At least 73 records · Page 4

Industry Assessment and Initial Adaptive Protection System Design

This report presents the success merits, logic design details, and test plans for adaptive protection schemes for microgrids, secondary distribution networks, and radial distribution feeders. Success merits are presented in terms of challenges and issues which should be mitigated. The challenges and issues were identified during site-specific simulations and analysis presented in a prior report. The adaptive protection logic designs are presented in a vendor-neutral manner to make them readily adaptable to site--specific protection relays and controllers which support custom logic design. Vendor-specific implementations of the logic for the adaptive protection laboratory tests are also presented. The final section of the report presents details of the testing methodology, plans, and documentation for each of the three adaptive protection schemes.

14 SOLAR ENERGY↗

Variable frequency response testbed to validate protective relays up to 20 kHz☆

Microgrids operate in islanding or utility grid mode. In islanding mode, distributed energy sources with power electronics inverters can generate fault currents over a wide range of frequencies. To gain a better understanding of the nature of these events, it is crucial to measure currents at frequencies of up to 20 kHz at transient states with protective relays. Protective relays at these frequency responses should be tested prior to being installed in microgrids. However, testing at high-frequency currents cannot be done with Relay Test Equipment (RTE) that generate signals up to 50th Harmonic for 60 Hz (3 kHz). In this study, a frequency response method and testbed for high-frequency currents of up to 20.16 kHz was developed and tested. The testbed utilized a RTE and High-Frequency Power Source/ Amplifier. Furthermore, frequency relay experiments were run at frequencies of up to 1 and 20.16 kHz at a current magnitude of 0.1 and 0.5 A, respectively. The events were collected, and the current magnitude and frequency were plotted at time and frequency domain, respectively. The study of current magnitude and frequencies of up to 20.16 kHz for two overcurrent relays was performed and validated the variable frequency testbed and methodology.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Characterization of Harsh Environments, At-Risk Microgrid Components, and Hardening Technologies (Report Version 0.1)

Microgrid implementation can help improve electrical service, reliability, and resilience for localized communities. However, they may be susceptible to damage from natural disasters and extreme weather events, which often coincide with times of greater community dependence on microgrids due to likely increased vulnerability of equipment on the main grid. Microgrid equipment can be protected against these hazards through various hardening techniques. The selection of hardening mitigations may depend on the actual risk of the hazard in the specific location and for the specific type of system, as well as cost and feasibility factors. This report summarizes a framework that can be used to characterize risk to a microgrid system from a list of natural hazards enumerated by FEMA. We also describe hardening techniques and mitigations that can be used for specific energy generation, storage, loads, and power delivery elements within a microgrid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Real-Time Testbed for Smart Grid Recloser Controller

The growing need for a low voltage recloser has become apparent due to the rise in requirements for a smart grid. This includes more detailed management of power flow forward (towards load) and backward (towards generation), source synchronization in real time, more indepth fault responses, and the use of green energy. The SEL-651R-2 relay is a device that can manage these needs, especially in fault response and synchronization, and is commonly used in systems called microgrids. Microgrids are distribution level systems that are able to operate separated from the main grid, are typically installed much closer to the load(s), and are fed by distributed energy resources (DERs), such as wind, solar or diesel generators. The SEL-651R-2 is normally used in the field with presets operative settings, but the Western Michigan University (WMU) Center for Interdisciplinary Research on Secure, Efficient and Sustainable Energy Technology (WMU InterEnergy Center) wished to test this device in its range of capabilities for microgrid application. A Hardware-In-the-Loop (HIL) testbed was implemented and used through the Real Time Digital Simulator (RTDS) using the RSCAD software to test the SEL-651R-2's use cases and functions. The testbed includes a microgrid with interconnection to a larger main grid, and the relay is meant to control the recloser at the point of common coupling (PCC) between the main grid and microgrid. The testbed shows how basic protections, reclosing, and synchronization checks function when handling faults that affect both the microgrid and the main grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design and Development of a High Fidelity Cyber-Physical Testbed

In order to ensure that future critical infrastructure systems are resilient to various types of such advanced and persistent threats, it is important to develop and integrate tailored solutions that holistically address cyber-attack detection and mitigation in a timely manner such that adverse system impacts that impact a large population are avoided. Further, it is essential to create environments that allow control, protection and communication to exist within a realistic environment to analyze the effects of adverse conditions and system operating modes. This project aims to establish a high-fidelity testbed environment for modeling and simulating a single microgrid all the way up to a network of microgrids along with baseline controls, protection, and associated cyber communication. This is an important activity because accurately modeling and simulating the various power-electronics-based DERs and loads in a microgrid is critical to adequately capturing their behaviors over a wide range of off-normal conditions, as well as to evaluate the resilience of the system using the developed controls. The work presented in this report focuses on the process of building this high-fidelity testbed and the associated experimentation it enables. The model enables the creation of high-fidelity use cases and associated datasets that have been used extensively within the initiative to study resilience and support novel control development and prototyping. The work heavily leverages existing capability that is part of the high-fidelity cyber-physical system experimentation lab to create a power hardware-in-the-loop setup. The report also details the creation of an automated model building platform that can enable high-fidelity real-time models to be built without much effort allowing existing low-fidelity models to be analyzed in higher fidelity. Lastly, the report also discusses efforts center around scaling to large complex power system models to make the experimentation more effective.

97 MATHEMATICS AND COMPUTING↗

Travelling wave‐based fault detection and location in a real low‐voltage DC microgrid

Abstract This paper discusses a device‐level implementation of a travelling wave (TW) protection device (PD) designed for a real low‐voltage DC microgrid. The TWPD fault detection and location algorithm is executed on a commercial digital signal processor (DSP) board, involving signal sampling at 1 MHz via the DSP board's analog‐to‐digital converter (ADC). The analogue input card measures positive pole, negative pole and pole‐to‐pole voltages at the TWPD location. Upon a successful fault detection using a second‐order high‐pass filter, the voltage data is normalised and multi‐resolution analysis (MRA) is performed on a 128‐sample buffer around the TW arrival time. MRA employs the discrete wavelet transform (DWT) to capture high‐frequency voltage patterns, and then the Parseval's energy theorem quantifies these TW characteristics by computing the energy of reconstructed wavelet coefficients. These energy values per decomposed frequency band are the basis for training a random forest classifier that predicts fault location and type. The TWPD is fully implemented and connected to a real DC microgrid in Albuquerque, NM, USA, for validation, and results are shown for field tests verifying the performance under faults.

Paruthiyil, Sajay Krishnan [Department of Electric↗

Comparison of Sequence Component-Based Fault Detection and Relay Coordination Algorithms in Inverter-Based Networks

Protection of inverter-based microgrids using sequence component-based relaying schemes is a promising solution. These methods offer several advantages, including lower computational requirements, compatibility with commercial relay systems, and cost-effectiveness compared to communication-based approaches. This article investigate the performance of various sequence component based schemes with the objective of identifying the algorithms that provide the best fault detection and relay coordination, solely relying on local voltages and current at relay terminals. Positive, negative and zero sequence impedance, admittance and power detection algorithms were tested on modified IEEE 13 bus test network for various shunt faults (LG, LL, LLG, LLL). Hardware-in-the-loop validation was achieved using the Typhoon real-time simulator, interfacing with a SEL 751 relay. This research demonstrates that while several algorithms are capable of detecting faults with sufficient accuracy, only a few are effective in achieving proper coordination. Validation results indicate that the negative sequence power approach provides the best performance in both fault detection and coordination.

Patel, Deepika [ORNL] (ORCID:0000000341099994)↗

Investigation on Tuning Power–Frequency Droop for Improved Grid–Forming Inverter and Synchronous Generator Transient Load Sharing

Poor transient load sharing has been observed during the parallel operation of synchronous generators (SGs) and droop-controlled grid-forming (GFM) inverter-based resources (IBRs) in islanded microgrids. This can result in overcurrent protections, causing the inverters to trip, which leads to the collapse of voltage and frequency. In this article, small-signal analysis supported by electromagnetic transients (EMTs) simulation is performed on a detailed model of a microgrid containing IBRs and an SG to identify underdamped modes and their sensitivities to the power–frequency (P-F) droop parameter. Further EMT simulation of a more complex microgrid model with multiple GFM IBRs and SGs is performed to determine whether trends identified from the modal analysis extend to cases where the number of SGs in operation may vary. The objective is to investigate the effectiveness of tuning this parameter to reduce the likelihood of overcurrents in response to load and generation disturbances. The work uncovers both fast and slow modes of concern. Primarily, the findings show that increasing the P-F droop value improves the damping of the slower mode while degrading the damping of the faster mode, leading to an upper limit on the damping improvement of the GFM IBR output current. In EMT simulations of the more complex microgrid, the greatest damping improvement still exhibits significant maximum overshoot. Furthermore, the optimal value of the P-F droop parameter is sensitive to the number of SGs in operation. The conclusion is that tuning the P-F droop parameter is not an effective means to avoid the overcurrent tripping of GFM IBRs during response to large load or generation disturbances when operating in parallel to SGs in islanded microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Quantifying the Protectability of Power Systems for Restoration Applications

With the increasing availability of distributed energy resources, controllable switches, and advanced metering infrastructure, distribution systems are exploring opportunities for improving system reliability through fault location, isolation, and service restoration. During permanent outages, this requires islanding microgrids and/or reconfiguration of the feeders; however, it is critical to assess the protection of the islanded/reconfigured networks before transition because the rated load and fault current conditions change. This paper presents a novel “protectability” metric that quantifies the protection performance and allows the operators to compare the effectiveness of the protection between two or more possible reconfiguration and islanding approaches. We present the mathematical formulation and assumptions for the metric. Multiple configurations of the Electric Power Research Institute J1 feeder, both in grid-connected and weak-sourced islanded operation, are used to demonstrate the performance of the metric with reference to overcurrent protection. Takeaways for future studies on system planning integration are provided.

distributed energy resources↗

Understanding Community Microgrids

Increasing need for distribution circuit reliability and resilience prompt a clearer understanding of community microgrid interconnection and operational requirements. While customer-owned, behind-the-meter microgrid implementation is not always simple, increasing demand for reliability has commercialized many installation approaches. This rapid commercialization has broadened industry understanding of single-customer microgrid integration. Moreover, off-grid behaviors of such microgrids are not required to meet utility standard interconnection requirements. However, multi-customer community microgrids (utility- or third-party operated), are less well explored and introduce more complex design and operational challenges. The control of DER along with distribution automation devices, unmanned operation, protection coordination, and other aspects makes community microgrids challenging to implement and operate in both on-grid and off-grid modes. This whitepaper is a technical primer for understanding community microgrids. It provides a foundation for understanding the components, configurations, design, and operational considerations for community microgrids.

14 SOLAR ENERGY↗

Low Voltage Network Protection Utility Workshop (Summary and Next Steps)

Increased penetration of Distributed Energy Resources and microgrids have fundamentally changed the operation al characteristics of Low Voltage (LV) network systems. Current LV network protection philosophy and practice are due for a significant re vamp to keep up with changing operating conditions. This workshop invites four of the major LV network users in the US to discuss the challenges they face today and the new technologies they have been experimenting with in light of this workshop discussion, use cases for further hardware-in-the-loop testing efforts are proposed to evaluate new LV network protection solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Microgrid to Microgrid Synchronization with Grid-Forming Inverters: Challenges and Solution

Research on network microgrids has primarily focused on control and optimization. However, application aspects such as microgrid-to-microgrid synchronization have not been fully addressed in existing literature. This paper first addresses the challenges of networking microgrids with grid-forming inverter in droop control. Then, it proposes a pre-synchronization algorithm to improves the synchronization speed and transient stability. To improve the speed, the phase difference between adjacent microgrids is minimized. Transients such as inrush current and oscillations are effectively mitigated by increasing the virtual impedance during interconnection. The proposed strategy allows smooth transitions when reconfiguration of the microgrids is needed. The applicability of this strategy to today’s microgrid systems is demonstrated through a validation in a 480V three-phase network microgrid testbed with commercial-grade inverters, protective devices, and switchgear.

Ferrari Maglia, Max↗

Integrating a Microgrid Controller with a Local OpenADR Server

When military microgrids isolate themselves from the main electrical grid, they must locally balance electricity supply and demand. Since local generation may be limited, the current strategy is to shed all but the most critical loads by tripping smart circuit breakers, which must then be reset manually (e.g., ESTCP project EW-201350). This strategy is typically applied at the building level, meaning that entire buildings housing mission critical activities must be excluded from any load management, while those considered non-critical may lose service entirely. The remotely controlled switchgear needed to manage load in this way is very expensive ($\$30,000$-$\$50,000$ per building). While effective at shedding load, this strategy disrupts installation operation and risks damaging equipment during both disconnection and re-energization. With the goals of lowering costs, protecting equipment, and enhancing the agility of DoD microgrids, this report demonstrates the use of cybersecure automated demand response (ADR) technology to manage microgrid loads during grid-independent (a.k.a. "islanded") operation. This automated approach achieves load shedding and shifting through communication signals sent to equipment controllers rather than by cutting off the flow of electricity within the microgrid itself. Because it operates only on the base network, with no connection to external entities, this strategy avoids the main cybersecurity concern raised by past applications of ADR on military bases.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Resilient Operation of Networked Community Microgrids with High Solar Penetration

This project, funded by the US Department of Energy’s Solar Energy Technologies Office (SETO), focused on the operation of microgrids as a coordinated network. The primary objective, which was successfully achieved, was to develop both control strategies and hardware solutions to support the resilient and efficient operation of networked microgrids with high solar penetration. The work was structured around the following four main tasks: • Development of distributed and scalable optimization algorithms for AC-coupled networked microgrids. • Design and implementation of a novel DC interconnection hardware to enable precise power exchange between microgrids. • Laboratory operational validation of the developed technologies using 480 V testbeds and commercially available hardware. • Field operational validation of the complete solution in Adjuntas, Puerto Rico, interconnecting two kW-scale, split-phase microgrids of Casa Pueblo’s microgrids. This project addressed multiple technical challenges across the domains of optimization, control, hardware interconnection, and protection. One of its key contributions was delivering tangible, real-world solutions for networking microgrids. In contrast to purely theoretical or simulation-based work, this project included full-scale hardware operational validation both in the lab and in the field. The work conducted as part of this project—in collaboration with the University of Puerto Rico; the University of Tennessee, Knoxville; the University of Central Florida; and Casa Pueblo—has advanced the state of the art in networked microgrids. Key contributions include the development of distributed control strategies, practical solutions for real-world implementation challenges, and the introduction of a novel DC interlink approach for microgrid interconnection. The project featured both laboratory and field validation using commercial off-the-shelf components. The field deployment successfully validated that a group of microgrids can operate in a coordinated manner, enabling precise power flow between systems and mutual support during extreme events. This project resulted in 15 journal publications and 15 conference papers; 5 graduate students and 15 undergraduate students were supported. The codes of distributed optimization and forecasting were made open-source through OSTI.gov for distributed optimization and forecasting. All the publications are available in the ORNL-hosted project landing page. The DC interlink with state-of-charge balancing control was operationally validated in Adjuntas by interconnecting two real-world, 240 V split-phase microgrids. To the best knowledge of the team, this represents the first operational validation of AC microgrids interconnected via DC-interlinks. As a culmination of this project, a follow-on grant was awarded to support the technology transfer of the distributed optimization framework to a commercial microgrid controller, Stellar Edge, developed by the California-based company New Sun Road.

14 SOLAR ENERGY↗

Voices of Experience: Microgrids for Resiliency

Modern attitudes around microgrids have evolved, from the idea that microgrids represent "grid defection" to perceiving them as a tool that utilities can use to solve challenges. One such challenge is improving resiliency. Faced with unpredictable, yet intensifying and dynamic weather and cyber risks, the value of resiliency is only growing for utility customers, regulators, and policymakers. Moreover, policymakers and regulators are increasingly asking utilities to accommodate the expansion and enhancement of such resiliency. The purpose of Voices of Experience: Microgrids for Resiliency is to guide discussions around this topic - everything from defining the many types of microgrids, to siting, ownership, control, and value streams. Utilities who participated in this project were generous with their time, insights, and examples of how they are using microgrids to solve one of their most urgent challenges: resiliency.

61 RADIATION PROTECTION AND DOSIMETRY↗

Assessing Dynamic Behaviors in Converter- Dominated Power Systems via RMS and EMT Simulations: A Study of Hawaii’s NELHA Microgrid

The transition from conventional power systems to converter-based microgrids has significantly advanced sustainability, clean energy integration, and operational reliability. However, this paradigm shift introduces operational challenges due to the intermittent nature of renewable energy sources and the non-linear characteristics of power electronic loads, inducing voltage fluctuations and harmonic distortions that complicate voltage and frequency regulation. Accurate dynamic modeling is hypothesized to be critical for capturing such effects, enabling reliable simulation and control strategy development. This study introduces an innovative dynamic modeling framework for a real-world converter-based microgrid, utilizing both root mean square (RMS) and electromagnetic transient (EMT) simulation methods. The microgrid was modeled in DIgSILENT PowerFactory, with simulations calibrated against high-resolution field measurements from SEL-735 power quality meters. Results show that RMS simulations effectively characterize steady-state dynamics, while EMT simulations are essential for capturing high-frequency transients and non-linear effects from photovoltaic inverters and variable frequency drives (VFDs). This complementary approach provides a comprehensive understanding of microgrid behavior, providing critical insights for improving simulation accuracy, advancing protection schemes, and improving resilience in future low-inertia power networks.

24 POWER TRANSMISSION AND DISTRIBUTION↗