Investigating Performance of Geothermal Reservoirs With Bi-Directional Heat Transfer for Seasonal Thermal Storage Using Thermal-Hydraulic Reservoir Simulations
This paper presents initial simulation results of deep subsurface seasonal thermal storage of waste heat from a natural gas-fired power plant during the summer months for providing heating during winter months at the Cornell University main campus in Ithaca, New York. An injection temperature profile is calculated with the MEnU tool and numerical reservoir simulations are conducted with the simulator FALCON. Both a porous medium and large single fracture geothermal reservoir are considered at about 3 km depth with initial reservoir temperature of 75 degrees C. Simulations indicate that a much smaller reservoir - which is technically easier and less risky to develop - is sufficient when operating the reservoir for seasonal thermal storage instead of for continuous heat production. For example, storing 13 GWh of heat seasonally in a 100 m thick porous medium based on the Galway formation requires about 65 m of well spacing to limit the yearly variation in production temperature to 10 degrees C. Operating this reservoir for continuous heat production would require a well spacing of 365 m to limit the thermal decline to 10 degrees C after 10 years. Neglecting wellbore heat losses and assuming uniform and homogeneous properties, a round-trip thermal efficiency of 100% can be obtained if the yearly averaged injection temperature matches the initial reservoir temperature.