load Scheduling of Resilient Communities

This paper presents a methodology for enhancing community resilience through optimal renewable resource allocation and load scheduling in order to minimize unserved load and thermal discomfort. The proposed control architecture distributes the computational effort and is easier to be scaled up than traditional centralized control. The decentralized control architecture consists of two layers: The community operator layer (COL) allocates the limited amount of renewable energy resource according to the power flexibility of each building. The building agent layer (BAL) addresses the optimal load scheduling problem for each building with the allowable load determined by the COL. Both layers are formulated as a model predictive control (MPC) based optimization. Simulation scenarios are designed to compare different combinations of building weighting methods and objective functions to provide guidance for real-world deployment by community and microgrid operators. The results indicate that the impact of power flexibility is more prominent than the weighting factor to the resource allocation process. Allocation based purely on occupancy status could lead to an increase of PV curtailment. Further, it is necessary for the building agent to have multi-objective optimization to minimize unserved load ratio and maximize comfort simultaneously.

model predictive control↗

Intelligent multi-zone residential HVAC control strategy based on deep reinforcement learning

Residential heating, ventilation, and air conditioning (HVAC) has been considered as an important demand response resource. However, the optimization of residential HVAC control is no trivial task due to the complexity of the thermal dynamic models of buildings and uncertainty associated with both occupant-driven heat loads and weather forecasts. In this paper, we apply a novel model-free deep reinforcement learning (RL) method, known as the deep deterministic policy gradient (DDPG), to generate an optimal control strategy for a multi-zone residential HVAC system with the goal of minimizing energy consumption cost while maintaining the users’ comfort. Here, the applied deep RL-based method learns through continuous interaction with a simulated building environment and without referring to any prior model knowledge. Simulation results show that compared with the state-of-art deep Q network (DQN), the DDPG-based HVAC control strategy can reduce the energy consumption cost by 15% and reduce the comfort violation by 79%; and when compared with a rule-based HVAC control strategy, the comfort violation can be reduced by 98%. In addition, experiments with different building models and retail price models demonstrate that the well-trained DDPG-based HVAC control strategy has high generalization and adaptability to unseen environments, which indicates its practicability for real-world implementation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Factors Influencing Building Demand Flexibility

The U.S. Department of Energy’s National Roadmap for Grid-interactive Efficient Buildings (GEB) acknowledged that building demand flexibility (DF) is both an important strategy to decarbonizing the buildings sector and an important resource for meeting the changing needs of the electrical grid such as improving grid reliability. However, understanding the complexity and uncertainties in real building field performance of DF strategies is a large gap hindering stakeholders on both grid and buildings side to make investments on deploying such strategies. The research work in this report intended to advance understanding of the variability and influential factors in building demand flexibility. Adding such knowledge based on lab testing results and measured performance data from real buildings is an important contribution. The report uses standardized metrics and methods to quantify DF performance from field-measured DF datasets of two significant building groups of big-box retail and medium office buildings to present the challenge of building DF variability in multiple dimensions. The report presents findings related to how several key factors influence building demand flexibility from implementing a common, cost-effective DF control strategy (i.e., adjusting zone temperatures). The findings are supported by full-scale lab testing, field data analysis and simulation research. The authors also provided application-oriented recommendations to stakeholders such as building aggregators, utility program design professionals, sophisticated building portfolio owners, and more.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Directing the adsorption and assembly of laponite nano-discs at oil–water interfaces

Achieving tunable controls on the adsorption and self-assembly of nanoscale building blocks at immiscible fluid interfaces is essential for synthesizing advanced materials, stabilizing emulsions, and the sustainable storage and recovery of fluids. Although extensive efforts have been directed toward resolving the assembly of spherical nanoparticles at water–hydrocarbon interfaces, 2D nanoparticles have received far less attention. In this study, we developed novel controls to direct the adsorption and assembly of 2D laponite nano-discs (diameter = ∼30 nm and thickness = ∼1 nm) at water–heptane interfaces using traces of sodium dodecyl sulfate (SDS) surfactant, demonstrated by advanced in situ small-angle X-ray scattering, atomic force microscopy, spinning drop tensiometer measurements and molecular dynamics simulations. The results show that SDS surfactant displaces the adsorbed laponite nano-discs from the interface toward the aqueous phase. The extent of this displacement increases with SDS concentration such that high SDS concentrations convert laponite-rich interfaces to SDS-rich interfaces free of laponite nano-discs. This transformation is associated with significant alterations in the rheological and nanomechanical properties of the host interface. In this context, reduction in interfacial tension and interfacial stiffness and an increase in the interfacial deformation is observed on increasing the SDS concentration from 0 to 0.1 wt%. The displacement of laponite nano-discs from the interface is driven by strong electrostatic interactions between the hydrophilic SDS group and interfacial water molecules. These studies unlock new insights into the adsorption and assembly of 2D nanoscale particles at water–hydrocarbons interfaces that are relevant for various applications related to energy and environmental science and engineering.

interfacial tension↗

Automatic Receptacle Controls: Evaluating the clarity of receptacle markings

Plug loads and the electric loads of devices plugged into receptacles in commercial buildings play a significant and growing role in commercial buildings. Because plug loads are portable and are often placed in the building by the occupants, they are a challenging load to manage. This report summarizes an analysis of commercially available automatic receptacle controls (ARCs). As a part of this study, generic versions of ARCs were presented to a general user audience via an online survey, wherein survey respondents indicated which markings more clearly indicated that the receptacle was controlled. A total of 210 responses were collected and included in the analysis presented in this report. The results showed that receptacles with high-contrast markings were consistently clearer and more evident to the users than low-contrast markings. The survey responses also revealed that receptacles with a border drawn around each controlled receptacle were clearer and distinct to the users compared to other markings. These results led to the conclusion that for energy saving technology to be effective, consistent and easy to understand markings are necessary.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Exploring strongly correlated quantum spin systems with quantum computers

At inception, quantum annealing leveraged quantum mechanics for classical optimization tasks. However, as machine coherence increases, the realization of quantum spin systems has emerged as an even more fruitful application of this computational model. Alternatives to the standard gate model deserve exploration, to achieve useful quantum advantage via analog quantum computing. The recent demonstration of so-called coherent quantum annealing with 1,000s of qubits, further expands the potential for this hardware to explore quantum system dynamics where the effects of quantum fluctuations can be carefully controlled and observed directly. Implementing existing celebrated spin models—or in fact new and dedicated ones—into quantum annealers will lead to observation and detection of quantum phenomena not yet observed, or not visualized directly, in experimental physics laboratories. Rather than computing or simulating quantum systems, these quantum computers allow one to simply build quantum systems, and experiment on them in an uniquely controlled way, with characterization down to the constitutive degree of freedom. This provides an unprecedented opportunity for understanding the physics of quantum spin systems. Keywords: Theoretical physics currently abounds of interesting theoretical spin models to explore frustration, strongly correlated spins, spin liquids, fractionalized excitations, and topological matter. However enticing, such models are generally only weak proxies for the properties of actual materials. In quantum annealers these models could be realized and experimented upon. Moreover, many more realistic models of such materials could be realized in quantum annealers. Employed in this way, quantum annealers provide an extraordinary versatile platform to explore quantum effects that are hard to find, detect, and characterize in natural materials.

36 MATERIALS SCIENCE↗

Demand Response in Residential Energy Code: Technical Brief

As buildings account for over 75% of U.S. electricity use, effectively managing their loads can greatly facilitate the transition towards a clean, reliable grid. Grid-interactive efficient buildings (GEBs) combine efficiency and demand flexibility with smart technologies and communication to provide occupant comfort and productivity while serving the grid as a distributed energy resource (DER). In turn, GEBs can play a key role in ensuring access to an affordable, reliable, sustainable, and modern U.S. electric power system. Their national adoption could provide $\$$100-200 billion in U.S. electric power system cost savings over the next two decades. The associated reduction in CO 2 emissions is estimated at 6% per year by 2030 (DOE 2021). Building codes represent standard design practice in the construction industry and continually evolve to include advanced technologies and innovative practices. Historically, national model energy codes establish minimum efficiency requirements for new construction (ICC 2020). Expanding codes to support GEB capabilities is a pivotal step towards realizing demand flexibility in support of a clean grid by addressing capabilities to improve interoperability between smart building systems, the grid, and renewable energy resources. Realizing GEBs requires buildings with automated demand response (DR) capabilities that enable standardized communication with or control of, subject to explicit consumer consent, energy smart appliances or home energy management systems. This is achieved through direct or indirect (i.e., via an aggregator) communication between appliances and the electric grid. Energy codes can also support DR communication standardization and advance the deployment of building-integrated DERs such as energy storage, generation, and electric vehicles (EVs). Incorporating automated DR capabilities in energy codes provides many benefits to the consumers. Specifically, it aligns building electric load demand with intermittent renewable energy source availability, decreases peak load on the electric grid, allows buildings to respond to utility price signals, supports electrical network reliability and market growth of products and processes aligned with clean economic growth. The incorporation of DR into the model residential energy codes was considered for both the 2021 and 2024 International Energy Conservation Code (IECC) code development cycles. The approved DR measures in the 2021 cycle were removed in response to appeals (ICC 2020). Updated language was presented for consideration again for the 2024 IECC, where it was negotiated and again approved, and again removed in response to appeals (ICC 2024). This resulted in many sections, including sections on demand responsive controls, being moved to the credits options or an appendix as a voluntary application. This technical brief updates the proposed DR components such that they can be considered by states and local governments for direct incorporation into their codes, as well as for future IECC energy code development. The proposal refinements are intended to support consistency in approach and provide a degree of certainty for building owners, designers, contractors, manufacturers, and building and fire safety professionals. The scope of this technical brief includes three strategies for DR in residential buildings: 1) smart thermostats with demand-responsive control, 2) electric water heating incorporating demand-responsive controls and communication and 3) grid Integrated solar and energy storage systems.

2021 IECC↗

Augmented DNA Nanoarchitectures: A Structural Library of 3D Self-Assembling Tensegrity Triangle Variants

The DNA tensegrity triangle is known to reliably self-assemble into a 3D rhombohedral crystalline lattice via sticky-end cohesion. Here, in this study, the library of accessible motifs is expanded through covalent extensions of intertriangle regions and sticky-end-coordinated linkages of adjacent triangles with double helical segments using both geometrically symmetric and asymmetric configurations. The molecular structures of 18 self-assembled architectures at resolutions of 3.32–9.32 Å are reported; the observed cell dimensions, cavity sizes, and cross-sectional areas agree with theoretical expectations. These data demonstrate that fine control over triclinic and rhombohedral crystal parameters and the customizability of more complex 3D DNA lattices are attainable via rational design. It is anticipated that augmented DNA architectures may be fine-tuned for the self-assembly of designer nanocages, guest–host complexes, and proscriptive 3D nanomaterials, as originally envisioned. Finally, designer asymmetric crystalline building blocks can be seen as a first step toward controlling and encoding information in three dimensions.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

Evaluation of thermostat location for multizone commercial building performance

In multi-zone buildings, it is often found that a single shared thermostat controls more than one conditioned zones. Although these shared zones are supposed to have similar thermal needs (e.g., cooling and heating load), in reality, they are not mainly due to different orientations, sizes of windows, occupancy, space types, etc. This can cause unnecessary energy waste or thermal discomfort for the occupants. How to quantify this impact in multizone buildings remains a research gap. Therefore, this study aims to evaluate the impact of different sensor (i.e., thermostat) locations for multizone commercial buildings through a comprehensive modeling study. Here, two different scenarios for the sensor locations were selected to evaluate the impact in terms of energy and thermal comfort. The scenario (1) is that one to five sensors distributed among the five zones, but the sensor readings from selected zones will be used for no-sensor zones, which is no-mean sensor scenario. The scenario (2) is that one to five sensors distributed among the five zones, but the average temperature from the shared zones will be used for each of the shared zones, which is a mean sensor scenario. The uncertainty analysis was performed for different sensor location scenarios.(a)The major findings from an energy perspective, for scenario (1), the differences of cooling energy go as high as 17% more or 12% less, compared with the baseline. For heating energy consumption, the discrepancies go as high as 51% more or 52% less, compared with baseline. For site energy consumption, the discrepancies go as high as 3.2% more or 3.2% less, compared with baseline. For fan energy consumption, the discrepancies go as high as 3.2% more or as low as 1.0% less, compared with baseline. For scenario (2), the discrepancies of cooling energy go as high as 3% more, or 0.5% less, compared with the baseline. For heating energy consumption, the discrepancies, are go as high as 10.1% more or as low as 3.0% less, compared with baseline. For site energy consumption, the discrepancies go as high as 1.3% more or 0.3% less, compared with baseline. For fan energy consumption, the discrepancies go as high as 3.1% more or as low as 1.0% less, compared with baseline.(b) In terms of the indoor thermal comfort, for the no-mean-sensor scenarios, the discrepancies of unmet hours for cooling mode can be as high as 1,200 h, compared with the baseline. The discrepancies of unmet hours for heating mode can be as high as 740 h, compared with the baseline. For the mean-sensor scenarios, the discrepancies of unmet hours for cooling mode can be as high as 750 h, compared with the baseline. The discrepancies of unmet hours for heating mode can be as high as 50 h, compared with the baseline.

42 ENGINEERING↗

To Dim or Not to Dim: Why Is That Still a Difficult Question?

LED lighting is becoming widely adopted and is displacing most traditional lighting technologies. However, the traditional methods used to control light sources have not been similarly displaced. In an effort to address some of the long-standing weaknesses of one of the most popular control methods, the National Electrical Manufacturers Association (NEMA) recently released the ANSI C137.1-2019 standard for 0-10V control of LED drivers and fluorescent ballasts. The new standard builds upon previous specifications by providing requirements for some aspects of dimming-curve shape and endpoints. In order to characterize the performance variation found in market-available LED drivers, and to explore the potential impact of ANSI C137.1, Pacific Northwest National Laboratory’s Connected Lighting Test Bed was used to evaluate the response to 0-10V controls signals of 21 different LED outdoor cobrahead luminaires (typically used for street-lighting applications) that claimed dimmability via a 0-10V interface. The results provide insights about how ANSI C137.1 will affect the performance variation currently found among such products.

0-10V, LED dimming, interoperability↗

Generation and representation of synthetic smart meter data

Advanced energy algorithms running at big-data scale will be necessary to identify, realize, and verify energy savings to meet government and utility goals of building energy efficiency. Any algorithm must be well characterized and validated before it is trusted to run at these scales. Smart meter data from real buildings will ultimately be required for the development, testing, and validation of these energy algorithms and processes. However, for initial development and testing, smart meter data are difficult to work with due to privacy restrictions, noise from unknown sources, data accessibility, and other concerns which can complicate algorithm development and validation. This paper describes a new methodology to generate synthetic smart meter data of electricity use in buildings using detailed building energy modeling, which aims to capture the variability and stochastics of real energy use in buildings. The methodology can create datasets tailored to represent specific scenarios with known truth and controllable amounts of synthetic noise. Knowledge of ground truth also allows the development and validation of enhanced processes which leverage building metadata, such as building type or size (floor area), in addition to smart meter data. The methodology described in this paper includes the key influencing factors of real-world building energy use including weather data, occupant-driven loads, building operation and maintenance practices, and special events. Data formats to support workflows leveraging both synthetic meter data and associated metadata are proposed and discussed. Finally, example use cases of the synthetic meter data are described to illustrate potential applications.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Adaptive Urban Traffic Signal Control for Multiple Intersections: An LQR Approach

Traffic congestion leads to severe problems especially in urban traffic networks. It increases the chance of accidents, energy waste, and social costs. In order to address these problems, an adaptive linear quadratic regulator (LQR) approach is developed for traffic signal control at multiple intersections in an urban area. The proposed method controls the green time of the traffic signals to reduce traffic congestion and smooth traffic flow. Real-world data from vision-based traffic sensors are used to build the traffic network model, which mimics the real-world traffic behavior. In addition, the proposed control utilizes recursive least square parameter estimation, which is capable of tracking dynamic changes in traffic conditions. Simulation of Urban MObility (SUMO) is used to analyze the efficacy of the proposed method. Results of the simulation show that the proposed method outperforms pretimed control in various aspects.

adaptive LQR control↗

Modeling and Evaluation of Cyber-Attacks on Grid-Interactive Efficient Buildings

Grid-interactive efficient buildings (GEBs) are not only exposed to passive threats (e.g., physical faults) but also active threats such as cyber-attacks launched on the network-based control systems. The impact of cyber-attacks on GEB operation are not yet fully understood, especially as regards the performance of grid services. To quantify the consequences of cyber-attacks on GEBs, this paper proposes a modeling and simulation framework that includes different cyber-attack models and key performance indexes to quantify the performance of GEB operation under cyber-attacks. The framework is numerically demonstrated to model and evaluate cyber-attacks such as data intrusion attacks and Denial-of-Service attacks on a typical medium-sized office building that uses the BACnet/IP protocol for communication networks. Simulation results show that, while different types of attacks could compromise the building systems to different extents, attacks via the remote control of a chiller yield the most significant consequences on a building system’s operation, including both the building service and the grid service. It is also noted that a cyber-attack impacts the building systems during the attack period as well as the post-attack period, which suggests that both periods should be considered to fully evaluate the consequences of a cyber-attack.

Fu, Yanyang↗