Recommendations for Trust and Encryption in DER Interoperability Standards

Recently developed Distributed Energy Resource (DER) interoperability standards include communication and cyber security requirements. In 2018, the US national interconnection standard, IEEE 1547, was revised to require DER to include a Sun Spec Modbus, IEEE 2030.5 (Smart Energy Profile, SEP 2.0), or IEEE 1815 (DNP3) communication interface but does not include any normative overarching cybersecurity requirements. IEEE 2030.5 and associated implementation requirements for California, known as the California Smart Inverter Profile (CSIP), prescribe the greatest security features - including encryption, authentication, and key management requirements. Sun Spec Modbus and IEEE 1815 security requirements are not as comprehensive, leading to implementation questions throughout the industry. Further, while the security features in IEEE 2030.5 are commonly used in computing platforms, there are still questions of how well the technologies will scale in highly-distributed, computationally-limited inverter environments. In this paper, (a) the elements of IEEE 2030.5 encryption, authentication, and key management guidelines are analyzed, (b) potential scalability gaps are identified, and (c) alternative technologies are explored for possible inclusion in DER interoperability or cyber security standards.

42 ENGINEERING↗

Microgrid Service Restoration Incorporating Unmonitored Automatic Voltage Controllers and Net Metered Loads

Islanded microgrids may experience voltage and frequency instability due to uncontrolled state changes of voltage regulation devices and inaccurate demand forecasts. Uncontrolled state changes can occur if optimal microgrid restoration and dispatch algorithms, used for generating control commands for distributed energy resources, do not incorporate the behavior of automatic controllers of voltage regulation devices. Inaccurate demand forecasts may be encountered since post-outage demand of behind-the-meter net metered (NM) loads can vary significantly from their historical NM profiles. Here, this paper proposes an optimization formulation which allows optimal control of voltage regulators and capacitor banks without remote control and communication capabilities. A generalized demand model for NM loads is proposed which incorporates the cold load pickup phenomenon and their time varying post-outage demand in accordance with the IEEE 1547 standard. The time dependent optimal control formulation and the NM demand model are integrated in a sequential microgrid restoration algorithm by linearization of the involved logic propositions. A detailed case study on the unbalanced IEEE 123-node test system in OpenDSS validates the effectiveness of the proposed approach.

30 DIRECT ENERGY CONVERSION↗

Network Constraints Consideration for Grid-Edge Energy Management System

Increased deployment of distributed energy resources (DER) in distribution system is bringing need for enhanced grid intelligence, control, and flexibility. This is significant at the edge of the grid where DERs, loads or microgrids are located. Integrated DERs in a distribution system need to follow grid codes to avoid violations that results in DER disconnection. To comply with grid code requirements (e.g. IEEE 1547-2018) at the grid edge level, network constrained grid edge energy management system (GEEMS) is proposed in this paper. The objective of GEEMS is to provide economic solution for active and reactive power dispatch set-points at each interval and ensure voltage regulation to support secure interconnection of the grid edge segment to the distribution system. To evaluate the proposed GEEMS framework, four DERs are included into IEEE 13 bus system. GEEMS outperforms the existing economic dispatch-based energy management system by reducing the voltage violation.

Electric vehicle depot charging station↗

Security Enhancement of Network Constraint Grid-Edge Energy Management System

Network constrained grid edge energy management system (EMS) provides economic solution for active and reactive power dispatch of distributed energy resources (DERs) at the grid edge level. Grid edge EMS ensures secure interconnection of a circuit segment to the distribution system by maintaining grid code requirements (e.g. IEEE 1547–2018). Grid edge EMS is dependent on communication to receive load measurement, which brings a risk of unobservable false data injection attacks (FDIAs). To mitigate the risk, this paper proposes a framework to enhance resilient operation of grid edge EMS by detecting the unobservable FDIAs on loads and replacing them with forecasted values. In this work, a two-step detection algorithm is proposed. In first step, conventional residual based algorithm is deployed. Autoencoder (AE) based data driven mechanism is included in second step to detect the presence of unobservable FDIAs. After ensuring the presence of FDIA, its specific location is detected by checking the maximum residue values till the predefined threshold value is reached. Detected false data injected loads are then replaced with forecasted load values following long-short term memory (LSTM) based forecast to ensure resilient performance of grid edge EMS in the presence of attacks. This proposed security enhancement framework for grid edge EMS is evaluated in IEEE 13 bus system with three integrated DERs. Numerical simulation shows the validation of the proposed framework by reducing voltage violation in real operation of grid edge EMS.

cyber attack detection↗

Circulating Current Reduction of Back-to-Back MMC with Advanced Grid-Support Functionalities for Medium-Voltage Applications

A Lyapunov energy function based circulating current reduction scheme for a back to back modular multilevel converter based system for a microgrid application has been proposed in this digest. In order to ensure no circulating or zero sequence currents within the modules, the dynamics from one leg of the converter to the other are evaluated. A Lyapunov energy function is then developed and utilizing the circulating current dynamics of the converter the overall control law is implemented. In this digest a decentralized hierarchical control architecture has been implemented for the main current control; where the outer loop or the central controller implements the higher level grid interconnection functions as per IEEE 1547-2018 standards and the inner loop based on synchronous reference frame implements the current control architecture. The inner loops' outputs are the commanded converter voltages either on either side which are augmented by the Lyapunov energy function based circulating current suppression architecture. To evaluate the efficacy of the overall system, the overall system is modeled around a 300kVA back to back SiC multilevel modular converter used as a direct-connected medium voltage (MV) grid intertie based on MATLAB/Simulink domain. Several important case studies are presented in this paper to prove the effectiveness of the proposed architecture. case study results are presented.

circulating current↗

Development and Validation of a SiC Based 50 kW Grid-Connected PV Inverter: Preprint

In this digest a 50kW string PV inverter formed using all SiC semiconductor devices is presented. The inverter design includes additively manufactured power block, symmetrical Y-core inductors for ac side filter, and advanced inverter functionality for grid support. This inverter utilizes the conventional three-phase Voltage Source Inverter topology and optimizes the design for SiC based devices. This paper presents the full functional validation of the designed inverter along with quantification of the efficiency and power density. The performance of the inverter for high dc-bus voltage without multi-level topology to exploit SiC advantages is also presented in this digest. The full paper will include details of inverter design, optimization and further experimental validation.

14 SOLAR ENERGY↗

Control and Grid Support Function Evaluation for a Three-Phase Back-to-Back Modular Multilevel Converter System

This paper focuses on the evaluation of advanced inverter controls for a 500kW back-to-back (B2B), silicon carbide, multilevel modular converter (MMC) used as a direct-connected medium-voltage grid intertie. A decentralized hierarchical controller architecture for the MMC system is presented, which uses the main controller to implement higher level grid interconnection functions per the IEEE 1547–2018 standards and the local controllers to execute lower level closed-loop functionality of the MMC stages. This paper presents and elaborates on the grid functionalities are elaborated and presented. The back-to-back converter system is equipped with local controllers and their corresponding functionalities are presented. Case study results for the corresponding functionalities presented show the effectiveness of the proposed architecture. To enhance the operation capabilities of the system, a parameter update scheme has been implemented and utilized in unison with the controller.

decentralized control↗

Operation and Control of a Back to Back Modular Multilevel Converter System for Grid Forming Application with Advanced Grid Support Functionalities

The main focus of this paper is to investigate the possibility of using modular multilevel converter based back-to-back system for grid forming applications. A decentralized hierarchical control architecture with a modified local controller based on nonlinear techniques for grid forming application have been investigated. Grid functionalities based on IEEE 1547-2018 for grid forming converters have been utilized. The local controllers ensure distortion free balanced sinusoidal output voltage on the grid forming side with unbalanced or nonlinear loading condition. The grid following side ensures unity power factor currents under unbalanced grid voltage condition. The dc bus voltage control ensures oscillation free voltage under balanced conditions and control of the average voltage under unbalanced condition. Efficacy of the overall system is verified by modeling the system in MATLAB/Simulink and PLECS domain and the most important case studies are presented.

advanced grid support functionalities↗

Convolutional Neural Network-Based Protection-Zone Classification of Faults in Distribution Feeders with Photovoltaics.

Fault detection and isolation is critical for reliable operation of distribution systems. The ride-through requirements for the distributed energy resources (DER), mandated by the IEEE 1547-2018 standard, makes it challenging to use undervoltage (UV) conditions for fault detection. In addition, with low fault current contribution from these inverter-based DERs, the time-overcurrent relays are also less effective. Thus motivated, this paper presents a learning-based approach for fault detection and localization. A convolutional neural network (CNN)-based model is proposed which uses local voltage and current waveforms from DER locations and feeder substations, for training a zonal classifier. The classifier can be adopted into any relay-like device for discriminating between faults originating from different protection zones. The performance of the proposed approach was tested on publicly available test feeders with distributed photovoltaics (PVs).

Fault localization, convolutional neural networks,↗

An intelligent energy router for managing behind-the-meter resources and assets

With increase in distributed energy resources (DERs) and smart loads, each energy resource and load need a separate power conversion system leading to complex coordination and interaction, reduced energy conversion efficiency, coordinating compliance to grid standards (IEEE 1547) from multiple sources, reduced security. Also, multiple vendors with legacy system designs and proprietary communications interfaces result in redundancy and increase in cost of power electronics systems. This paper presents an energy router concept for buildings applications which provides autonomous power flow between sources and loads with a novel agent-based software interface.

Chinthavali, Madhu Sudhan↗

Analysis of Transformer Magnetizing Reactance Using Describing Function in Direct Power Control of Back-to-Back Modular Multilevel Converter with Advanced Grid Support

This paper presents a Port Controlled Hamiltonian based direct power control architecture for a back-to-back modular multilevel converter system connecting two ac sources at different frequencies. The system features advanced grid support functionalities based on IEEE 1547-2018, implemented on the inverter side. The rectifier side controller ensures reference following for active and/or reactive powers and maintains the commanded dc bus voltage. The inverter side controller ensures power command following for active and reactive powers.The proposed control architecture is designed to suppress second harmonic oscillations in powers during unbalanced grid voltage sags by dynamically adjusting the currents on each ac side. This also ensures effective elimination of any second harmonic oscillations in the equivalent dc bus voltage. Validation is performed on an OPAL-RT real-time platform with case studies on unbalanced and balanced sags, demonstrating the controller's effectiveness during real time implementation. A reduced-scale laboratory prototype further verifies these case studies, with experimental results for balanced sags due to grid simulator limitations. The results confirm the robustness and efficiency of the proposed control strategy in ensuring stable and reliable operation under various grid conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Model-Based Detection Scheme for Spoofed Sensor Data in Grid-Connected Inverters

In this article, a novel method to detect spoofed sensor data (SSD) for grid-connected inverters is proposed. First, a Kalman filter is used to estimate the inverter status in the proposed method. Then, the impact of SSD on the residual between estimation and control reference is analyzed. By leveraging the standard error of residual, an adaptive cumulative sum (CUSUM) chart is developed to achieve fast SSD detection and improve robustness. In addition, the proposed SSD detection method is verified by the hardware experiment. A comparative experiment with a conventional method also demonstrates the rapidity and robustness of the proposed method. Lastly, the performance of the proposed method under different noise covariance matrices is analyzed. Comprehensive analysis shows that the proposed method meets the detection requirement in IEEE 1547 Standard.

42 ENGINEERING↗

Enabling Resiliency Operations across Multiple Microgrids with Grid Friendly Appliance Controllers

Changes in economic, technological, and environmental policies are resulting in a re-evaluation of the dependence on large central generation facilities and their associated transmission networks. Emerging concepts of smart communities/cities are examining the potential to leverage cleaner sources of generation, as well as integrating electricity generation with other municipal functions. When grid connected, these generation assets can supplement the existing interconnections with the bulk transmission system, and in the event of an extreme event, they can provide power via a collection of microgrids. To achieve the highest level of resiliency, it may be necessary to conduct switching operations to interconnect individual microgrids. While the interconnection of multiple microgrids can increase the resiliency of the system, the associated switching operations can cause large transients in low inertia microgrids. The combination of low system inertia and IEEE 1547 and 1547a-compliant inverters can prevent multiple microgrids from being interconnected during extreme weather events. This study will present a method of using end-use loads equipped with Grid Friendly™ Appliance controllers to facilitate the switching operations between multiple microgrids; operations that are necessary for optimal operations when islanded for resiliency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Microgrid Modeling for Stability Analysis

Here this document is a summary of a report prepared by the IEEE PES Task Force (TF) on Microgrid (MG) Dynamic Modeling, IEEE Power and Energy Society, Tech. Rep. PES-TR106, 2023. In this paper, the major issues and challenges in microgrid modeling for stability analysis are discussed, and a review of state-of-the-art modeling approaches and trends is presented. In the context of the IEEE 1547 standard, the document covers issues associated with component models for MG dynamic studies and simulations, including generator and grid modeling, full and average converter models, unbalanced and balanced system conditions, dynamic and static loads, protection requirements, and detailed and simplified controls considering communications delays, packet losses, and security issues. Considering the future integration of grids and MGs to form broad integrated networks, a discussion is presented of the use of phasor vis-à-vis electromagnetic transient simulation tools for MG dynamic stability studies, as well as modeling scale-up issues and MG equivalent models. Specifically white-, grey-, and black-box models, are presented. This TF paper and companion report constitute a modeling guide for R&D groups working on developments and standards of MGs with a focus on stability issues.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Updating Interconnection Screens for PV System Integration

This white paper evaluates the origins and usefulness of the capacity penetration screen, offer short-term solutions which could effectively allow fast-track interconnection to many PV system applications, and considers longer-term solutions for increasing PV deployment levels in a safe and reliable manner while reducing or eliminating the emphasis on the penetration screen. Short-term andlonger-term alternatives approaches are offered as examples; however, specific modifications to screening procedures should be discussed with stakeholders and must ultimately be adopted by state and federal regulatory bodies.

14 SOLAR ENERGY↗

Analysis of High-Penetration Levels of Photovoltaics into the Distribution Grid on Oahu, Hawaii: Detailed Analysis of HECO Feeder WF1

Renewable generation is growing at a rapid rate due to the incentives available and the aggressive renewable portfolio standard (RPS) targets implemented by state governments. Distributed generation in particular is seeing the fastest growth among renewable energy projects, and is directly related to the incentives. Hawaii has the highest electricity costs in the country due to the high percentage of oil burning steam generation, and therefore has some of the highest penetration of distributed PV in the nation. The High Penetration PV (HiP-PV) project on Oahu aims to understand the effects of high penetration PV on the distribution level, to identify penetration levels creating disturbances on the circuit, and to offer mitigating solutions based on model results. Power flow models are validated using data collected from solar resources and load monitors deployed throughout the circuit. Existing interconnection methods and standards such as IEEE 1547, Hawaii Rule 14H and California Rule 21 are evaluated in these emerging high penetration scenarios. A key finding is a shift in the level of detail to be considered and moving away from steady-state peak time analysis towards dynamic and time varying simulations. Each level of normal interconnection study is evaluated and enhanced to a new level of detail, allowing full understanding of each issue.

14 SOLAR ENERGY↗

Microgrid Plant Control Design and Development

This report discusses the technical performance of the proposed microgrid at Potsdam, New York, and the enhanced microgrid controller platform. The test objectives were outlined by the DOE, and summary results and discussion are given for each objective. The findings show that the proposed Potsdam, NY microgrid would have a significant impact on the regional CO 2 emissions, the amount of imported energy from the utility, and the resiliency of the critical loads. Additionally, the enhanced microgrid control system developed for this project was tested to be compliant with IEEE 1547 standards, and able to generate revenues to help offset energy costs by way of participation in ancillary services.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Standard Inverter Interface and Compliance Framework

Electric Power Research Institute, Inc. (EPRI) and Sandia National Laboratories (SNL) collaborated to develop and demonstrate a standard communication interface for solar inverters as well as a compliance framework to verify proper product operation via that interface. This activity filled a key void in the needs of California in relation to revisions to California’s Electric Tariff Rule 21 interconnection guidelines. Rule 21 is a CPUC-approved tariff based on IEEE 1547 technical requirements that describes the interconnection, operating, and metering requirements for generation facilities to be connected to a utility’s distribution system, over which the CPUC has jurisdiction. These guidelines, as presently being developed, anticipate a requirement for future inverters to have a standard communication interface and to be testable to verify their proper operation prior to deployment.

14 SOLAR ENERGY↗