At least 73 records · Page 4

Hardware-in-the-Loop Evaluation of an Advanced Distributed Energy Resource Management Algorithm: Preprint

This paper presents the laboratory performance evaluation of voltage regulation under a new distributed energy resource management system (DERMS) algorithm via an advanced hardware-in-tbe-loop (HIL) platform. The HIL platform provides realistic testing in a laboratory environment, including the accurate modeling of a full-scale real-world distribution system from a utility partner, the DERMS software controller, and power hardware photovoltaic (PV) inverters. The new DERMS algorithm is developed based on online multiobjective optimization (OMOO) algorithms that perform fast dispatch of distributed solar PV simulated in a real-time digital simulator and real physical hardware devices. Experimental tests confirm the correct functioning of the HIL platform for evaluating controller algorithms and satisfactory voltage regulation performance of the developed OMOO algorithms.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Transient Efficiency, Flexibility, and Reliability Optimization of Coal-Fired Power Plants - Final Program Review

This program developed an advanced model-based monitoring and model-predictive control algorithms for a coal fired power plant (CFPP), and deployed these algorithms in a real-time platform to demonstrate performance benefits for transient flexibility and plant operation efficiency. More specifically, the objectives were successfully achieved through a combination of (i) developing a high-fidelity transient plant model in Apros, which was used as a high-fidelity plant simulation between $100-50\% TMCR$ where TMCR denotes the turbine maximum continuous rating, i.e., baseload, (ii) developing a very fast physics-based reduced-order model (ROM) of the plant, which ran more than $100\times$ faster than real-time, enabling its use as real-time embedded model for model-based estimation (MBE) and model predictive control (MPC) (iii) implementing a real-time MBE based on ROM using a robust unscented Kalman filter (UKF) to continuously tune the ROM to match the measurements from high-fidelity Apros plant model despite significant plant-model mismatch, and thus, obtain a Digital Twin of the plant (iv) designing and implementing a real-time MPC with dual objectives of transient plant load tracking with high ramp rates and minimizing coal consumption, i.e., improving plant efficiency in the baseload-partload operation range of $100-50\% TMCR$. Each key element above was developed and tested individually, and has been reported in corresponding Topical Reports. Finally, all the individual elements were integrated in an overall closed-loop system, that was successfully tested in desktop Simulink test harness simulations with ROM or high-fidelity model as the plant. Thereafter, the Simulink implementation was used to auto-generate C-code and deploy as real-time Docker microservice containers in Linux, and validate that they can run in real-time in the hardware-in-the loop (HIL) setup and produce the same results as in Simulink. The results of the integrated simulation tests in Simulink as well as the real-time HIL deployment are documented in this final report, showing good load tracking for load ramps at $3-4\%/min$ ramp rates, and achieving up to $5.5\%$ reduction in coal relative to baseline operation at $50\% TMCR$ load. The desktop and HIL simulations show successful performance of the overall model based estimation and control solution and achieve the key objectives of the program for flexible, efficient and reliable operation of sub-critical coal fired power plants.

20 FOSSIL-FUELED POWER PLANTS↗

Controller Hardware-in-the-Loop Modeling and Operation of a High-Power DC Charging Hub

High-power charging (HPC) concept will be a critical enabler for the wide-scale adoption and integration of electric vehicles (EVs). HPC hubs will have a significant impact on achieving this goal, particularly when considering the charging requirements of next-generation medium and heavy-duty vehicles (MD/HD) used in various vocational scenarios. This emphasizes the significance of evaluating and confirming the technical planning and multi-level operation of HPC hubs through modeling, protocol implementation, and simulation before hardware demonstration. The focus of this study is to develop the architecture, modeling, communication, and real-time controller hardware-in-the-loop (C-HIL) simulation of HPC hubs using the DC distribution system approach. Specifically, this work demonstrates the practical implementation of a custom Smart Energy Management System (SEMS) for a real-time C-HIL HPC hub simulation using the Open Charge Point Protocol (OCPP) for communication. OCPP is implemented on the Node-Red framework and the custom controller is executed in Python. We developed a rule-based controller to demonstrate the proposed approach.

ADVANCED PROPULSION SYSTEMS↗

Performance Evaluation of Data-Enhanced Hierarchical Control for Grid Operations

This paper presents a hardware-in-the-loop (HIL) simulation to evaluate the performance of voltage regulation of Data-Enhanced Hierarchical Control (DEHC). This DEHC uses an advanced distribution management system (ADMS) for grid operations to control legacy and grid-edge devices and coordinate with distributed energy management systems (DERMS) to manage high penetrations of photovoltaics (PV) on a utility distribution system. The HIL platform provides realistic laboratory testing, including accurate modeling (legacy devices, grid-edge devices, and PV) of the real-world distribution system from a utility partner, a real controller (ADMS), software controller DERMS, hardware grid-edge devices, and standard communications protocols. The test results demonstrate functionalities of the integrated platform and the performance of voltage regulation of the coordinated control systems. Based on laboratory testing, the utility can set up the same grid-automation system to manage DERs, legacy devices, and grid-edge devices to achieve their system-level control and operation objectives (e.g., voltage regulation), thus de-risking potential issues such as instability for field deployment.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Anomaly Detection and Mitigation in FACTS-based Wide-Area Voltage Control Systems using Machine Learning

With the increasing deployment of Flexible AC Transmission System (FACTS) devices in wide-area voltage control systems (WAVCS) for achieving improved voltage stability of bulk power systems, the possibility for cyber attacks on these systems is also increasing. Successful stealthy cyber attacks that are difficult to detect by traditional informational technology (IT)-based cybersecurity solutions or threshold-based bad data detectors can lead to a voltage collapse in power grid. This paper presents the testbed-based attacks implementation and real-time evaluation of machine learning (ML) algorithm for detecting and mitigating stealthy cyber attacks on FACTS-based WAVCS on a hardware-in-the-loop (HIL) testbed. Initially, we discuss the implementation of a fuzzy logic controller (FLC) that controls a Static VAR Compensator (SVC) device deployed in a two-area four-machine Kundur power system for improving transient voltage stability. Later, the ML-based Anomaly Detection and Mitigation (ADM) system is implemented on the cyber-physical HIL testbed to detect and mitigate various stealthy cyber attacks, which are injected in real-time over the wide-area network (WAN). The experimental results show accurate and effective performance of ADM system in detecting and mitigating anomalies while keeping the grid stable and within the system operating limits, as defined by the North America Electric Reliability Corporation (NERC).

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Evaluation of Hierarchical Controls for Advanced Distribution Management System-Centered Grid Operations: Preprint

This paper presents a hardware-in-the-loop (HIL) platform to evaluate the performance of voltage regulation using an advanced distribution management system (ADMS) for grid operations to control legacy and grid-edge voltage control devices and coordinate with distributed energy management systems (DERMS) to manage high penetrations of photovoltaics (PV) on a utility distribution system. The HIL platform provides realistic laboratory testing, including accurate modeling (legacy devices, grid-edge devices, and PV) of the real-world distribution system from a utility partner, a real controller (ADMS), software controller DERMS, hardware grid-edge devices, and standard communications protocols. The test results show proper functionalities of the integrated platform and the performance of voltage regulation of the coordinated control systems. Based on laboratory testing, the utility can set up the same grid-automation system to manage DERs, legacy devices, and grid-edge devices to achieve their system-level control and operation objectives (e.g., voltage regulation), thus de-risking potential issues (e.g., instability) for field deployment.

ADMS↗

Agentic traffic intelligence: Augmented human-in-the-loop scenario generation for microscopic traffic simulation

Traditional microscopic traffic simulation generation often relies on static datasets and manual design, limiting its ability to simulate complex conditions easily. This paper presents a novel framework, Agentic Traffic Intelligence, which combines human approval large language models (LLMs), the Real-Twin tool, and multi-agent systems to perform realistic microscopic traffic simulation scenario generation. The proposed framework incorporates human-in-the-loop (HIL) control, retrieval-augmented generation (RAG), and multi-agent control mechanisms. HIL mechanisms are used to guide multiple LLMs focused on attributes for microscopic simulation generation and to improve the interpretability and transparency of LLM execution for users. RAG enhances context extraction by dynamically integrating external knowledge sources for traffic scenario generation foundations. A multi-agent architecture with supervisory control coordinates the interaction of simulation components, including traffic simulators, control logic, and calibration tools. This enables the synthesis of simulation-ready scenarios that reflect dynamic demand profiles and behavior controls. Furthermore, the framework fuses multisource traffic data with unstructured context and supports iterative refinement through interactive user feedback. Validated through microscopic simulation using Simulation of Urban Mobility, the generated scenarios demonstrate high-fidelity network generation with inflow and turn movement and behavioral calibration, offering a robust and efficient tool for stress-testing and optimizing urban mobility systems.

Hierarchical multi-agent control↗

Emulation and detection of physical faults and cyber-attacks on building energy systems through real-time hardware-in-the-loop experiments

The increasing use of remote or mobile access, integrated wearable technologies, data exchange, and cloud-based data analytics in modern smart buildings is steering the building industry towards open communication technologies. The increased connectivity and accessibility could lead to more cyber-attacks in smart buildings. On the other hand, physical faults (e.g., HVAC -heating, ventilation, and air-conditioning faults) may have similar adverse impacts as those from the cyber-attacks on building energy systems, such as occupant discomfort, energy wastage, and equipment downtime. However, current physical behavior-based anomaly detection methods fail to differentiate between cyber-attacks and physical faults in building energy systems. Moreover, the challenge in collecting real-world threat data with ground truth has led researchers to rely on numerical models with user-defined assumptions, which may not accurately reflect real-world conditions due to the lack of in-situ experimental datasets. To address these challenges and gaps, this paper presents a flexible hardware-in-the-loop (HIL) testbed for generating cyber-attack and physical fault datasets and demonstrating threat detection algorithms in a real building automation system (BAS) environment. This testbed combines hardware (i.e., real BAS with local HVAC controllers and a physical network) with software (i.e., high-fidelity models to represent behaviors of building envelope and HVAC energy systems), enabling emulations of realistic threats. Five HIL experiments, including one baseline without any threats, two with physical faults, and two with cyber-attacks, were conducted to generate datasets containing detailed network traffic and system states. A joint classification framework, incorporating a network analyzer and a physical HVAC fault detector, was proposed to automatically detect cyber-physical abnormalities on BAS at both the network and the physical HVAC levels. The network analyzer comprises a conditional random fields (CRF) based command validator and a statistics-based detection strategy. The fault detector employs a weather and schedule-based pattern matching and feature-based principal component analysis (WPM-FPCA) method. Evaluation of the classification using four metrics from the multi-class confusion matrix revealed an average accuracy of 90.2%, recall of 89.7%, precision of 88.5% and F1-score of 89.2%. Finally, these results demonstrate that the proposed joint classification framework can effectively differentiate between specific types of cyber-attacks (e.g., device reinitialization attack, network Denial-of-Service attack) and physical faults (e.g., air handling unit operational fault, cooling coil valve stuck) in real time for improved building energy management.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Balance of Plant Modeling and Real-Time Hardware-in-the-Loop Integration with the Microreactor Automated Control System

The advent of novel microreactor technology has driven a focused effort to explore safety and efficiency improvements that can be achieved through the use of automated system control. Development of control strategies, especially for initial demonstration, requires an adequate surrogate environment to safely research failure modes and control integration with realistic hardware delay. However, efficiency gains from control strategies are improved when the scope of controller action is expanded to include system-level dynamics such as downstream heat extraction and mass flow. For this reason, a balance-of-plant (BOP) model of a representative microreactor system has been developed using the TRANsient Simulation Framework of Reconfigurable Models library in Modelica. This model captures a reactor and primary NaK coolant loop that represent corresponding system components of the Microreactor Applications Research Validation and EvaLuation (MARVEL) design as well as a secondary coolant loop and heat extraction representative of the Microreactor Agile Non-Nuclear Experimental Test Bed (MAGNET). This model configuration allows for hardware-in-the-loop (HIL) integration with microreactor automated control system (MACS) hardware in real time through a Python-based gRPC client. Real-time simulation of model performance with emulated hardware and communication delay suggests that under independent proportional-integral-derivative control of BOP model drum dynamics and downstream heat extraction, stable power load following is achievable. A slight delay in load following, filtering of high-frequency dynamics, and localized temperature fluctation suggest room for improvement through the development of higher-level control strategies. The simulated coupling of the MAGNET facility lays the groundwork for future digital twin analysis with a coupled MACS-MAGNET HIL demonstration.

McConnell, Jono [ORNL] (ORCID:0000000238984741)↗

A Novel Protection Scheme for Unbalanced Faults in Inverter Dominated Networks: A Computationally Efficient Algorithm for Entry-Level Relays

Microgrids are now a common practice in distribution systems to increase resilience and reliability. However, microgrid protection remains a critical challenge, considering its requirement to operate in both grid connected and islanded, and the variability in fault characteristics under each mode of operation. This paper presents unbalanced power (S unb ) based fault detection algorithm, which considers local voltage and current unbalances to determine faults in the system. S unb is a computationally efficient fault detection algorithm that is suitable for implementation in the programmable logic of entry level protective relays. In addition, the difference in current and voltage unbalance (D n ) is used to determine the fault type. The proposed method demonstrates high sensitivity and selectivity for line-to-ground (LG), line-to-line (LL), and double line-to-ground (LLG) faults, representing the most common faults in distribution systems. It also allows relay coordination with upstream and downstream protection devices in both island and grid connected operation, while preserving grading margins. The same pickup and time multiplier settings of a particular relay for both modes of operation eliminates the need for adaptive settings, which rely on communication networks. Validation was performed with a hardware-in-the-loop (HIL) setup using Typhoon HIL real time simulator interfaced with three entry-level, SEL 751 relays. Results confirmed the algorithm’s ability to discriminate fault conditions, and determine the fault type under both operating modes, maintain fast detection times, and ensure proper protection coordination.

fault classification↗

A Robust Communication-Free Protection Scheme for Islanded Microgrids with Relay Logic and Hardware-in-the-Loop Validation

This paper presents the Imbalance Square Factor (ISF) detection algorithm, an effective, computationally lightweight method for detecting faults in inverter-based microgrids. ISF provides a high magnitude at the time of the fault, which allows for fast detection and coordination between primary and backup relays. The imbalance squared factor, calculated using local voltage and currents, is used for fault detection and coordination among three relays. ISF is validated in hardware-in-the-loop (HIL) implementation inside commercial-grade relay logic (SEL-751). The HIL validation shows that ISF can coordinate primary, secondary, and tertiary relays in the 13-bus system in islanded operation.

Ferrari Maglia, Max [ORNL]↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗

Cyber-Physical Smart Light Control System Integration with Smart Grid using Zigbee

This paper presents a hardware-in-the-loop cyber-physical system architecture design to monitor and control smart lights connected to the active distribution grid. The architecture uses Zigbee-based (IEEE 802.15.4) wireless sensor networks and publish-subscribe architecture to exchange monitoring and control signals between smart-light actuators (SLAs) and a smart-light central controller (SLCC). Each SLA integrated into a smart light consists of a Zigbee-based endpoint module to send and receive signals to and from the SLCC. The SLCC consists of a Zigbee-based coordinator module, which further exchanges the monitoring and control signals with the active distribution management system over the TCP/IP communication network. The monitoring signals from the SLAs include light status, brightness level, voltage, current, and power data, whereas, the control signals to the SLAs include light intensity, turn ON, turn OFF, standby, and default settings. We have used our existing hardware-in-the-loop (HIL) cyber-physical system (CPS) security SCADA testbed to process signals received from the SLCC and respond suitable control signals based on the smart light schedule requirements, system operation, and active distribution grid dynamic characteristics. We have integrated the proposed cyber-physical smart light control system (CPSLCS) testbed to our existing HIL CPS SCADA testbed. We use the integrated testbed to demonstrate the efficacy of the proposed algorithm by real-time performance and latency between the SLCC and SLAs. The experiments demonstrated significant results by 100% realtime performance and low latency while exchanging data between the SLCC and SLAs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling and Feedback Compensator Design for Power-Hardware-in-the-Loop System for Medium-Voltage Grid-Connected Power Converters

Hardware-in-the-loop (HIL) evaluation is a method in which the test subject is split into a physical part and a simulated part, and these parts are connected with interfaces to form a combined physical-numerical system. Power-hardware-in-the-loop (PHIL) systems, where actual hardware is connected to a real-time model, can exhibit issues of instability, inaccuracy and errors when operating in a closed-loop. The challenges of generating a PHIL setup are that, first, because of the limited dynamic response of the different parts of the system, the test results might be inaccurate, and, second, because of the high frequency noise introduced by the sensors to the closed-loop system, it can be difficult to design a compensator for the real-time emulator response, while stabilizing the closed-loop system at the same time. In this paper, different parts of a PHIL system are characterized, and the feedback compensator system design is proposed for the stable operation of the closed-loop PHIL system. The issues as observed in a PHIL system without any compensator are demonstrated using experimental results, and the effectiveness of a first order phase lead compensator is validated.

compensator design↗

Performance Evaluation of Distributed Energy Resource Management Algorithm in Large Distribution Networks

This paper presents performance evaluation of hierarchical optimization and control for distributed energy resource management system (DERMS) in large distribution networks via an advanced hardware-in-the-loop (HIL) platform. The HIL platform provides realistic testing in a laboratory environment, including the accurate modeling of a full-scale distribution system of 11,000 nodes, the DERMS software controller, and 90 power hardware photovoltaics (PVs) and battery inverters. The applied DERMS algorithm is designed based on a realtime optimal power flow algorithm and implemented with acceleration design that performs fast dispatch of simulated PVs and real physical hardware DER devices every 4 seconds.

DERMS↗

Data-Driven Cyber-Attack Detection for PV Farms via Time-Frequency Domain Features

The internetworking of grid-connected power electronics converters (PECs) in photovoltaic (PV) farms has inevitably expanded the cyber-attack surfaces. Here this paper presents a comprehensive study on cyber-attack detection and diagnosis for PEC-enabled PV farms via single waveform sensor to distinguish between normal conditions, open-circuit faults, short-circuit faults, and cyber-attacks. To our knowledge, this has not been attempted before. Firstly, we propose frequency-domain magnitude-based residuals to identify short-circuit faults and a time-domain mean current vector-based feature to distinguish open-circuit faults from other threats. These features can fully reflect the specific physical characteristics of PV farms during threat duration. Secondly, unlike micro phasor measurement units (µPMU) and raw electric waveform-based methods, the proposed innovative features can address novel cyber-attacks that are excluded from the training process. Thirdly, an online hardware-in-the-loop (HIL) testbed using the OPAL-RT real-time digital simulator has verified the effectiveness. The monitoring system runs in real-time while using HIL as an operational solar farm and a National Instruments (NI) data acquisition card as the electric waveform sensor at the point of coupling.

42 ENGINEERING↗

CYDRES: CYber Defense and REsilient System for securing grid-interactive efficient buildings

Smart buildings, especially Grid-interactive Efficient Buildings (GEBs), suffer from cyber-attacks and physical faults due to the integration of a large number of sensors and controls, connected devices, and associated communication networks. This study demonstrated a real-time advanced building resilient platform, called CYber Defense and REsilient System (CYDRES), which is deployable for existing and emerging Building Automation Systems (BASs). CYDRES aims to empower GEBs with cyber-attack-immune capabilities through multi-layer prevention and adaptation mechanisms to monitor, detect, and respond to cyber-attacks and physical operational faults. CYDRES is demonstrated through real-time experiments in a Hardware-in-the-Loop (HIL) testbed.

Building automation system, Cyber-attacks, Physica↗

Microgrid Fast Charging Station (MFCS) Design Platform Project (Summary Report)

This report documents the important steps and outcomes of the Microgrid Fast Charging Station (MFCS) Design Platform project, executed by XENDEE Corporation and its testing and validation by Idaho National Laboratory (INL). This final summary report builds on the first summary released on April 30th, 2021 and adds the final results from the Hardware in the Loop (HIL) simulations and tests, which have been completed July 14th 2021. With this report XENDEE Corporation and Idaho National Laboratory conclude the first version of the Microgrid Fast Charging Station (MFCS) Design Platform as well as all related tests and validations for two in-depth case studies for islanded and non-islanded operation. The platform itself utilizes XENDEE’s advanced modeling systems and INL’s HIL system to ensure project viability and technical feasibility. It also intelligently maps all cables, transformers, and distributed technology interactions to anticipate and mitigate problems during peak usage or adverse conditions. Finally, the system is designed to optimize dispatch and generation at each time step of the day allowing the Microgrid to take advantage of energy sales to the utility and best manage the charging of an electrical fleet. This allows operators to reliably build bankable Microgrid systems and to operate them to reach the maximum efficiency even under the dynamic needs of electric vehicle fast charging

24 POWER TRANSMISSION AND DISTRIBUTION↗