Impact of heating and cooling loads on battery energy storage system sizing in extreme cold climates

Efficient operation of battery energy storage systems requires that battery temperature remains within a specific range. Current techno-economic models neglect the parasitic loads heating and cooling operations have on these devices, assuming they operate at constant temperature. In this work, these effects are investigated considering the optimal sizing of battery energy storage systems when deployed in cold environments. Here, a peak shaving application is presented as a linear programming problem which is then formulated in the PYOMO optimization programming language. The building energy simulation software EnergyPlus is used to model the heating, ventilation, and air conditioning load of the battery energy storage system enclosure. Case studies are conducted for eight locations in the United States considering a nickel manganese cobalt oxide lithium ion battery type and whether the power conversion system is inside or outside the enclosure. The results show an increase of 42% to 300% in energy capacity size, 43% to 217% in power rating, and 43% to 296% increase in capital cost dependent on location. This analysis shows that the heating, ventilation, and air conditioning load can have a large impact on the optimal sizes and cost of a battery energy storage system and merit consideration in techno-economic studies.

25 ENERGY STORAGE↗

A Flow Rate Dependent 1D Model for Thermally Stratified Hot-Water Energy Storage

Stratified tank models are used to simulate thermal storage in applications such as residential or commercial hot-water storage tanks, chilled-water storage tanks, and solar thermal systems. The energy efficiency of these applications relates to the system components and the level of stratification maintained during various flow events in the tank. One-dimensional (1D) models are used in building energy simulations because of the short computation time but often do not include flow-rate dependent mixing. The accuracy of 1D models for plug flow, plug flow with axial conduction, and two convection eddy-diffusivity models were compared with experimental data sets for discharging a 50-gal residential tank and recharging the tank with hot water from an external hot-water source. A minimum and maximum relationship for the eddy diffusivity factor were found at Re <2100 and >10,000 for recirculation of hot water to the top of the tank and vertical tubes inletting cold water at the bottom. The root mean square error decreased from >4 °C to near 2 °C when considering flow-based mixing models during heating, while the exponential decay of the eddy diffusion results in a root mean square error reduction of 1 °C for cone-shaped diffusers that begin to relaminarize flow at the inlet.

1D flow model↗

Simplified Performance Rating Method - Review of Existing Tools, Rulesets, and Programs. Literature and technical review

The Performance Rating Method (PRM) in ASHRAE Standard 90.1 (ASHRAE 2016) is a simulation ruleset for establishing minimum code compliance and for rating a building’s beyond-code applications. Building energy modeling (BEM) to comply with the PRM is often expensive and time consuming due to the complexity of code requirements. The goal of this project is to develop and codify a simplified PRM (S-PRM) approach for commercial buildings that will expand the use of BEM for small or simple buildings by defining a low-cost, simplified approach for creating robust and detailed models. This report summarizes a review of (i) the more commonly used existing codes, (ii) incentive programs, and (iii) the existing simplified energy modeling tools to identify which requirements are good candidates for simplification.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Performance study of a novel dew point evaporative cooler in the climate of central Europe using building simulation tools

This paper presents the performance research of a hybrid air conditioning system (System II) equipped with novel dew point evaporative cooler (DPIEC) for a retail building located in temperate climatic conditions. The new cooler has a dedicated, adaptable structure that maximizes its performance in the climate conditions of central Europe. The unit can operate as a typical regenerative air cooler when outdoor air is drier than indoor air, it can operate as a counter-flow heat recovery unit when indoor conditions are more dry than outdoor and it can operate as a combination of both arrangements. The year-round, hourly-stepped building energy simulations were carried-out using a prognostic tool of energy consumption. The novel dew point evaporative cooler application potential was established using the black-box model based on regression equations was established based on experimental tests on a prototype of novel DPIEC. The hybrid system operation was compared to the typical air handling unit equipped with a standard energy wheel for heat recovery (System I). Presented research shows that DPIEC can cover about 95% of total cooling loads while the energy wheel covers only 9% of total cooling load. System II allows us to save 65% of seasonal electricity consumption comparing to System I. It comes from the fact that during most of the cooling season DPIEC is in operation and it covers most of the cooling loads without the need to switch the chilled water system.

Air conditioning↗

Inventory of Clean Energy Education and Workforce Programs in Connecticut's I-91 Corridor

This document reports on the findings of an inventory of the educational and workforce development resources in a four-county area on the I-91 corridor in Connecticut. The overarching goal of this exercise is to help the local workforce leaders in Bridgeport, Connecticut to optimize their training programs to support the county's clean energy transition. The inventory generally finds that Fairfield County, where Bridgeport is located, lacks adequate education and training programs compared to other surrounding counties with similar populations. More than half of Fairfield County's programs occur through high school or career technical education programs, suggesting that there are minimal opportunities for workers who are not currently high school students. Much of the existing focus within Fairfield County is on general construction or plumbing and electrical skills. There is room to expand by offering more programs focusing on energy efficiency and renewable energy skills. The document outlines some potential next steps and questions for consideration for the local workforce leaders in Bridgeport. Bridgeport is a city located within Fairfield County in southwestern Connecticut. It is the largest city in Connecticut with an estimated population of 150,000. Through the Department of Energy-funded Communities LEAP program, NREL conducted an analysis of existing education and workforce development (EWD) programs located in Fairfield County that align with (or could support) the worker pipeline for occupations related to building energy efficiency (EE), renewable energy (RE), and clean energy manufacturing. The analysis also looked at EWD offerings in other counties in Connecticut as a point of comparison.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

RETScreen Plus Software Tutorial

Greater emphasis is being placed on reducing both the carbon footprint and energy cost of buildings. A building's energy usage depends upon many factors one of the most important is the local weather and climate conditions to which it's electrical, heating and air conditioning systems must respond. Incorporating renewable energy systems, including solar systems, to supplement energy supplies and increase energy efficiency is important to saving costs and reducing emissions. Also retrofitting technologies to buildings requires knowledge of building performance in its current state, potential future climate state, projection of potential savings with capital investment, and then monitoring the performance once the improvements are made. RETScreen Plus is a performance analysis software module that supplies the needed functions of monitoring current building performance, targeting projected energy efficiency improvements and verifying improvements once completed. This tutorial defines the functions of RETScreen Plus as well as outlines the general procedure for monitoring and reporting building energy performance.

Ganoe, Rene D.↗

The value of integrating a geothermal district heating system into a microgrid

As electrical grids increasingly rely on variable renewable energy, maintaining reliability and cost efficiency becomes more complex. To address these challenges, this study analyzed the integration of geothermal district heating as a grid-responsive thermal resource within a microgrid in Tuttle, Oklahoma. Building energy modeling using EnergyPlus estimated annual district heating demand at 2.9 GWh, with a peak load of 2.8 MW th . Techno-economic analyses were conducted to meet the heating demand under three geothermal scenarios, varying by production depth, flow rate, and thermal output, each supplemented by natural gas peaking boilers. In parallel, equivalent electrical load profiles were developed using typical coefficients of performance (COPs) for air-source heat pumps and electric boilers to establish an electrified baseline scenario. A complete end-use electrical load profile was also developed for the microgrid using Cambium dataset. The modeling results demonstrated reliable and economic operation of the geothermal systems over 30 years, with COPs ranging from 2.6 to 8.9 and the lowest levelized heating cost at $\$$54.6/MWh. Geothermal integration reduced electricity consumption by up to 94.7 % compared to the non-geothermal base case, yielding annual energy savings of up to $\$$803 k. Avoided grid costs ranged from $\$$65 k–$\$$147 k per year, with individual events avoiding up to $\$$4,863 per hour. Grid-responsive operation further reduced wholesale energy costs by 53–56 %. These findings demonstrate geothermal heating, traditionally treated as a non-grid-responsive thermal resource, can be reconfigured to support dynamic grid services, offering a scalable pathway to enhance reliability and reduce costs in renewable-rich microgrids and district heating networks.

15 GEOTHERMAL ENERGY↗

Energy Systems Integration Facility Stewardship Summary: Fiscal Year 2023

A summary of NREL's good stewardship of the nationally unique Energy Systems Integration Facility (ESIF) highlighting performance metrics, infrastructure and capability upgrades, and examples of R&D impact. In fiscal year 2023, ESIF installed its third-generation high-performance computer, expanded capabailities for validating building energy controls, and demonstrated a leap in scale through virtual networking with another national laboratory. ESIF researchers made breakthroughs in cybersecurity for energy systems, efficient high-powered electric vehicle charging, leveraging reinforcement learning for grid resilience, and more.

ADVANCED PROPULSION SYSTEMS,ENERGY CONSERVATION, C↗

Future of Energy Efficiency in Buildings: Drivers and Market Expectations [Slides]

This slide-deck report identifies drivers of energy efficiency in buildings over the next 10 years, for all fuels. The report also provides insights on what the future of efficiency may look like in that time period and considers other distributed energy resources, as well as decarbonization and demand flexibility, to the extent they are intertwined with efficiency activities. Understanding market drivers and possible future market attributes for energy efficiency can help policy makers, regulators and industry make informed decisions—for example, how best to design policies and investments to support desired outcomes.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Estimating internal moisture generation rates in recently constructed, occupied homes in the southeastern United States

Internal moisture generation (IMG), or moisture generated by building occupants via activities such as respiration, cooking, bathing, and cleaning, is a critical input required for design, analysis, and simulation of building enclosure and heating, ventilation, and air conditioning (HVAC) systems. Based on previously published values, ASHRAE Standard 160-2021 provides guidance for estimating IMG rates for moisture control design analysis, which is based on occupied home datasets collected in the 1980s and 1990s. Residential energy use simulation software also utilizes estimates for IMG for energy rating, energy analysis, and code compliance calculations, as specified in ANSI/RESNET/ICC Standard 301. Data quantifying IMG rates in newer homes is useful in determining the continued relevance of current design and simulation guidance, and whether the guidance represents conditions found in new housing stock. ASHRAE Research Project 1844, conducted by the Florida Solar Energy Center (FSEC), a research institute of the University of Central Florida, estimated IMG rates in newer occupied homes built since 2013 in the southeastern US using a moisture balance model approach. Furthermore, the project obtained occupied home data in cooperation with a US Department of Energy Building America research project to characterize indoor air quality (IAQ) in newer US homes, along with presence, functionality, and occupant use of control measures. Full-scale laboratory homes operating with known IMG rates were used to validate a moisture balance model and quantify the accuracy of estimates obtained when the model is applied to data from occupied homes with unknown IMG rates.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Lahaina Energy Partnership: Technical Assistance Task Updates and Discussion Part 2

The Lahaina Energy Partnership (LEP) is an initiative funded by the U.S. Department of Energy (DOE) Office of Energy Efficiency and Renewable Energy (EERE) to support energy planning and rebuilding efforts in Hawaii's historic town of Lahaina on Maui as the community recovers from a devastating fire on August 8, 2023, with technical assistance provided by the National Laboratory of the Rockies. NLR has partnered with Hawaii-based community organizations to engage with Lahaina the community on energy priorities and inform the technical assistance scope. This virtual workshop presentation is the second in a two-part series to provide progress updates and request community input to guide next steps. Workshop 1 on November 18 focused on hydropower resource potential, building energy modeling, and workforce development. Workshop 2 on December 11 (this presentation) will focus on microgrids, electric grid hardening, policy and regulation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Lahaina Energy Partnership: Technical Assistance Task Updates and Discussion Part 1 [Slides]

The Lahaina Energy Partnership (LEP) is an initiative funded by the U.S. Department of Energy (DOE) Office of Energy Efficiency and Renewable Energy (EERE) to support energy planning and rebuilding efforts in Hawaii's historic town of Lahaina on Maui as the community recovers from a devastating fire on August 8, 2023, with technical assistance provided by the National Laboratory of the Rockies. NLR has partnered with Hawaii-based community organizations to engage with Lahaina the community on energy priorities and inform the technical assistance scope. This virtual workshop presentation is the first in a two-part series to provide progress updates and request community input to guide next steps. Workshop 1 on November 18 (this presentation) will focus on Hydropower resource potential, building energy modeling, workforce development. Workshop 2 on December 11 (presentation forthcoming) will focus on microgrids, electric grid hardening, policy and regulation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Towards Trust-Augmented Visual Analytics for Data-Driven Energy Modeling

The promise of data-driven predictive modeling is being increasingly realized in various science and engineering disciplines, where experts are used to the more conventional, simulation-driven modeling practices. However, trust remains a bottleneck for greater adoption of machine learning-based models for domain experts, who might not be necessarily trained in data science. In this paper, we focus on the building energy domain, where physics-based simulations are being complemented or replaced by machine learning-based methods for forecasting energy supply and demand at various spatio-temporal scales. We study the trust problem in close collaboration with energy scientists and engineers and describe how visual analytics can be leveraged for alleviating this trust bottleneck for stakeholders with varying degrees of expertise and analytics goals in this domain.

Kandakatla, Akshith R.↗

Impact of Insulation Strategies of Cross-Laminated Timber Assemblies on Energy Use, Peak Demand, and Carbon Emissions

Cross-Laminated Timber (CLT) panels have many structural benefits but do not have much thermal resistance. We have developed a solution to insulate CLT structures that uses high-performance insulation panels that provide R-values up to R40/inch. The CLT panels are made of layers of wood laminates (three, five, seven or more). The solution replaces some of the wood laminates in the CLT production with the insulation panels in a staggered fashion so that the wood laminates maintain contact throughout the panel, ensuring the CLT panel’s structural integrity. The insulated CLT panels have factory-installed water-resistive barriers reducing the installation time by eliminating installing insulation and water-resistive barriers on site. Per simulations, the CLT/insulation panel achieved code-required insulation levels with commonly available insulation materials. The significance of the thermal mass of CLT/insulation hybrid building envelopes was quantified by comparing the whole building energy performance and peak demand of traditional low mass and CLT wall assemblies resulting in up to 7% reduction in peak demand for cooling in Knoxville, TN, in a multifamily building. Buildings contribute over 40 percent of carbon emissions. The proposed CLT/insulation hybrid building envelope addresses both operational and embodied carbon by having high thermal resistances due to the embedded insulation sections and eliminating the use of high embodied carbon materials such as steel and concrete. The carbon benefit is estimated.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Multi-criteria thermal resilience certification scheme for indoor built environments during heat waves

With climate change, the indoor built environment is expected to significantly influence the occupant's safety and well-being. A novel multi-criteria thermal resilience certification scheme for indoor built environments during extreme heat events is proposed in this paper. The certification scheme considers overheating, thermal comfort, heat stress, and hygrothermal discomfort in built environments. These criteria are quantified using key performance indicators like indoor overheating degree, hours of exceedance, wet-bulb globe temperature, and heat index, respectively. This scheme is developed based on existing best practices like standards, rating systems, and literature. The scheme is implemented on a benchmark building energy performance model for detached post-World War II dwellings in Belgium as a case study using weather data measured from the City of Brussels. The indoor overheating in the reference dwelling is assessed with a static threshold of 27 °C for the bedrooms and adaptive thresholds for other areas. The analysis found that the building performance is within the defined threshold levels throughout the heat wave duration for all criteria. Therefore, the reference dwelling got a maximum attainable score of four points and is rated five-star for thermal resilience during heat waves. The proposed certification scheme is intended as a standardized framework and highlights the need for further revisions in building performance policies and guidelines.

Climate change↗

Techno-Economic Analysis for a Potential Geothermal District Heating System in Tuttle, Oklahoma: Preprint

Geothermal deep direct use (DDU) has potential across a wide swath of the United States but is underutilized due to challenging project economics associated with developing a deep geothermal resource for a large-scale and variable heat demand. The National Renewable Energy Laboratory (NREL) and University of Oklahoma evaluated the feasibility of a geothermal district heating (GDH) and cooling system in two schools and 250 houses by utilizing existing oil and gas (O&G) wells in Tuttle, Oklahoma. Heating and cooling demand in the two schools and a typical single-family house were modeled using EnergyPlus building energy simulation software. The modeling results indicated that annual heating demand in two schools and 250 houses is approximately 2.61 GWhth, and cooling demand in the two schools is approximately 2.65 GWhth. In this scope, the techno-economic analysis (TEA) was conducted using the GEOPHIRES tool combined with the TOUGH2 reservoir simulator. The reservoir performance, including geothermal heat production capacity, was modeled by the reservoir simulator TOUGH2. Then, levelized cost of heat (LCOH) was calculated using GEOPHIRES version 3.0, which includes new features such as hourly heat load optimization and peak performance evaluation. Geothermal reservoir temperature was estimated as 90.5 degrees C at a total depth of 3.3 km by the regional average temperature gradient of 22.8 degrees C/km and validated by cation geothermometer calculations. Four production scenarios with two different well configurations and two different heat load profiles have been developed for well flow rates ranging between 3.1 kg/s and 9.3 kg/s. The LCOH of the district heating and cooling system was calculated between $95 and $210/MWh ($28/MMBtu to $62/MMBtu) for four different production scenarios. Typical natural gas prices for residential customers in Oklahoma have ranged from 9 to 19 $/MMBtu over the past decade, which indicates a challenge for deployment of such a GDH system.

deep direct-use↗

Techno-Economic Analysis for a Potential Geothermal District Heating System in Tuttle, Oklahoma

Geothermal deep direct use (DDU) has potential across a wide swath of the United States but is underutilized due to challenging project economics associated with developing a deep geothermal resource for a large-scale and variable heat demand. The National Renewable Energy Laboratory (NREL) and University of Oklahoma evaluated the feasibility of a geothermal district heating (GDH) and cooling system in two schools and 250 houses by utilizing existing oil and gas (O&G) wells in Tuttle, Oklahoma. Heating and cooling demand in the two schools and a typical single-family house were modeled using EnergyPlus building energy simulation software. The modeling results indicated that annual heating demand in two schools and 250 houses is approximately 2.61 GWhth, and cooling demand in the two schools is approximately 2.65 GWhth. In this scope, the techno-economic analysis (TEA) was conducted using the GEOPHIRES tool combined with the TOUGH2 reservoir simulator. The reservoir performance, including geothermal heat production capacity, was modeled by the reservoir simulator TOUGH2. Then, levelized cost of heat (LCOH) was calculated using GEOPHIRES version 3.0, which includes new features such as hourly heat load optimization and peak performance evaluation. Geothermal reservoir temperature was estimated as 90.5 degrees C at a total depth of 3.3 km by the regional average temperature gradient of 22.8 degrees C/km and validated by cation geothermometer calculations. Four production scenarios with two different well configurations and two different heat load profiles have been developed for well flow rates ranging between 3.1 kg/s and 9.3 kg/s. The LCOH of the district heating and cooling system was calculated between $95 and $210/MWh ($28/MMBtu to $62/MMBtu) for four different production scenarios. Typical natural gas prices for residential customers in Oklahoma have ranged from 9 to 19 $/MMBtu over the past decade, which indicates a challenge for deployment of such a GDH system.

deep direct-use↗

Indoor air quality in California homes with code-required mechanical ventilation

Data were collected in 70 detached houses built in 2011-2017 in compliance with the mechanical ventilation requirements of California's building energy efficiency standards. Each home was monitored for a 1-week period with windows closed and the central mechanical ventilation system operating. Pollutant measurements included time-resolved fine particulate matter (PM 2.5 ) indoors and outdoors and formaldehyde and carbon dioxide (CO 2 ) indoors. Time-integrated measurements were made for formaldehyde, NO 2 , and nitrogen oxides (NO X ) indoors and outdoors. Operation of the cooktop, range hood, and other exhaust fans was continuously recorded during the monitoring period. Onetime diagnostic measurements included mechanical airflows and envelope and duct system air leakage. All homes met or were very close to meeting the ventilation requirements. On average, the dwelling unit ventilation fan moved 50% more airflow than the minimum requirement. Pollutant concentrations were similar to or lower than those reported in a 2006-2007 study of California new homes built in 2002-2005. Mean and median indoor concentrations were lower by 44% and 38% for formaldehyde and 44% and 54% for PM 2.5 . Ventilation fans were operating in only 26% of homes when first visited, and the control switches in many homes did not have informative labels as required by building standards.